2.0COOLING CONFIGURATIONS

NOTE

All field-installed piping must comply with applicable local, state and federal codes.

Air-Cooled

Air-cooled unit piping is spun closed from the factory and contain a nitrogen holding charge. Each installation requires refrigerant piping to a condenser.

Glycol-Cooled

Glycol-cooled units are factory-charged and tested. Field-installed piping is required from the unit to the drycooler and pump package.

GLYCOOL

GLYCOOL units are factory-charged and tested. Field-installed piping is required from the unit to the drycooler and pump package. An additional coil is included for use when fluid temperatures are sufficiently low (below room temperature). Cooling is provided by circulating cold glycol through this second coil, reducing compressor operation.

Water-Cooled

Water-cooled units are factory-charged and tested. Field-installed water piping is required from the unit to the cooling tower.

Dual-Cool

This system has all of the features of a compressorized system, but adds a second cooling coil that is connected to a source of chilled water. Cooling is provided by circulating water through this second coil and reducing compressor operation.