HP Performance Optimized Data Center (POD) 40cp manual Rack specifications

Page 52

Feature

Humidifier

Specification

3.79l/hr (1 gal/hr) domestic water from an alternate supply source

Rack specifications

Standard HP POD racks (AN982A)

Feature

Specification

 

 

U height

50U

 

 

Width

56-mm

 

 

Depth

1,000-mm

 

 

Maximum load weight

3,000 lb

 

 

International shock-mounted HP POD racks (AT052A)

Feature

Specification

 

 

U height

46U

 

 

Width

56-mm

 

 

Depth

1,000-mm

 

 

Maximum load weight

2,760 lb

 

 

Thermal and air flow performance

Maximum thermal and air flow

HP POD specification

performance parameters

 

 

 

Air temperature—Inlet to rack-

Cold aisle setpoint temperature in BMS

mounted components

 

 

 

Chilled water temperature

12°–19°C (55°–65°F)

 

 

Total rack-mounted component air

Variable as required to maintain cold

flow

aisle setpoint temperature

 

 

Chilled water flow rate

240 gal/min (908 l/min) without

 

utility module

 

280 gal/min (1,060 l/min) with

 

utility module

 

 

Chilled water pressure differential at

5 psi max

flow needed to meet thermal

 

specifications

 

 

 

Server heat load

450 kW standard HP POD

 

605 kW high density HP POD

 

 

Specifications 52

Image 52
Contents HP Performance-Optimized Datacenter User Guide Part Number March 2009 First EditionIntended audience Contents HP POD frequently asked questions Water precautions Water temperatureHP POD troubleshooting Acronyms and abbreviations Index Site requirements Optimum environmentLocation considerations Moving the HP PODCooling water Power Drain optional Available to connect to central facility infrastructureTemperature considerations Environmental considerationsWork space requirements Callout ConnectionComponent documentation Leveling requirementsGrounding requirements Lightning protectionSafety information Safety considerationsOperator safety Component health Safety considerations HP POD components Component identificationHP POD components Component Description HP POD emergency components External emergency components Component DescriptionInternal emergency components Component Description HP POD panel locationsComponent Description Transformer and switchboard components optional ∗Optional componentWater distribution kit components optional Installation HP POD contentsRequired tools Preinstallation checklistComponent Quantity Part number Connecting the water Installing the HP POD using the optional componentsPipe wrench Installation Installation Installation Connecting the power Installation Commissioning the HP POD Installation Water supply temperature Cooling systemHP POD cooling system Controlling the fan speedHP POD drains Condensation managementPull the overhead down Leak detection Acceptable water quality specifications Water quality requirements and specificationsWater quality requirements Water precautions Water temperatureFrost damage Plumbing materials to avoidPower management Electrical buswayPower distribution Rack power Panels Assd panel BMS panelElectrical busway enclosed circuit breaker EPO PanelEPO modes Fire alarm control panel Epms panelFan control panel House panelSecurity panel location Connecting the HP POD to the BMS Using a building management system BMSBuilding management system Managing BMS settings from the HP POD BMS alarmsFire alarm sequence of operations Safety and security alarmsAlarm Meaning Solution Building management system Optional components Transformers and switchboards Water distribution kitWater distribution kit power requirements Callout SpecificationHP POD frequently asked questions Frequently asked questionsQuestion Answer Drain pans or the water main drain pan. The additional water HP POD troubleshooting TroubleshootingIssue Resolution Specifications HP POD specificationsElectrical specifications Features SpecificationsFeature Specification Water specificationsWater supply specifications with a water distribution kit Standard HP POD racks AN982A Feature Specification Rack specificationsThermal and air flow performance Water distribution kit specifications Environmental specificationsFor more information, see Water specifications on Maintenance Before you contact HP HP contact informationRegulatory compliance notices Bsmi notice Korean class a notice Japanese class a notice Chinese noticeClass a equipment Acronyms and abbreviations Power distribution unit Uninterruptible power systemNational Electrical Manufacturers Association Performance-Optimized DatacenterIndex Fire alarm control panel 13, 14, 35Fan Fan control panel 14, 35 Fan speed Safety considerations Index