Piping Schematics

Figure 66 Primary connection locations—downflow, air-cooled, 28-42kW (8-12 ton), semi-hermetic compressor models

NOTE: Drawing not to scale.

Tolerance on all

 

 

All dimensions from

piping dimensions

A

A

rear corner of unit ,

 

is ±1/2" (13mm)

Front View

 

including panels

 

 

Section A-A

 

X

O

 

 

 

4" (102mm)

L1 L2 G1 G2

16-7/16" (418mm)

R

ECS

HUM

CD E1 E2 ECR

Blower Outlet

16-1/16" (408mm)

B

LV1 LV2 LV3

Y

35"

(889mm)

FRONT OF UNIT

 

86"

 

(2184 mm)

DPN000803

 

 

Rev. 2

 

 

X

Y

Connection Size / Opening

Point

Description

inches (mm)

inches (mm)

inches (mm)

 

 

 

 

 

R

Refrigerant Access

63 (1600)

13-13/16 (351)

16-7/16 x 4 (418 x 102)

 

 

 

 

 

L1

Liquid Line System 1

79-3/16 (2011)

16-3/4 (425)

1/2 Cu Sweat

 

 

 

 

 

L2

Liquid Line System 2

76-1/2 (1943)

16-3/4 (425)

1/2 Cu Sweat

 

 

 

 

 

G1

Hot Gas Discharge 1

73-7/8 (1876)

16-3/4 (425)

5/8 Cu Sweat

 

 

 

 

 

G2

Hot Gas Discharge 2

70-1/8 (1780)

16-3/4 (425)

5/8 Cu Sweat

 

 

 

 

 

CD

Condensate Drain*

46 (1168)

29-1/2 (749)

3/4 FPT

 

 

 

 

W/ Optional Pump

46 (1168)

29-1/2 (749)

1/2 Cu Sweat

 

 

 

 

 

 

HUM

Humidifier Supply Line

53-1/2 (1359)

29 (737)

1/4 Cu Sweat

 

 

 

 

 

ECS

Econ-O-Coil Supply

54-7/8 (1394)

22-9/16 (573)

1-5/8 Cu Sweat

 

 

 

 

 

ECR

Econ-O-Coil Return

49-3/8 (1254)

30-3/4 (781)

1-5/8 Cu Sweat

 

 

 

 

 

HS

Hot Water Reheat Supply

 

Consult factory

 

 

 

 

HR

Hot Water Reheat Return

 

Consult factory

 

 

 

 

 

E1

Electrical Connection (High Volt)

55-1/2 (1410)

31-1/4 (794)

2-1/2

 

 

 

 

 

E2

Electrical Connection (High Volt)

52-7/16 (1332)

31-1/4 (794)

2-1/2

 

 

 

 

 

LV1

Electrical Connection (Low Volt)

2-1/4 (57)

27 (686)

7/8

 

 

 

 

 

LV2

Electrical Connection (Low Volt)

2-1/4 (57)

29 (737)

7/8

 

 

 

 

 

LV3

Electrical Connection (Low Volt)

2-1/4 (57)

31 (787)

7/8

 

 

 

 

 

B

Blower Outlet

21-15/16 (558)

18-1/16 (459)

18-3/4 x 16-1/16 (476 x 408)

 

 

 

 

 

*Field-pitch condensate drain line a minimum of 1/8" (3.2mm) per foot (305mm). All units contain a factory-installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes.