York DFAH, DFAA Section III Filters, Return AIR Requirements, Blend AIR Installations

Page 10

107272-UIM-B-1105

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DFAH Furnaces:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If a matching cooling coil is used, it may be placed directly on the fur-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nace outlet and sealed to prevent leakage. Follow the coil instructions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

for installing the supply plenum. On all installations without a coil, a

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

removable access panel is recommended in the outlet duct such that

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

smoke or reflected light would be observable inside the casing to indi-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

cate the presence of leaks in the heat exchanger. This access cover

Blend Air

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

shall be attached in such a manner as to prevent leaks.

Flex Duct

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RETURN AIR REQUIREMENTS

Blend Air

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Closet Installations

Damper

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Additional Requirements

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Additional requirements for floor and ceiling return system for closet

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

installed sealed combustion heating appliances are given in the next

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

paragraph.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Floor or Ceiling Return Air System

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Floor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Listed in the next paragraph are the conditions to be met by Manufac-

WARM AIR DUCT

DUCT CONNECTOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

tured Home Manufacturers to have U.L. acceptance of in-floor or ceiling

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FIGURE 14: Floor Installation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

return air systems of closet installed direct vent forced air heating appli-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SECTION III: FILTERS

ances for Manufactured Homes to be sold in the United States.

1.

The return air opening into the closet, regardless of location, is to

FILTER INSTALLATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

be sized not less than 16” X 24” (40.6 cm x 101.6 cm).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

All applications require the use of a filter. A standard air filter is located

2.

If the return air opening is located on the floor of the closet (versus

in the return filter rack on the louvered door. The air filter(s) must be

 

the vertical front or side wall), the opening is to be provided with

 

replaced with air filter(s) that

are the same size and same type.

 

means to prevent its inadvertent closure by a flat object placed

over the opening.

Replacement filter size is shown in Table 5.

 

3.The cross sectional area of the return duct system (when located in the floor or ceiling of the manufactured home) leading into the closet is to be not less than 16” X 24” (40.6 cm x 101.6 cm).

4.At least one register is to be located where likelihood of its being covered by carpeting, boxes, and other objects is minimized.

5.Materials located in the return duct system have a flame spread classification of 200 or less.

6.Non-combustible pans having 1” (2.5 cm) upturned flanges are located beneath openings in the floor return duct system.

7.Wiring materials located in the return duct system conform to Arti- cle 300-22 (B&C) of the National Electrical Code (NFPA-70).

8.Fuel piping is not run in or through the return duct system.

9.The negative pressure in the closet as determined by test with the air circulating fan operating at high heating speed and the closet door closed is to be not more negative than minus 0.05 inches (1.2 kPa) water column.

10.For floor return systems, the manufactured home manufacturer or installer shall affix a prominent marking on or near the appliance where it is easily read when the closet door is open. The marking shall read:

HAZARD OF ASPHYXIATION, DO NOT COVER OR RESTRICT FLOOR OPENING.

BLEND AIR INSTALLATIONS

If a blend air ventilation system is installed, the 5” (12.7 cm) diameter knockout in the top cover must be removed. The blend air damper is to be placed on the top cover and secured with screws as shown in Figure

14.The power wires for the Blend Air Damper are inserted through the 7/8” (2.22 cm) hole in the top cover. The wires to the Blend Air Damper will be connected as shown in Figure 24. Refer to the Blend Air Installa- tion Manual to complete the installation.

Downflow Filters:

There are two types of downflow filter racks.

1.FURNACE FILTER RACK: A return filter rack is with two standard throwaway type filters are supplied on all models. The return filter rack is located on the inside of the louvered door. This type of filter rack is designed for two standard air filters only. Pleated Media or Washable Filters cannot be used in this filter rack because they cause too much pressure drop causing a reduction in airflow.

2.EXTERNAL RETURN FILTER GRILLE: The second type is an external return air filter grille that can only be used in applica- tions where the furnace is installed in a closet. This type of fil- ter grille is typically installed in a closet door or wall with the filters located within 12" (30.5 cm) of the return air opening of the fur- nace. There must be a minimum clearance of 6" (15.2 cm) between the front of the furnace and the closet door and/or the fur- nace and the filter grille to prevent the return air flow from being obstructed. Refer to Table 1 Unit Clearances to Combustibles.

a.If the standard throwaway filter are used the external filter grille must have a minimum area of 540 in² (3483 cm²) which would equal a 15" X 36" (38.1 cm x 91.4 cm) filter grille.

b.If the Pleated Media or Washable Filters are used the exter- nal filter grille must have a minimum area of 684 in² (4413 cm²) which would equal a 18" X 38" (38.1 cm x 91.4 cm) filter grille. The increased area is to reduce the pressure drop across the air filter.

c.Consideration should be given when locating the return filter grille for maintenance.

d.Any filter that has a large pressure drop should be checked to be sure the pressure drop caused by the air filter will not pre- vent the furnace from operating within the rise range, speci- fied on the rating plate and in Table 8. If the furnace does not operate within the specified rise range then a larger air filter or an air filter that has a lower pressure drop must be installed.

TABLE 5: Filter Sizes

Input / Output

CFM

Top Return

BTU/H (kW)

(m3/mm)

Filter In. (cm)

66 / 53 (19.34 / 15.53)

1050 (29.73)

(2) 14 x 20 (35.56 x 50.8)

84 / 67 (24.62 / 19.64)

1250 (35.40)

(2) 14 x 20 (35.56 x 50.8)

10

Unitary Products Group

Image 10
Contents List of Sections Section I SafetyFor Installation List of FiguresSafety Requirements Specific Safety Rules and PrecautionsFollowing requirements to be met Combustion AIR Quality List of Contaminants InspectionTOP Front Back Sides AIR Inlet Roof Jack DUCT1 Check Certifications / ApprovalsFurnace Location and Clearances Piping FLOOR/BOTTOMSection II Ductwork Duct system’s design and installation mustDuctwork General Information Duct Design Canada Duckwork InstallationAir Distribution Systems Clearance Requirements CanadaAir Distribution Systems Duct Connectors Installation of Screw Attachment Duct ConnectorInstallation of the Furnace Installation of TAB Attachment Duct ConnectorsFurnace and Air Conditioner Installations MBH CFMSection III Filters Blend AIR InstallationsReturn AIR Requirements Section IV OIL Piping OIL SafetyConnect Fuel Lines Example Installation and Checking of OIL PipingEffect of Elevation on OIL Burner Firing AFGElectrical Power Connections Section V Electrical PowerSolenoid Wiring ONE Pipe SystemEighteen gauge thermostat wire is highly recommended LOW Voltage Control Wiring ConnectionsVent and Combustion AIR Safety Section VI VENT/COMBUSTION AIR SystemInstallation in Snow Regions Existing Furnace ReplacementNEW Home Installation Exterior Roof Jack ExtensionLocating and Cutting Roof Jack Opening Installing Roof Jack in RoofConnect Roof Jack to Furnace Interior ExtensionsSecure Roof Jack to Roof Complete Installation, as requiredRoof Jack Adjustable Height with Interior ExtensionDfaa Models Dfah Models UIM-B-1105 Vent System Installing Ceiling RingVent Clearances Home Layout Canadian Installations1 US Installation2 Section VII Safety Controls Specifications Section Viii START-UP AdjustmentsSTART-UP and Adjust Burner Ignition System Sequence Adjustment of OIL Pump PressureAdjustment of Temperature Rise SET Combustion with InstrumentsApplying Filter Pressure Drop to Final ProcedureInstall Furnace Doors Determine System AirflowItem Number Description Dfaa ModelDfah Model Section IX Wiring Diagram OIL-FIRED Furnace Wiring Diagram for Dfaa Oil-Fired FurnaceWiring Diagram for Dfah Oil Furnace Unitary Products Group UIM-B-1105Preparation of Combustion Chamber Installation of Burner and ControlsSection X GAS GUN Burner GAS PipingLocate GAS LEAKS, USE a Soap Solution Testing Piping for LeaksGAS Piping Installation Length of Pipe Nominal Diameter of Pipe in Inches mmGAS Orifice Conversion for Propane LP High Altitude GAS Orifice ConversionPropane GAS Sizing Furnace InputNatural GAS Gas Firing Rate Orifice Air ShutterPurging Section XI START-UP AdjustmentsCalculating the Furnace Input Natural GAS USA use the following formula to calculate the furnace input Checking the GAS Pressures Adjustment of Manifold GAS PressureInitial Start UP Inlet GAS Pressure RangeIf Furnace Fails to Operate Properly Observing Burner OperationPerformance Check Electrode Orientation and Gap Section XII Wiring Diagram GAS Conversion Burner Wiring Diagram for Dfah Gas Gun Unitary 5005 Norman Product York Group Drive 73069 Copyright by York International Corp . All rights reserved