5Electrical connections (continued)
Locating Temperature Control | NOTICE |
Remove the control panel door on the front of the unit in order to locate and access the temperature control.
Installation & Service Manual
Anytime that OJ1 is the only jumper cut, a new overlay is required under the Set Point knob on the temperature controller because the scale has changed to a maximum of 190°F.
Temperature Control Settings
Remove the control panel door on the front of the unit unless your unit is specified as a boiler only with an outdoor air reset option. If your unit is a boiler only with an outdoor air reset option, there are additional controls for this option. They are explained under Outdoor Air Reset Option, page 37.
The three setting knobs on the temperature control are for Set point, Differential, and
Figure |
Maximum Set Point Determination
The maximum set point for the control is factory set. Boilers can be set to 240°F max., water heaters are set to 190°F max., and specialty state and local codes to 200°F.
These maximum set points are established by cutting the OJ1 and OJ2 jumpers located on the right side of the temperature controller. The maximum set point is determined as shown below in Table 5C.
TABLE - 5C
MAXIMUM SET POINT DETERMINATION
| OJ1 | OJ2 | MAX. |
|
| SET POINT |
| ||
|
|
|
| |
|
|
|
|
|
| Connected | Connected | 240°F |
|
|
|
|
|
|
| Cut | Connected | 190°F |
|
|
|
|
|
|
| Connected | Cut | 200°F |
|
|
|
|
|
|
| Cut | Cut | 160°F |
|
|
|
|
|
|
Anytime the OJ2 jumper is cut (with or without OJ1), a new overlay is required under the Set Point knob on the temperature controller because the scale has changed to a maximum of 200°F.
Set Point
The Set Point knob specifies the target inlet (or system sensor, if used) water temperature in degrees, Fahrenheit. After the water temperature reaches the set point, the temperature control shuts off the burners.
Differential
The Differential specifies the number of degrees below the set point that the control will allow the water temperature to drop before it brings the unit back on again.
High-Fire Offset
The temperature control operates a
The
The
If the High Fire Offset knob is set to 0 or 1, the delay will be 10 seconds; if set to 2 or above the delay will be 120 seconds.
Boiler Application
Standard boiler units are equipped with one inlet water temperature sensor. An optional sensor is also provided for use as a remote system sensor. Boilers with the outdoor air reset option also have an outside air temperature sensor.
Water Heater Application
Water heater units are shipped with an inlet water temperature sensor and a
35