York DFAA, DFAH Exterior Roof Jack Extension, Existing Furnace Replacement, NEW Home Installation

Page 15

107272-UIM-B-1105

EXTERIOR ROOF JACK EXTENSION

Application

Available to comply with instances in which the roof jack crown needs to be raised to meet a roof clearance requirement. One extension will raise the roof jack crown by 18” 45.7 cm).

ROOF JACK

Failure to follow all venting instructions can result in fire, asphyxiation, or explosion.

Only use the appropriate roof jack. See Figures 26, 27, 30, and 31 for correct application.

Do not exceed the maximum height as determined from Table 9. Installer should allow an additional 1-1/2" (3.8 cm) travel before the flue pipe assembly is fully extended against the built-in stop. This provides an additional safe- guard against the flue assembly being pulled from the roof jack during transportation or other stress conditions.

EXISTING FURNACE REPLACEMENT

If this furnace replaces an existing furnace, do the following:

1.If a 2nd roof, roof cap or addition has been made to the existing roof of the home, remove the old roof jack completely! To avoid the possibility of an improperly installed pipe or gaps in the old roof jack, INSTALL A NEW ROOF JACK. Your ceiling and roof height will determine the correct roof jack to use.

2.After unpacking the roof jack, check the rain caps. Insure they are not damaged, tilted or crooked. Do not twist, crush or sit on the roof caps during installation. Damaged roof caps will cause improper furnace operation. The furnace will not heat properly and could result in explosion.

3.Before inserting the roof jack into the furnace top, inspect the fur- nace flue and combustion air opening for debris or insulation which might have fallen in during pre-installation steps. Do not pro- ceed unless all debris has been cleaned out or removed.

4.After installing roof jack on furnace top collar, check to make sure there is no gap in back or side between the pipe collar and the fur- nace casing top.

5.Use only the pipes provided with the roof jack assembly. Do not add to or adapt other sheet metal pipes. Do not cut, insert or add other pipes to this assembly.

6.In no case should there be a gap between sections of the flue pipe or the combustion air pipe. If necessary to prevent excessive air leakage, the installer should seal joints in the combustion air tube with Chemcaulk 900 sealant or other suitable sealant.

NEW HOME INSTALLATION

If this furnace is installed in a new home do the following:

1.Inspect the furnace top collars for signs of insulation or ceiling debris which might have fallen in during cutting of the ceiling and roof holes. Remove all debris before continuing.

The vent and combustion air openings in the top of the furnace must be free of construction debris before the Roof Jack is installed. Failure to ensure that these openings are free will result in excessive amounts of CARBON MONOXIDE and elevated heat exchanger temperatures which can lead to premature heat exchanger failure, resulting in a fire or explosion or cause damage to the furnace or some of its components that will result in property damage and loss of life.

2.After unpacking the roof jack, check the rain caps. Insure they are not damaged, tilted or crooked. Do not twist, crush or sit on the roof caps during installation. Damaged roof caps will cause improper furnace operation. The furnace will not heat properly and could result in explosion.

3.Before inserting the vent pipe into the furnace top, inspect the fur- nace flue and combustion air opening for debris or insulation which have fallen in during pre-installation steps. Do not proceed unless all debris have been cleaned out or removed.

4.After installing roof jack on furnace top collar, check to make sure there is no gap in back or side between the pipe collar and the fur- nace casing top. If necessary to prevent excessive air leakage, the installer should seal joints in the combustion air tube with Chem- caulk 900 sealant or other suitable sealant.

INSTALLATION IN SNOW REGIONS

When the combustion air pipe inlet is covered or blocked with snow, the furnace will not operate properly due to the depleted combustion air supply.

Therefore, if the furnace will be located in regions where snow accumu- lation on the roof exceeds 4" or in H.U.D. Snow Load Zones, a roof jack extension and PVC combustion air inlet extension is recommended. Refer to Figure 26 or 27.

COMBUSTION AIR INLET

All combustion air pipe and fittings must conform to American National Standards Institute (ANSI) standards and American Society for Testing and Materials (ASTM) standards D1785 (Schedule 40 PVC), D2665 (PVC-DWV), F891 (PVC-DWV cellular core). D2241 (SDR-21 and SDR-26 PVC), D2261 (ABS-DWV), or F628 (Schedule 40 ABS. Pipe cement and primer must conform to ASTM Standards D2564 (PVC) or D2235 (ABS).

1.Mark vertical combustion air inlet centerline on ceiling. Cut hole for combustion air inlet piping. Clearance to combustible materials is not required.

2.Cut hole in roof. Provide minimum 12” (30.5 cm) vertical separa- tion between combustion air inlet pipe and roof jack vent cap. Clearance to combustible materials is not required.

3.Route piping through ceiling and holes. Provide firestop as required.

4.Insert combustion air inlet coupling into casing. See Figure 26 or 27.

5.Slide PVC pipe into coupling. Use a hose clamp to secure the PVC pipe to the coupling.

6.Complete piping through roof. Provide flashing at roof penetration.

7.Prepare elbow assembly. See Figure 25. Insert screen into elbow socket. Secure in place with street elbow (or nipple).

8.PVC pipe can be straight through the roof or it can be offset by using up to 4-90° elbows. Horizontal PVC pipe can be up to 10 ft. (3.1 m) long in any direction from the furnace vent connection. Ver- tical PVC pipe can be up to 10 ft. (3.1 m) in length.

90° Street

90°

Elbow

Elbow

 

Screen

Pipe to Furnace

FIGURE 25: Elbow Assembly

9.Attach elbow assembly to combustion air inlet piping. See Figure 26 or 27. Inlet must be minimum 6” (15.2 cm) above highest antic- ipated snow level, but no more than 24” 61.0 cm) above roof.

Unitary Products Group

15

Image 15
Contents List of Figures Section I SafetyFor Installation List of SectionsSpecific Safety Rules and Precautions Safety RequirementsFollowing requirements to be met Inspection Combustion AIR Quality List of ContaminantsPiping FLOOR/BOTTOM Check Certifications / ApprovalsFurnace Location and Clearances TOP Front Back Sides AIR Inlet Roof Jack DUCT1Duct system’s design and installation must Section II DuctworkDuctwork General Information Clearance Requirements Canada Duckwork InstallationAir Distribution Systems Duct Design CanadaAir Distribution Systems Installation of Screw Attachment Duct Connector Duct ConnectorsMBH CFM Installation of TAB Attachment Duct ConnectorsFurnace and Air Conditioner Installations Installation of the FurnaceBlend AIR Installations Section III FiltersReturn AIR Requirements OIL Safety Section IV OIL PipingConnect Fuel Lines AFG Installation and Checking of OIL PipingEffect of Elevation on OIL Burner Firing ExampleONE Pipe System Section V Electrical PowerSolenoid Wiring Electrical Power ConnectionsSection VI VENT/COMBUSTION AIR System LOW Voltage Control Wiring ConnectionsVent and Combustion AIR Safety Eighteen gauge thermostat wire is highly recommendedExterior Roof Jack Extension Existing Furnace ReplacementNEW Home Installation Installation in Snow RegionsInterior Extensions Installing Roof Jack in RoofConnect Roof Jack to Furnace Locating and Cutting Roof Jack OpeningInterior Extension Complete Installation, as requiredRoof Jack Adjustable Height with Secure Roof Jack to RoofDfaa Models Dfah Models UIM-B-1105 Installing Ceiling Ring Vent SystemVent Clearances Home Layout Canadian Installations1 US Installation2 Section VII Safety Controls Section Viii START-UP Adjustments SpecificationsSTART-UP and Adjust Burner SET Combustion with Instruments Adjustment of OIL Pump PressureAdjustment of Temperature Rise Ignition System SequenceDetermine System Airflow Final ProcedureInstall Furnace Doors Applying Filter Pressure Drop toDfaa Model Item Number DescriptionDfah Model Wiring Diagram for Dfaa Oil-Fired Furnace Section IX Wiring Diagram OIL-FIRED FurnaceUIM-B-1105 Wiring Diagram for Dfah Oil Furnace Unitary Products GroupGAS Piping Installation of Burner and ControlsSection X GAS GUN Burner Preparation of Combustion ChamberLength of Pipe Nominal Diameter of Pipe in Inches mm Testing Piping for LeaksGAS Piping Installation Locate GAS LEAKS, USE a Soap SolutionHigh Altitude GAS Orifice Conversion GAS Orifice Conversion for Propane LPGas Firing Rate Orifice Air Shutter Sizing Furnace InputNatural GAS Propane GASSection XI START-UP Adjustments PurgingCalculating the Furnace Input Natural GAS USA use the following formula to calculate the furnace input Inlet GAS Pressure Range Adjustment of Manifold GAS PressureInitial Start UP Checking the GAS PressuresObserving Burner Operation If Furnace Fails to Operate ProperlyPerformance Check Electrode Orientation and Gap Section XII Wiring Diagram GAS Conversion Burner Wiring Diagram for Dfah Gas Gun Copyright by York International Corp . All rights reserved Unitary 5005 Norman Product York Group Drive 73069