Piping
Leak Checking of Unit and Field Piping
Liebert unit fluid systems are
NOTE
During leak checking of
8.2Refrigeration Piping
! WARNING
Risk of explosive discharge from
Relieve pressure before working with piping.
! WARNING
Risk of refrigerant system rupture or explosion from over pressurization. Can cause equipment damage, injury or death.
If a pressure relief device is not provided with the condenser unit, the system installer must provide and install a discharge pressure relief valve rated for a maximum of 500 psig (34bar) in the high side refrigerant circuit. Do not install a shutoff valve between the compressor and the field installed relief valve.
One or more additional pressure relief valves are required downstream of any and all field- installed isolation valves as shown in Figures 57 and 58. Do not isolate any refrigerant circuits from overpressurization protection.
For systems requiring EU CE compliance (50Hz), the pressure relief valve must be CE certified to the EU Pressure Equipment Directive by an EU “Notified Body.”
! CAUTION
Risk of oil contamination with water. Can cause equipment damage.
Some Liebert DS Systems require the use of POE (polyolester) oil. See 12.7.1 - Compressor Oil for requirements. POE oil absorbs water at a much faster rate when exposed to air than previously used oils. Because water is the enemy of a reliable refrigeration system, extreme care must be used when opening systems during installation or service. If water is absorbed into the POE oil, it will not be easily removed and will not be removed through the normal evacuation process. If the oil is too wet, it may require an oil change. POE oils also have a property that makes them act as a solvent in a refrigeration system. Maintaining system cleanliness is extremely important because the oil will tend to bring any foreign matter back to the compressor.
NOTE
A pressure relief valve is provided with Liebert