Maintenance
12.5Air-Cooled Condenser and Drycoolers
•Clear coil surface of all debris that will inhibit airflow.
•Check for bent or damaged coil fins and correct.
•Do not permit snow to accumulate around or under outdoor unit.
•Periodically consider commercial cleaning of coil surface
•Inspect fans, motors and controls for proper operation.
•Check all piping and capillaries for proper support.
•Inspect for leaks.
12.6Reheat—Electric Reheat (Three-Stage and SCR)
•Inspect and clean reheat elements.
•Inspect and tighten support hardware.
12.7Compressor
12.7.1Compressor Oil
!CAUTION
Risk of improper compressor lubrication. Can cause compressor and refrigerant system damage.
Failure to use oil types, viscosities and quantities recommended by the compressor manufacturer may reduce compressor life and void the compressor warranty. See oil types specified in Table 55.
•Do NOT mix polyolester (POE) and
•Do NOT mix oils of different viscosities.
Consult Emerson or the compressor manufacturer if you have questions.
Table 55 Compressor oil types
| Refrigerant Type | ||
Compressor Type |
|
| |
| |||
|
|
| |
Carlyle | Mineral Oil 1 | POE Oil - ISO | |
68 Viscosity 2 | |||
|
| ||
Copeland Scroll | POE Oil - ISO 22 Viscosity 3 | ||
and Digital Scroll | |||
|
| ||
1.Use Carlyle Mineral Oil Totaline
2.Use Carlyle POE Oil Totaline
3.Use Copeland POE Oil ULTRA 22CC, Mobil EAL Arctic 22CC or other
12.7.2Semi-Hermetic Compressors
Oil level can be viewed at the sight glass on
After a compressor has been idle for an extended length of time, foaming will usually be present when compressor first starts. Wait until compressor has been operating for at least five minutes before viewing the oil level.
If oil level is low, the cause must be corrected and oil level returned to its proper level.
12.7.3Scroll and Digital Scroll Compressors
Hermetic scroll and digital scroll compressors do not have an oil sight glass.
117