Liebert DS user manual Top View, Front View

Models: DS

1 136
Download 136 pages 14.39 Kb
Page 21
Image 21
Top View

Liebert DS Dimensions and Weights

Figure 6 Cabinet and floor planning dimensions—downflow, air-cooled, 28-42kW (8-12 ton), semi-hermetic compressor models

Secondary Refrigerant Piping Entrance

56-7/8" Opening (1445mm)

33"

(838mm)

35"

Air Inlet Opening

 

(889mm)

 

Top View

Secondary Entrance

High Volt Connection(s)

86"

(2184mm)

 

 

Notes:Filters are accessible

 

 

 

 

 

through top of unit only.

24-3/8"

 

Opening

Downflow electrical

 

(619mm)

 

connections can be made

 

 

 

 

 

 

from top or bottom of unit.

 

 

 

 

3/4"

 

(19mm) Bezels

 

Secondary Entrance

Minimum clearance

Low Volt Connections

required for filter

 

replacement

 

15"

 

(381mm)

76"

(1930mm)

 

 

34"

 

Shaded areas indicate a

(864mm)

 

recommended minimum

 

 

clearance for component￿

 

2"

access.

 

Front View

DPN000795

(51mm)

85"

Rev. 3

 

 

(2159mm)

 

Table 3 Weights for downflow, air-cooled, 28-42kW (8-12 ton), semi-hermetic compressor models

 

Dry Weight - lb. (kg),

 

Approximate

Model No.

 

028, 035, 042

 

 

Air-Cooled

1780 (809)

 

 

Dual-Cool

1930 (877)

 

 

11

Page 21
Image 21
Liebert DS user manual Top View, Front View