Specifications
HP POD specifications
Features | Specifications |
|
|
Dimensions | 40 ft x 8 ft x 9.5 ft |
|
|
Maximum weight | 30,000 lb (empty)- 101,000 lb |
|
|
Maximum power/ cooling | • 450 kW (Standard POD) |
| • 605 kW (High density POD) |
|
|
Maximum rack quantity | 22 racks |
|
|
Rack Units (RU) per rack | 50 RU |
|
|
Rack Units (RU) maximum | 1100 RU |
|
|
Nominal power/ cooling per rack | 25 kW |
|
|
Maximum power/ cooling per rack | 35 kW |
|
|
Power input voltage | 415 VAC, 3 Phase, 50/60 Hz, with neutral |
|
|
Power distributed internally | Through 2 400A electrical busways |
| 240/415 VAC, 50/60 Hz |
|
|
Customer access | |
| Two 3 ft x 7 ft doors to the cold aisle (customer access) |
| Four 6 ft x 7 ft doors to the hot aisle (rear component access) |
|
|
Network supported | Bulk cable |
| Bulk cable |
| (Optional) External rated DEMARC box |
|
|
Electrical specifications
Panel information
Feature | Electrical busway panel | House panel | |
|
|
|
|
Number of panels | • 2 | (Standard HP POD) | 1 |
| • 3 | (High density HP POD) |
|
|
|
| |
Amps (per panel) | 400A | 225A | |
|
|
|
|
Poles (per panel) | 1 |
| |
|
|
|
|
Phases | 3 |
| 3 |
|
|
|
|
Circuit breaker information (Input)