York DFAA, DFAH Initial Start UP, Checking the GAS Pressures, Adjustment of Manifold GAS Pressure

Page 35

INITIAL START UP

1.Read the applicable sequence of gas control operation in the Operation and Troubleshooting section before proceeding.

2.Move the gas valve control switch to the “OFF” position.

3.Adjust the primary air. Set the damper to the start up settings.

4.On new gas line installations, air may be trapped in the line, the burner may experience several lockouts until all the air is purged from the lines.

5.Turn on the main electrical power and set the thermostat to call for heat. Allow the burner to run a MINIMUM of 5 minutes to purge combustion chamber and appliance heat exchanger.

6.Set the thermostat below room temperature, shutting the burner “OFF”.

7.Move the gas valve control switch to the “ON” position.

8.Set the thermostat or operating control to call for heat. The burner will start and go through the applicable sequence of burner/pri- mary gas control operation, refer to step 1.

9.Once burner is running, adjust the orifice manifold pressure regu- lator as described in Pressure Regulator Adjustment.

Be sure to relight any gas appliances that were turned off at the start of this input check.

CHECKING THE GAS PRESSURES

1.The pressure ports on the gas valve are marked OUT and INLET.

2.The manifold pressure must be taken at the port marked OUT.

3.The inlet gas supply pressure must be taken at the port marked IN LET.

4.Using a 3/32” (0.2 cm) Allen wrench, loosen the set screw by turn- ing it 1 turn counter clockwise. DO NOT REMOVE THE SET SCREW FROM THE PRESSURE PORT.

5.Use the 4” (10.2 cm) piece of 3/8” (0.9 cm) tubing to connect the positive side of the manometer to the gas valve pressure refer- ence port. Refer to Figure 43 for connection details.

TABLE 20: Inlet Gas Pressure Range

INLET GAS PRESSURE RANGE

 

Natural Gas

Propane (LP)

Minimum

4.5” W.C. (1.12 kPa)

8.0” W.C. (1.99 kPa)

 

 

 

Maximum

10.5” W.C. (2.61 kPa)

13.0” (3.24 kPa) W.C.

 

 

 

IMPORTANT: The inlet gas pressure operating range table specifies the minimum and maximum gas line pressures required for safe fur- nace operation.

The minimum inlet gas pressure required to obtain the BTU input speci- fied on the rating plate and in these instructions is shown below:

7.0” w.c. (1.74 kPa) for Natural Gas

11.0” w.c. (2.74 kPa) for Propane (LP) Gas

107272-UIM-B-1105

ADJUSTMENT OF MANIFOLD GAS PRESSURE

Manifold gas pressure may be measured at the gas valve.

Turn gas off at the ball valve or gas cock on gas supply line before the gas valve. Find the pressure ports on the gas valve marked OUT and INLET.

IMPORTANT: The cap for the pressure regulator must be removed entirely to gain access to the adjustment screw. Loosening or tightening the cap does not adjust the flow of gas.

1.Refer to Figure 42 for location of pressure regulator adjustment cap and adjustment screw on main gas valve.

2.Adjust manifold pressure by adjusting gas valve regulator screw for the appropriate gas per the following:

TABLE 21: Nominal Manifold Pressure

NOMINAL MANIFOLD PRESSURE

Natural Gas

3.5" w.c. (0.87 kPa)

Propane (LP) Gas

3.5" w.c. (0.87 kPa)

Outlet

 

Vent Port

Pressure Port

 

 

 

Inlet

 

Outlet

Wrench

OFF

 

Boss

 

Inlet

ON

 

Pressure Port

Main Regulator

1/4” Quick Connect

On/Off Switch

Adjustment

 

Electrical Terminals

(Shown in ON position)

FIGURE 42: Gas Valve

IMPORTANT: If gas valve regulator is turned in (clockwise), manifold pressure is increased. If screw is turned out (counter clockwise), mani- fold pressure will decrease.

3.After the manifold pressure has been adjusted, re-calculate the furnace input to make sure you have not exceeded the specified input on the rating plate. Refer to “CALCULATING THE FURNACE INPUT (NATURAL GAS)”.

4.Once the correct BTU (kW) input has been established, turn the gas valve to OFF and turn the electrical supply switch to OFF; then remove the flexible tubing and fittings from the gas valve pressure tap and tighten the pressure tap plug using the 3/32” Allen wrench.

5.Turn the electrical and gas supplies back on, and with the burners in operation, check for gas leakage around the gas valve pressure port for leakage using an approved gas detector, a non-corrosive leak detection fluid, or other leak detection methods.

The manifold pressure must be checked with the screw-off cap for the gas valve pressure regulator in place. If not, the manifold pres- sure setting could result in an over-fire condition. A high manifold pressure will cause an over-fire condition, which could cause pre- mature heat exchanger failure. If the manifold pressure is too low, sooting and eventual clogging of the heat exchanger could occur. Be sure that gas valve regulator cap is in place.

Unitary Products Group

35

Image 35
Contents List of Figures Section I SafetyFor Installation List of SectionsFollowing requirements to be met Specific Safety Rules and PrecautionsSafety Requirements Inspection Combustion AIR Quality List of ContaminantsPiping FLOOR/BOTTOM Check Certifications / ApprovalsFurnace Location and Clearances TOP Front Back Sides AIR Inlet Roof Jack DUCT1Ductwork General Information Duct system’s design and installation mustSection II Ductwork Clearance Requirements Canada Duckwork InstallationAir Distribution Systems Duct Design CanadaAir Distribution Systems Installation of Screw Attachment Duct Connector Duct ConnectorsMBH CFM Installation of TAB Attachment Duct ConnectorsFurnace and Air Conditioner Installations Installation of the FurnaceReturn AIR Requirements Blend AIR InstallationsSection III Filters Connect Fuel Lines OIL SafetySection IV OIL Piping AFG Installation and Checking of OIL PipingEffect of Elevation on OIL Burner Firing ExampleONE Pipe System Section V Electrical PowerSolenoid Wiring Electrical Power ConnectionsSection VI VENT/COMBUSTION AIR System LOW Voltage Control Wiring ConnectionsVent and Combustion AIR Safety Eighteen gauge thermostat wire is highly recommendedExterior Roof Jack Extension Existing Furnace ReplacementNEW Home Installation Installation in Snow RegionsInterior Extensions Installing Roof Jack in RoofConnect Roof Jack to Furnace Locating and Cutting Roof Jack OpeningInterior Extension Complete Installation, as requiredRoof Jack Adjustable Height with Secure Roof Jack to RoofDfaa Models Dfah Models UIM-B-1105 Vent Clearances Installing Ceiling RingVent System Home Layout Canadian Installations1 US Installation2 Section VII Safety Controls START-UP and Adjust Burner Section Viii START-UP AdjustmentsSpecifications SET Combustion with Instruments Adjustment of OIL Pump PressureAdjustment of Temperature Rise Ignition System SequenceDetermine System Airflow Final ProcedureInstall Furnace Doors Applying Filter Pressure Drop toDfah Model Dfaa ModelItem Number Description Wiring Diagram for Dfaa Oil-Fired Furnace Section IX Wiring Diagram OIL-FIRED FurnaceUIM-B-1105 Wiring Diagram for Dfah Oil Furnace Unitary Products GroupGAS Piping Installation of Burner and ControlsSection X GAS GUN Burner Preparation of Combustion ChamberLength of Pipe Nominal Diameter of Pipe in Inches mm Testing Piping for LeaksGAS Piping Installation Locate GAS LEAKS, USE a Soap SolutionHigh Altitude GAS Orifice Conversion GAS Orifice Conversion for Propane LPGas Firing Rate Orifice Air Shutter Sizing Furnace InputNatural GAS Propane GASCalculating the Furnace Input Natural GAS Section XI START-UP AdjustmentsPurging USA use the following formula to calculate the furnace input Inlet GAS Pressure Range Adjustment of Manifold GAS PressureInitial Start UP Checking the GAS PressuresPerformance Check Observing Burner OperationIf Furnace Fails to Operate Properly Electrode Orientation and Gap Section XII Wiring Diagram GAS Conversion Burner Wiring Diagram for Dfah Gas Gun Copyright by York International Corp . All rights reserved Unitary 5005 Norman Product York Group Drive 73069