Maintenance
12.11.3Drycooler Settings
Applications with the Optional Stat Setting require field piping to be insulated to prevent condensa- tion. Table 57 shows acceptable applications where stats must be adjusted to Optional Setting. Aqu- astats must be
•GLYCOOL/Dual Cool applications
•Single Drycooler loops with motor ball valve flow controls (motor ball valves are used on all Lie- bert DS units with digital compressors). These units have a “D” or “G” in the seventh character: DS/VS/xxxxD or DS/VS/xxxxG.
Table 57 Water/glycol system conditions requiring optional settings for aquastats
Cooling Type |
| Glycool |
|
| Glycol |
| ||
|
|
|
|
|
|
|
| |
Flow Control | MBV | WRV | MBV | WRV | ||||
|
|
|
|
|
|
|
|
|
Drycoolers in Loop | 1 | Multiple | 1 | Multiple | 1 | Multiple | 1 | Multiple |
|
|
|
|
|
|
|
|
|
Stat Setting* | Optional | Optional | Optional | Optional | Optional | Factory | Factory | Factory |
|
|
|
|
|
|
|
|
|
Insulate Field Piping | Yes | Yes | Yes | Yes | Yes | No | No | No |
|
|
|
|
|
|
|
|
|
* See Tables 58 through 60
MBV=motor ball valve; WRV=water regulating valve
Table 58 Aquastat settings—two-fan through four-fan drycoolers
Dial Setting (Stat Open Temp) Set for Mid Differential 8°F (4.4°C) Rise to Close
|
| Factory Setting | Optional Setting |
Aquastat # | Fans | (Glycol) (see Notes 1 and 2) | (GLYCOOL) (see Note 3) |
|
|
|
|
AQ1 | F1 | 65°F (18.3°C) | 35°F (1.7°C) |
|
|
|
|
AQ2 | F2 & F3 | 75°F (23.9°C) | 45°F (7.2°C) |
|
|
|
|
AQ3 | F4 | 70°F (21.1°C) | 40°F (4.4°C) |
|
|
|
|
Table 59 Aquastat settings—six-fan drycoolers
Dial Setting (Stat Open Temp) Set for Mid Differential 8°F (4.4°C) Rise to Close
|
| Stat Location | Factory Setting | Optional Setting |
Aquastat # | Fans | Cabinet | (Glycol) (see Notes 1 and 2) | (GLYCOOL) (see Note 3) |
|
|
|
|
|
AQ1 | F1 | Main | 65°F (18.3°C) | 35°F (1.7°C) |
|
|
|
|
|
AQ2 | F2 | Main | 70°F (21.1°C) | 40°F (4.4°C) |
|
|
|
|
|
AQ3 | F3 & F4 | Auxiliary | 73°F (22.8°C) | 43°F (6.1°C) |
|
|
|
|
|
AQ4 | F5 & F6 | Auxiliary | 75°F (23.9°C) | 45°F (7.2°C) |
|
|
|
|
|
Table 60 Aquastat settings—eight-fan drycoolers
Dial Setting (Stat Open Temp) Set for Mid Differential 8°F (4.4°C) Rise to Close
|
| Stat Location | Factory Setting | Optional Setting |
Aquastat # | Fans | Cabinet | (Glycol) (see Notes 1 and 2) | (GLYCOOL) (see Note 3) |
|
|
|
|
|
AQ1 | F1 | Main | 65°F (18.3°C) | 35°F (1.7°C) |
|
|
|
|
|
AQ2 | F2 | Main | 70°F (21.1°C) | 40°F (4.4°C) |
|
|
|
|
|
AQ3 | F3 & F4 | Auxiliary | 73°F (22.8°C) | 43°F (6.1°C) |
|
|
|
|
|
AQ4 | F5 & F6 | Auxiliary | 75°F (23.9°C) | 45°F (7.2°C) |
|
|
|
|
|
AQ5 | F7 & F8 | Main | 78°F (25.6°C) | 48°F (8.9°C) |
|
|
|
|
|
NOTE
1. All drycoolers are shipped at Factory Setting.
2.Factory Setting is used for all glycol applications, except single drycooler loops with motor ball valve controls.
3.Stats must be