Piping Schematics

9.0PIPING SCHEMATICS

Figure 57 Piping schematic—air-cooled, semi-hermetic compressor models

Relief Valve

 

Check Valve

Service

 

Valve Liquid Return

 

 

Head Pressure

Lee-Temp Receiver

Control Valve

Inverted trap on discharge and liquid lines to extend above base of coil by a minimum of 7-1/2” (190mm).

Fusible

Plug

Condenser Coil

(Fan Speed)

Condenser Coil

(Lee-Temp)

Hot Gas Discharge

Lee-Temp

 

 

Liquid

 

Cylinder

Sensing

Service

Bulb

Unloader(s)

Valve

 

Suction

 

Compressor

External

Muffler

Service Equalizer

 

 

Valve

* Traps every

Evaporator Coil25ft (7.6m) of rise

Field-installed relief valve (s) required for 50Hz EU CE units rated maximum 480 PSIG (33 Bar).

 

 

 

* Isolation

** Muffler

valve

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Expansion

Solenoid Sight Glass

Filter Dryer

Valve

Valve

 

 

 

Refrigerant Piping

Field Piping

Service/Schrader (Access) Connection No Valve Core

Service/Schrader (Access) Connection With Valve Core

Hot Gas Discharge

 

 

 

 

 

 

 

Liquid Return

 

* Isolation

 

 

 

 

 

 

 

valve

*Components are not supplied by Liebert, but are recommended for proper circuit operation and

maintenance.

**Components supplied by Liebert and must be field-installed(70kW, 77kW and 105kW models only).

Note: Schematic representation shown . Do not use for specific connection locations.

DPN000797

Two refrigeration circuits provided . Single refrigeration circuit shown for clarity .

Rev. 3

 

82

Page 92
Image 92
Liebert DS user manual Piping Schematics, Piping schematic-air-cooled, semi-hermetic compressor models