11.7 (5.3)

Piping

Table 47 Line charges - refrigerant per 100 ft (30m) of Type “L” copper tube

O.D.

Liquid Line, lb (kg)

 

 

 

1/2"

7.3

(3.3)

5/8"

11.7 (5.3)

 

 

 

7/8"

24.4

(11.1)

 

 

 

1-1/8"

41.6

(18.9)

Table 48 Outdoor condenser approximate refrigerant charge lb (kg) per circuit

 

Fan

Lee-Temp

Model

Speed

(includes receiver)

 

 

 

 

165

5

(2.3)

27 (12.3)

 

 

 

 

205

7

(3.2)

38 (17.2)

251

10 (4.6)

38 (17.20

 

 

 

308

11 (5.0)

58 (26.3)

 

 

 

415

15 (6.8)

75 (34.0)

510

30

(13.6)

149 (67.6)

 

 

 

143

17 (8)

64 (29)

 

 

 

214

23 (10

81 (37)

286

29 (13)

98 (44)

 

 

 

409

36 (16)

129 (59)

 

 

 

477

24 (11)

80 (36)

572

57 (26)

196 (89)

 

 

 

 