Piping

Figure 56 Gravity drain for downflow and upflow units

DOWNFLOW DS UNIT

INTERNAL DRAIN

UNIT

EXTERNAL

DRAIN

CONTINUOUS DOWNWARD SLOPE

CORRECT

UPFLOW DS UNIT

EXTERNAL

INTERNAL

DRAIN

DRAIN

 

UNIT

CONTINUOUS DOWNWARD SLOPE

CORRECT

 

INTERNAL

UNIT

DRAIN

 

 

EXTERNAL

 

DRAIN

EXTERNAL DRAIN

INTERNAL

DRAIN

UNIT

DO NOT EXTERNALLY

TRAP THE UNIT

INCORRECT

INTERNAL

DO NOT EXTERNALLY TRAP THE UNIT

INCORRECT

DRAIN

UNIT

EXTERNAL

DRAIN

EXTERNAL DRAIN

INTERNAL

DRAIN

UNIT

THESE ARE EXTERNAL TRAPS ALSO, ALTHOUGH UNINTENTIONAL. LINES MUST BE RIGID ENOUGH NOT TO BOW OVER TOP OF OTHER OBJECTS.

INCORRECT

Condensate Pump

THESE ARE EXTERNAL TRAPS ALSO, ALTHOUGH UNINTENTIONAL. LINES MUST BE RIGID ENOUGH NOT TO BOW OVER TOP OF OTHER OBJECTS.

INCORRECT DPN001556

Rev. 0

1/2" copper sweat connection is provided on units with optional factory-installed condensate pump

Condensate Pump (60Hz): Condensate pump is rated for approximately 400 gph at 10 feet total head

Condensate Pump (50Hz): Condensate pump is rated for approximately 315 gph at 10 feet total head

Size piping based on available condensate head

73

Page 83
Image 83
Liebert DS user manual Condensate Pump, Gravity drain for downflow and upflow units