Optional Low Voltage Terminal Package Connections

Electrical Connections

Optional Low Voltage Terminal Package Connections

20.Remote unit shutdown - Two additional contact pairs available for unit shutdown (labeled as 37B and 38B, 37C and 38C). Replace jumpers with field-supplied, normally closed switch having a minimum 75VA, 24VAC rating. Use Class 1 field-supplied wiring.

21.Common alarm—On any alarm, two additional normally open dry contacts are closed across terminals 94 and 95 and 96 and 97 for remote indication. 1A, 24VAC max load. Use Class 1 field-supplied wiring.

22.Main fan auxiliary switch—On closure of main fan contactor, normally open dry contact is closed across terminals 84 and 85 for remote indication. 1A, 24VAC max load. Use Class 1 field-supplied wiring.

23.Liebert Liqui-tectshutdown and dry contact—On Liebert Liqui-tect activation, normally open dry contact is closed across terminals 58 and 59 for remote indication (Liebert Liqui-tect sensor ordered separately). 1A, 24VAC max load. Use Class 1 field-supplied wiring.

NOTE

Refer to specification sheet for total unit full load amps, wire size amps and maximum overcurrent protective device size.

71