24-3/8"
(619mm) Opening

Liebert DS Dimensions and Weights

Figure 7 Cabinet and floor planning dimensions—downflow, air-cooled, 28-42kW (8-12 ton), scroll compressor models

Secondary Refrigerant

Piping Entrance

33"

(838mm)

35"

(889mm)

56-7/8" Opening (1445mm)

Air Inlet Opening

Notes: Filters are accessible through top of unit only. Downflow electrical connections can be made from top or bottom of unit.

Top View

Secondary Entrance

High Volt Connection(s)

73"

(1854mm)

76"

(1930mm)

2"

Front View

72"

(51mm)

(1829mm)

 

3/4" Bezels (19mm)

Minimum required Secondary Entrance for filter replacement Low Volt Connections

15"

(381mm)

34" (864mm)

Shaded area indicates a recommended minimum clearance for component

access.DPN000796 Rev. 2

Table 4 Weights for downflow, air-cooled, 28-42kW (8-12 ton), scroll compressor models

Dry Weight, lb (kg),

Approximate

Model No.

028, 035, 042

 

 

Air-Cooled

1470 (668)

 

 

Dual-Cool

1620 (736)

 

 

12

Page 22
Image 22
Liebert DS user manual Top View, Front View, Dry Weight, lb kg Approximate Model No 028, 035