Liebert DS user manual Front View

Models: DS

1 136
Download 136 pages 14.39 Kb
Page 31
Image 31
FRONT VIEW

Liebert DS Dimensions and Weights

Figure 16 Cabinet and floor planning dimensions—upflow, water/glycol/GLYCOOL, 28-42kW (8-12 ton), all compressor models

Condenser Cleanout Access

33"

(838mm)

35"

(889mm)

Note: Front air return unit shown. For rear return unit, in addition to front service area shown, also include 25" (635mm) on one side of unit for access to rear return filter box. See DPN001196, Figure 28

3/4"

(19mm) Bezels Required for condenser cleanout

Alternate RefrigerantTOP VIEW

Piping Entrance

 

High Volt Connection(s)

 

1-1/2"

86"

(2184mm)

(38mm)

 

76"

(1930mm)

Low Volt Connection(s)

Minimum required

for blower replacement

24"

(610mm)

34"

Shaded area indicates a (864mm) recommended minimum

clearance for component access.

 

FRONT VIEW

 

2"

85"

DPN001164

(51mm)

Rev. 1

(2159mm)

 

 

Table 13 Weights for upflow, water/glycol/GLYCOOL, 28-42kW (8-12 ton), all compressor models

 

Dry Weight, lb (kg) approximate

Compressor Type

 

 

Model

028-042

 

 

 

Semi-Hermetic

Water/Glycol

1980 (898)

 

 

GLYCOOL/Dual-Cool

2130 (966)

 

 

 

 

Scroll or Digital Scroll

Water/Glycol

1830 (830)

 

 

GLYCOOL/Dual-Cool

1980 (898)

 

 

 

 

21

Page 31
Image 31
Liebert DS user manual Front View