Liebert user manual Top View, Front View, Model, Liebert DS Dimensions and Weights

Models: DS

1 136
Download 136 pages 14.39 Kb
Page 36
Image 36
Manual background

Liebert DS Dimensions and Weights

Figure 21 Cabinet and floor planning dimensions—upflow water/glycol/GLYCOOL 105kW (30 ton), all compressors

Alternate Refrigerant

Piping Entrance

33"

 

 

(838mm)

 

 

35"

 

Required for

(889mm)

3/4"

condenser cleanout

 

Alternate Condenser

(19mm)

 

Bezels

 

Fluid Piping Entrance

TOP VIEW

Minimum required

High Volt Connection(s)

Low Volt Connection(s)

for blower replacement

132"

 

1-1/2"

 

(3353mm)

 

(38mm)

 

 

 

24"

(610mm)

76"

(1930mm)

 

 

 

Shaded area indicates a

34"

 

 

 

(864mm)

2"

131"

 

recommended minimum

 

 

clearance for component

 

(51mm)

(3327mm)

 

 

 

access.

 

 

FRONT VIEW

 

 

 

 

 

 

Note: Front air return unit shown. For rear return unit,

 

 

 

in addition to front service area shown, also include

 

 

 

25" (635mm) on one side of unit for access to rear

 

 

DPN001169

return filter box. See DPN001196.

 

 

REV 0

Table 18 Weights—upflow water/glycol/GLYCOOL 105kW (30 ton), all compressors

 

 

 

 

 

 

 

Model

105

 

 

 

 

 

 

 

Semi-Hermetic Compressor

Water/Glycol

3370 (1529)

 

 

 

 

 

 

GLYCOOL/Dual-Cool

3700 (1678)

 

 

 

 

 

 

 

 

 

 

Scroll or Digital Scroll

Water/Glycol

3250 (1474)

 

 

Compressor

GLYCOOL/Dual-Cool

3580 (1624)

 

 

 

 

 

 

 

26

Page 36
Image 36
Liebert user manual Top View, Front View, Model, Liebert DS Dimensions and Weights