Maintenance

12.11.3Drycooler Settings

Applications with the Optional Stat Setting require field piping to be insulated to prevent condensa- tion. Table 57 shows acceptable applications where stats must be adjusted to Optional Setting. Aqu- astats must be field-adjusted to Optional Setting for:

GLYCOOL/Dual Cool applications

Single Drycooler loops with motor ball valve flow controls (motor ball valves are used on all Lie- bert DS units with digital compressors). These units have a “D” or “G” in the seventh character: DS/VS/xxxxD or DS/VS/xxxxG.

Table 57 Water/glycol system conditions requiring optional settings for aquastats

Cooling Type

 

Glycool

 

 

Glycol

 

 

 

 

 

 

 

 

 

Flow Control

MBV

WRV

MBV

WRV

 

 

 

 

 

 

 

 

 

Drycoolers in Loop

1

Multiple

1

Multiple

1

Multiple

1

Multiple

 

 

 

 

 

 

 

 

 

Stat Setting*

Optional

Optional

Optional

Optional

Optional

Factory

Factory

Factory

 

 

 

 

 

 

 

 

 

Insulate Field Piping

Yes

Yes

Yes

Yes

Yes

No

No

No

 

 

 

 

 

 

 

 

 

* See Tables 58 through 60

MBV=motor ball valve; WRV=water regulating valve

Table 58 Aquastat settings—two-fan through four-fan drycoolers

Dial Setting (Stat Open Temp) Set for Mid Differential 8°F (4.4°C) Rise to Close

 

 

Factory Setting

Optional Setting

Aquastat #

Fans

(Glycol) (see Notes 1 and 2)

(GLYCOOL) (see Note 3)

 

 

 

 

AQ1

F1

65°F (18.3°C)

35°F (1.7°C)

 

 

 

 

AQ2

F2 & F3

75°F (23.9°C)

45°F (7.2°C)

 

 

 

 

AQ3

F4

70°F (21.1°C)

40°F (4.4°C)

 

 

 

 

Table 59 Aquastat settings—six-fan drycoolers

Dial Setting (Stat Open Temp) Set for Mid Differential 8°F (4.4°C) Rise to Close

 

 

Stat Location

Factory Setting

Optional Setting

Aquastat #

Fans

Cabinet

(Glycol) (see Notes 1 and 2)

(GLYCOOL) (see Note 3)

 

 

 

 

 

AQ1

F1

Main

65°F (18.3°C)

35°F (1.7°C)

 

 

 

 

 

AQ2

F2

Main

70°F (21.1°C)

40°F (4.4°C)

 

 

 

 

 

AQ3

F3 & F4

Auxiliary

73°F (22.8°C)

43°F (6.1°C)

 

 

 

 

 

AQ4

F5 & F6

Auxiliary

75°F (23.9°C)

45°F (7.2°C)

 

 

 

 

 

Table 60 Aquastat settings—eight-fan drycoolers

Dial Setting (Stat Open Temp) Set for Mid Differential 8°F (4.4°C) Rise to Close

 

 

Stat Location

Factory Setting

Optional Setting

Aquastat #

Fans

Cabinet

(Glycol) (see Notes 1 and 2)

(GLYCOOL) (see Note 3)

 

 

 

 

 

AQ1

F1

Main

65°F (18.3°C)

35°F (1.7°C)

 

 

 

 

 

AQ2

F2

Main

70°F (21.1°C)

40°F (4.4°C)

 

 

 

 

 

AQ3

F3 & F4

Auxiliary

73°F (22.8°C)

43°F (6.1°C)

 

 

 

 

 

AQ4

F5 & F6

Auxiliary

75°F (23.9°C)

45°F (7.2°C)

 

 

 

 

 

AQ5

F7 & F8

Main

78°F (25.6°C)

48°F (8.9°C)

 

 

 

 

 

NOTE

1. All drycoolers are shipped at Factory Setting.

2.Factory Setting is used for all glycol applications, except single drycooler loops with motor ball valve controls.

3.Stats must be field-adjusted to Optional Setting for GLYCOOL/Dual Cool applications and all single drycooler loops using motor ball valve flow controls.

121

Page 131
Image 131
Liebert DS user manual 12.11.3Drycooler Settings, Aquastat settings-two-fan through four-fan drycoolers