Liebert DS user manual Top View, Front View, 838mm

Models: DS

1 136
Download 136 pages 14.39 Kb
Page 32
Image 32
(838mm)

Liebert DS Dimensions and Weights

Figure 17 Cabinet and floor planning dimensions—upflow, air-cooled, 53-77kW (15-22 ton), semi-hermetic compressor models

Alternate Refrigerant

Piping Entrance

33"

(838mm)

35"

3/4"

Minimum required

(889mm)

(19mm)

 

Bezels

for blower replacement

Top View

Low Volt Connection(s)

 

High Volt Connection(s)

 

1-1/2"

109"

(2769mm)

(38mm)

24"

 

 

(610mm)

76"

(1930mm)

2"

(51mm)

108"

(2743mm)

Front View

34"

(864mm)

Shaded area indicates a recommended minimum clearance for component access.

Note: Front air return unit shown. For rear return unit, in addition to front service area shown, also include 25" (635mm) on one side of unit for access to rear return filter box. See DPN001196, Figure 28.

DPN001165

Rev. 1

Table 14 Weights for upflow, air-cooled, 53-77kW (15-22 ton), semi-hermetic compressor models

 

Dry Weight, lb (kg)

 

approximate

Model

 

 

053

070, 077

 

 

 

Air-Cooled

2350 (1069)

2500 (1134)

Dual-Cool

2530 (1150)

2680 (1216)

 

 

 

22

Page 32
Image 32
Liebert DS user manual Top View, Front View, 838mm