Piping
8.2.1Piping Guidelines—Air-Cooled Units
•Indoor unit ships with a nitrogen holding charge; do not vent the evaporator until all refrigerant piping is in place, ready for connection to the unit and condenser
•Use copper piping with high temperature brazed joints
•Isolate piping from building using
•Refer to Table 45 for piping sizes
•Refer to condenser installation manual for charging information
•Install traps on hot gas (discharge) lines at the base of vertical risers and every 25 feet (7.6m) of vertical rise.
•Consult factory if condenser is installed more than 15 feet (4.6m) below the evaporator
•Consult factory if piping run exceeds 150 feet (46m) equivalent length
•Keep piping clean and dry, especially on units with
•Avoid piping runs through
•Do not run piping directly in front of airstream
•Refrigerant oil – do not mix oil types (see 12.7.1 - Compressor Oil)
Refer to ASHRAE Refrigeration Handbook for general,
Table 45 Recommended refrigerant line sizes - OD copper (inches)*
Standard Scroll Models
Model | 028 | 035 | 042 | 053 | 070 | 077 | 105 | |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Hot |
| Hot |
| Hot |
| Hot |
| Hot |
| Hot |
| Hot |
|
Equivalent | Gas | Liquid | Gas | Liquid | Gas | Liquid | Gas | Liquid | Gas | Liquid | Gas | Liquid | Gas | Liquid |
Length | Line | Line | Line | Line | Line | Line | Line | Line | Line | Line | Line | Line | Line | Line |
50 ft (15m) | 7/8 | 1/2 | 7/8 | 1/2 | 7/8 | 1/2 | 7/8 | 5/8 | 7/8 | 7/8 | 7/8 | |||
100 ft (30m) | 7/8 | 5/8 | 7/8 | 5/8 | 7/8 | 5/8 | 7/8 | 7/8 | 7/8 | 7/8 | ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
150 ft (45 m) | 7/8 | 5/8 | 7/8 | 5/8 | 7/8 | 5/8 | 7/8 | 7/8 | 7/8 | |||||
Hermetic and Digital Scroll Models |
|
|
|
|
|
|
|
| ||||||
Model | 028 | 035 | 042 | 053 | 070 | 077 | 105 | |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Hot |
| Hot |
| Hot |
| Hot |
| Hot |
| Hot |
| Hot |
|
Equivalent | Gas | Liquid | Gas | Liquid | Gas | Liquid | Gas | Liquid | Gas | Liquid | Gas | Liquid | Gas | Liquid |
Length | Line | Line | Line | Line | Line | Line | Line | Line | Line | Line | Line | Line | Line | Line |
50 ft (15m) | 3/4 | 1/2 | 3/4 | 1/2 | 7/8 | 5/8 | 7/8 | 7/8 | 7/8 | 7/8 | 7/8 | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
100 ft (30m) | 3/4 | 5/8 | 7/8 | 5/8 | 7/8 | 5/8 | 7/8 | 7/8 | 7/8 | 7/8 | ||||
150 ft (45 m) | 7/8 | 5/8 | 7/8 | 5/8 | 5/8 | 7/8 | 7/8 | 7/8 | ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
* Downsize vertical riser one trade size
Table 46 Indoor unit approximate refrigerant charge for
System Type | Model | ||||
|
| per Circuit, lb (kg) | per Circuit, lb (kg) | ||
| 028, 035, 042 | 6.5 | (3.0) | 5.5 | (2.5) |
|
|
|
|
| |
053, 070, 077 | 9.5 | (5.0) | 8.0 | (3.6) | |
| 105 | 11.0 (5.0) | 9.5 | (4.3) | |
|
|
|
| ||
| 028, 035, 042 | 13.0 (5.9) | 12.2 (5.6) | ||
Water, Glycol/GLYCOOL |
|
|
| ||
053, 070, 077 | 18.5 (8.4) | 17.0 (7.8) | |||
| 105 | 24.0 | (10.9) | 22.5 | (10.3) |
|
|
|
|
|
|
76