Liebert DS Dimensions and Weights

Figure 13 Cabinet and floor planning dimensions—downflow, water/glycol/GLYCOOL, 105kW (30 ton), all compressor models

 

Condenser Cleanout Access

 

102-13/16"

 

(2611mm) Opening

33"

 

(838mm)

Air Inlet Opening

35"

(889mm)

Top View

Notes:Filters are accessible only through top of unit. Downflow electrical connections can be made from top or bottom of unit.

24-3/8" (619mm)Opening

3/4" Bezels (19mm)

Secondary Condenser

Secondary Entrance

Secondary Entrance

 

Low Volt Connections

Required for

High Volt Connection(s)

Fluid Entrance

 

condenser cleanout

 

 

 

 

24"

 

132"

Minimum required

 

(610mm)

 

(3353mm)

for filter replacement

 

 

 

 

 

15"

 

 

 

(381mm)

76"

(1930mm)

 

 

 

34"

 

Front View

 

(864mm)

 

 

Shaded area indicates a

 

131"

 

 

recommended minimum

 

(3327mm)

 

clearance for component

 

 

 

 

access.

 

 

 

 

DPN001013

 

 

 

 

Rev. 2

Table 10 Weights for downflow, water/glycol/GLYCOOL, 105kW (30 ton), all compressor models

 

 

 

 

 

Dry Weight, lb (kg) approximate

 

Compressor Type

 

 

 

Model

 

105

 

 

 

 

 

 

Semi-Hermetic Compressor

Water/Glycol

 

3410 (1550)

 

 

 

 

 

GLYCOOL/Dual-Cool

 

3770 (1714)

 

 

 

 

 

 

 

 

 

Scroll Compressor

Water/Glycol

 

3290 (1495)

 

 

 

 

 

GLYCOOL/Dual-Cool

 

3650 (1659)

 

 

 

 

 

 

 

 

 

18

Page 28
Image 28