HP Performance Optimized Data Center (POD) 40cp manual Transformers and switchboards

Page 45

Each external panel is secured through key lock hardware.

The following locations have been prewired for your own security upgrades.

Callout

Description

 

 

1

Prewired junction box locations

 

 

2

Card reader locations

 

 

3

Internal camera locations

 

 

4

External camera locations

 

 

Transformers and switchboards

HP offers several transformers and switchboards to supply your power needs.

On-site connections include:

From your main facility power to the primary side of the transformer

From the transformer to the switchboard

From the feeder breaker lugs within the switchboard assembly to the HP POD

The standard cables should allow for placing the transformer and switchboard approximately 3.0 m (10 ft) away from the HP POD. Installation costs assume that connections are within the 3.0 m (10 ft) recommendation. If you place the transformer and switchboard more than 3.0 m (10 ft) away from the HP POD, additional planning and costs are involved.

Water distribution kit

HP recommends using the optional water distribution kit to provide water to your HP POD. For more information about the kit, see Water distribution kit components ("Water distribution kit components (optional)" on page 16).

NOTE: The water distribution kit pipes are flushed prior to shipment.

The water distribution kit is enclosed within a 10 ft ISO container that includes internal lighting and heating. The heater comes equipped with a programmable thermostat that you can set to run as needed to ensure the water temperature inside does not drop below freezing.

Optional components 45

Image 45
Contents Part Number March 2009 First Edition HP Performance-Optimized Datacenter User GuideIntended audience Contents Water precautions Water temperature HP POD frequently asked questionsHP POD troubleshooting Acronyms and abbreviations Index Optimum environment Site requirementsLocation considerations Moving the HP PODAvailable to connect to central facility infrastructure Cooling water Power Drain optionalEnvironmental considerations Temperature considerationsWork space requirements Callout ConnectionLeveling requirements Component documentationGrounding requirements Lightning protectionSafety considerations Safety informationOperator safety Component health Safety considerations Component identification HP POD componentsHP POD components Component Description External emergency components Component Description HP POD emergency componentsHP POD panel locations Internal emergency components Component DescriptionComponent Description ∗Optional component Transformer and switchboard components optionalWater distribution kit components optional HP POD contents InstallationPreinstallation checklist Required toolsComponent Quantity Part number Installing the HP POD using the optional components Connecting the waterPipe wrench Installation Installation Installation Connecting the power Installation Commissioning the HP POD Installation Cooling system Water supply temperatureHP POD cooling system Controlling the fan speedCondensation management HP POD drainsPull the overhead down Leak detection Water quality requirements and specifications Acceptable water quality specificationsWater quality requirements Water temperature Water precautionsFrost damage Plumbing materials to avoidElectrical busway Power managementPower distribution Rack power Panels BMS panel Assd panelElectrical busway enclosed circuit breaker EPO PanelEPO modes Epms panel Fire alarm control panelFan control panel House panelSecurity panel location Using a building management system BMS Connecting the HP POD to the BMSBuilding management system BMS alarms Managing BMS settings from the HP POD Safety and security alarms Fire alarm sequence of operations Alarm Meaning Solution Building management system Optional components Water distribution kit Transformers and switchboardsCallout Specification Water distribution kit power requirementsFrequently asked questions HP POD frequently asked questionsQuestion Answer Drain pans or the water main drain pan. The additional water Troubleshooting HP POD troubleshootingIssue Resolution HP POD specifications SpecificationsElectrical specifications Features SpecificationsWater specifications Feature SpecificationWater supply specifications with a water distribution kit Rack specifications Standard HP POD racks AN982A Feature SpecificationThermal and air flow performance Environmental specifications Water distribution kit specificationsFor more information, see Water specifications on Maintenance HP contact information Before you contact HPRegulatory compliance notices Bsmi notice Chinese notice Korean class a notice Japanese class a noticeClass a equipment Acronyms and abbreviations Uninterruptible power system Power distribution unitNational Electrical Manufacturers Association Performance-Optimized DatacenterFire alarm control panel 13, 14, 35 IndexFan Fan control panel 14, 35 Fan speed Safety considerations Index