Piping

8.2.1Piping Guidelines—Air-Cooled Units

•Indoor unit ships with a nitrogen holding charge; do not vent the evaporator until all refrigerant piping is in place, ready for connection to the unit and condenser

•Use copper piping with high temperature brazed joints

•Isolate piping from building using vibration-isolating supports

•Refer to Table 45 for piping sizes

•Refer to condenser installation manual for charging information

•Install traps on hot gas (discharge) lines at the base of vertical risers and every 25 feet (7.6m) of vertical rise.

•Consult factory if condenser is installed more than 15 feet (4.6m) below the evaporator

•Consult factory if piping run exceeds 150 feet (46m) equivalent length

•Keep piping clean and dry, especially on units with R-407C refrigerant

•Avoid piping runs through noise-sensitive areas

•Do not run piping directly in front of airstream

•Refrigerant oil – do not mix oil types (see 12.7.1 - Compressor Oil)

Refer to ASHRAE Refrigeration Handbook for general, good-practice refrigeration piping.

Table 45 Recommended refrigerant line sizes - OD copper (inches)*

Standard Scroll Models (Non-Digital Scroll)

Model

028

035

042

053

070

077

105

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hot

 

Hot

 

Hot

 

Hot

 

Hot

 

Hot

 

Hot

 

Equivalent

Gas

Liquid

Gas

Liquid

Gas

Liquid

Gas

Liquid

Gas

Liquid

Gas

Liquid

Gas

Liquid

Length

Line

Line

Line

Line

Line

Line

Line

Line

Line

Line

Line

Line

Line

Line

50 ft (15m)

7/8

1/2

7/8

1/2

7/8

1/2

7/8

5/8

1-1/8

7/8

1-1/8

7/8

1-3/8

7/8

100 ft (30m)

7/8

5/8

7/8

5/8

7/8

5/8

1-1/8

7/8

1-1/8

7/8

1-1/8

7/8

1-3/8

7/8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

150 ft (45 m)

7/8

5/8

7/8

5/8

7/8

5/8

1-1/8

7/8

1-1/8

7/8

1-1/8

7/8

1-3/8

1-1/8

4-Step Semi-

Hermetic and Digital Scroll Models

 

 

 

 

 

 

 

 

Model

028

035

042

053

070

077

105

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hot

 

Hot

 

Hot

 

Hot

 

Hot

 

Hot

 

Hot

 

Equivalent

Gas

Liquid

Gas

Liquid

Gas

Liquid

Gas

Liquid

Gas

Liquid

Gas

Liquid

Gas

Liquid

Length

Line

Line

Line

Line

Line

Line

Line

Line

Line

Line

Line

Line

Line

Line

50 ft (15m)

3/4

1/2

3/4

1/2

7/8

5/8

7/8

7/8

1-1/8*

7/8

1-1/8

7/8

1-3/8

7/8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100 ft (30m)

3/4

5/8

7/8

5/8

7/8

5/8

1-1/8*

7/8

1-1/8

7/8

1-1/8

7/8

1-3/8

7/8

150 ft (45 m)

7/8

5/8

7/8

5/8

1-1/8*

5/8

1-1/8

7/8

1-1/8

7/8

1-1/8

7/8

1-3/8

1-1/8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* Downsize vertical riser one trade size (1-1/8" to 7/8")

Table 46 Indoor unit approximate refrigerant charge for R-22 or R-407C

System Type

Model

R-22 Charge

R-407C Charge

 

 

per Circuit, lb (kg)

per Circuit, lb (kg)

 

028, 035, 042

6.5

(3.0)

5.5

(2.5)

Air-Cooled

 

 

 

 

 

053, 070, 077

9.5

(5.0)

8.0

(3.6)

 

105

11.0 (5.0)

9.5

(4.3)

 

 

 

 

 

028, 035, 042

13.0 (5.9)

12.2 (5.6)

Water, Glycol/GLYCOOL

 

 

 

053, 070, 077

18.5 (8.4)

17.0 (7.8)

 

105

24.0

(10.9)

22.5

(10.3)

 

 

 

 

 

 

76

Page 86
Image 86
Liebert DS user manual Piping Guidelines-Air-Cooled Units, Recommended refrigerant line sizes OD copper inches