Front view shown
Utilities
Consider the proximity to required utilities, such as power, water, and network connections. While the required utilities can be brought to nearly any selected site, there is the potential for increased costs and decreased efficiency when the HP POD 20c is located farther from the utility sources.
For utility clearance information, see "Dimensions and clearances (on page 8)."
Humidifier water supply
The HP POD 20c requires supply water for the humidifier. The supply water must meet the following requirements.
Requirement | Specification |
| |
|
|
|
|
Pressure | Between 20 and 110 psi, 0.1 and 0.8 MPa |
| |
Temperature | Between 1º and 40°C (33º and 104°F) |
| |
Minimum flow rate | 1.45 lpm (0.12 gpm) |
| |
Connection | 1.9 cm (.75 in) G |
| |
|
| Adapter to 1.9 cm (.75 in) FPS |
|
Hardness | No greater than 40°fH (equal to 400 ppm of CaCO3) |
| |
Conductivity | 100 to 1250 μS/cm |
| |
Organic compounds | None |
| |
Type of water | Drinking water. Do not use |
| |
Instant water fill flow | 0.6 lpm (0.16 gpm) |
| |
rate |
|
| |
Humidifier | For the exact requirements, see the humidifier documentation. |
| |
|
|
|
|
IMPORTANT: If your water is out of range, consult a water quality expert.
In addition to the previous requirements, observe the following requirements and recommendations: