York DFAH, DFAA Ignition System Sequence, Adjustment of OIL Pump Pressure, Filter Performance

Page 24

107272-UIM-B-1105

IGNITION SYSTEM SEQUENCE

1.Turn the oil supply ON at external valve on the oil pump, and/or at the oil tank.

2.Set the thermostat above room temperature to call for heat.

3.System start-up will occur as follows:

a.The burner motor will start and come up to speed.

b.Shortly after the burner motor starts-up, the ignition trans- former will provide 10,000 volts through the electrods causing a spark that will last approximately 15 seconds.

c.The solenoid valve on the oil pump will open providing oil flow to the nozzle.

d.The oil vapor will ignite. The cad cell flame detector will detect the flame. The resistance will drop below 1600 ohms.

e.After flame is established, the supply air blower will start when the fan switch reaches approximately 110° F (43.3° C).

f.After flame is extinguished, the supply air blower will continue to operate until the air temperature at the fan switch is below 90o F (32.2o C).

FIRE OR EXPLOSION HAZARD

Failure to follow the safety warnings exactly could result in serious injury, death or property damage.

Pressing the reset button repeatedly could cause a pool of oil to form in the bottom of the chamber. If ignited, could result in a very dangerous situation which could result in personal injury, property damage, and/or death.

IMPORTANT: Burner ignition may not be satisfactory on first start-up due to residual air in the oil line or until pump pressure is adjusted. The ignition control will make 3 attempts to light before locking out.

The furnace should have a safety or fire shut-off valve connected to the inlet part of the oil pump to shut off the flow of oil in an emergency. Refer to Figure 36 for inlet port location.

ADJUSTMENT OF OIL PUMP PRESSURE

Nozzle Port

 

By Pass

 

 

 

Solenoid

 

 

3/16 Flare

 

Inlet Port

 

 

Valve

 

Fittting

 

1/4 NPTF

 

 

Cordset

Pressure

 

 

 

 

 

 

Adjustment

 

 

 

 

 

 

 

 

Screw

Beckett

 

 

 

 

CLEANCUT

INLET

 

 

 

USE ONLY WITH

 

 

 

 

VALVE ON DELAY

 

 

 

 

A2EA-6520

 

 

 

 

4 GPH 100-150 PSI 3450 RPM

 

 

 

NO. 2 & LIGHTER FUEL

 

 

 

3 GPH 150-200 PSI 3450 RPM

 

 

 

NO. 2 FUEL

 

Bleed &

 

 

INLET

BY-PASS

 

 

Made by Suntec

 

 

 

Exclusively for Beckett

 

 

 

 

 

Gauge Port

 

 

 

 

Return Port

 

 

Inlet Port

 

Install 1/16” by Pass Pipe

 

1/4 NPTF

 

Plug For Two-Pipe System Only

 

(0.64 cm)

 

(Use 5/32” Allen Wrench)

 

FIGURE 36: Oil Pump

SET COMBUSTION WITH INSTRUMENTS

The combustion must be adjusted using test instruments. Fail- ure to do so could result in burner or appliance failure, caus- ing potential severe personal injury, death, or substantial property damage.

1.Let the burner run for approximately 5 to 10 minutes.

2.Set the over-fire or stack draft to level specified by appliance man- ufacturer (usually -0.01” to -0.02” w.c. (-000024 to -0.0050 kPa) over-fire for natural draft applications).

3.Follow these four steps to properly adjust the burner:

a.Step 1: Adjust the air until a trace of smoke level is achieved.

b.Step 2: At the trace of smoke level, measure the CO2 (or O2). This is the vital reference point for further adjustments.

Example: 13.5% CO2 (2.6% O2).

c.Step 3: Increase the air to reduce CO2 by 1 to 2 percentage points. (O2 will be increased by approximately 1.4 to 2.7 per- centage points).

Example: Reduce CO2 from 13.5% to 11.5%. (2.6% to 5.3% O2).

d.Step 4: Recheck smoke level. It should be zero.

This procedure provides a margin of reserve air to accom- modate variable conditions.

If the draft level has to be changed, recheck the smoke and CO2 levels. Adjust the burner air if necessary.

4.Once combustion is set, tighten all fasteners on the air adjustment and escutcheon plate.

5.Start and stop the burner several times to ensure satisfactory operation. Test the primary control and all other appliance safety controls to verify that they function according to the manufacturer’s specifications.

ADJUSTMENT OF TEMPERATURE RISE

The temperature rise, or temperature difference between the return air and the supply (heated) air from the furnace, must be within the range shown on the furnace rating plate and within the application limitations shown in Table 8 “ELECTRICAL AND PERFORMANCE DATA”.

The supply air temperature cannot exceed the “Maximum Supply Air Temperature” specified in these instructions and on the fur- nace rating plate. Under NO circumstances can the furnace be allowed to operate above the Maximum Supply Air Temperature. Operating the furnace above the Maximum Supply Air Temperature will cause premature heat exchanger failure, high levels of Carbon Monoxide, a fire hazard, personal injury, property damage, and/or death.

After about 20 minutes of operation, determine the furnace temperature rise. Take readings of both the return air and the heated air in the ducts, about six feet (1.83 m) from the furnace where they will not be affected by radiant heat.

FILTER PERFORMANCE

The airflow capacity data published in Table 14 represents blower per- formance WITH CLEAN filters.

The filter pressure drop values in Table 13 are typical values for the type of filter listed and should only be used as a guideline. Actual pres- sure drop ratings for each filter type vary between filter manufacturers.

DO NOT USE Pleated Media or Hogs Hair filters on this furnace.

Be sure to check for leaks in the oil line and fittings. A leak will cause oil pump to loose it’s prime. Repair leaks before continuing with the final adjustments to the oil burner.

TABLE 13: Filter Performance - Pressure Drop Inches W.C. and (kPa)

 

 

Minimum

Filter Type

Airflow Range

Opening Size

Disposable

 

 

1 Opening

1 Opening

CFM

Cm/m

In2

m2

inwc

kPa

1001 - 1250

28.35 - 35.40

488

45.34

0.1

0.0249

1251 - 1500

35.42 - 42.47

488

45.34

0.1

0.0249

24

Unitary Products Group

Image 24
Contents Section I Safety For InstallationList of Sections List of FiguresSpecific Safety Rules and Precautions Safety RequirementsFollowing requirements to be met Combustion AIR Quality List of Contaminants InspectionCheck Certifications / Approvals Furnace Location and ClearancesTOP Front Back Sides AIR Inlet Roof Jack DUCT1 Piping FLOOR/BOTTOMDuct system’s design and installation must Section II DuctworkDuctwork General Information Duckwork Installation Air Distribution SystemsDuct Design Canada Clearance Requirements CanadaAir Distribution Systems Duct Connectors Installation of Screw Attachment Duct ConnectorInstallation of TAB Attachment Duct Connectors Furnace and Air Conditioner InstallationsInstallation of the Furnace MBH CFMBlend AIR Installations Section III FiltersReturn AIR Requirements OIL Safety Section IV OIL PipingConnect Fuel Lines Installation and Checking of OIL Piping Effect of Elevation on OIL Burner FiringExample AFGSection V Electrical Power Solenoid WiringElectrical Power Connections ONE Pipe SystemLOW Voltage Control Wiring Connections Vent and Combustion AIR SafetyEighteen gauge thermostat wire is highly recommended Section VI VENT/COMBUSTION AIR SystemExisting Furnace Replacement NEW Home InstallationInstallation in Snow Regions Exterior Roof Jack ExtensionInstalling Roof Jack in Roof Connect Roof Jack to FurnaceLocating and Cutting Roof Jack Opening Interior ExtensionsComplete Installation, as required Roof Jack Adjustable Height withSecure Roof Jack to Roof Interior ExtensionDfaa Models Dfah Models UIM-B-1105 Installing Ceiling Ring Vent SystemVent Clearances Home Layout Canadian Installations1 US Installation2 Section VII Safety Controls Section Viii START-UP Adjustments SpecificationsSTART-UP and Adjust Burner Adjustment of OIL Pump Pressure Adjustment of Temperature RiseIgnition System Sequence SET Combustion with InstrumentsFinal Procedure Install Furnace DoorsApplying Filter Pressure Drop to Determine System AirflowDfaa Model Item Number DescriptionDfah Model Section IX Wiring Diagram OIL-FIRED Furnace Wiring Diagram for Dfaa Oil-Fired FurnaceWiring Diagram for Dfah Oil Furnace Unitary Products Group UIM-B-1105Installation of Burner and Controls Section X GAS GUN BurnerPreparation of Combustion Chamber GAS PipingTesting Piping for Leaks GAS Piping InstallationLocate GAS LEAKS, USE a Soap Solution Length of Pipe Nominal Diameter of Pipe in Inches mmGAS Orifice Conversion for Propane LP High Altitude GAS Orifice ConversionSizing Furnace Input Natural GASPropane GAS Gas Firing Rate Orifice Air ShutterSection XI START-UP Adjustments PurgingCalculating the Furnace Input Natural GAS USA use the following formula to calculate the furnace input Adjustment of Manifold GAS Pressure Initial Start UPChecking the GAS Pressures Inlet GAS Pressure RangeObserving Burner Operation If Furnace Fails to Operate ProperlyPerformance Check Electrode Orientation and Gap Section XII Wiring Diagram GAS Conversion Burner Wiring Diagram for Dfah Gas Gun Unitary 5005 Norman Product York Group Drive 73069 Copyright by York International Corp . All rights reserved