Piping Schematics

Figure 68 Primary connection locations—downflow water/glycol/GLYCOOL 28-42kW (8-12 ton), all compressor models

Note: Drawing not to scale

 

 

 

All dimensions

 

Tolerance on all

 

 

 

from rear corner

 

piping dimensions

A

 

A

of unit including

 

is ± 1/2" (13mm)

 

Front View

 

panels

 

 

 

 

Section A-A

 

X

O

 

 

 

 

 

 

W

 

Blower

16-1/16"

Y

 

 

Outlet

(408mm)

 

 

WS

 

 

8" (203mm)

 

 

B

 

 

WR

 

 

 

35"

 

 

 

 

 

 

3-1/2"

 

 

 

 

 

ECS

 

 

(889mm)

 

(89mm)

 

 

 

 

 

 

LV1

 

 

 

HUM

 

 

 

 

 

CD

 

LV2

 

 

 

E1 E2

 

LV3

 

 

 

ECR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Front of Unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

86"

 

 

 

 

 

 

 

 

 

 

 

 

(2184mm)

 

DPN000900

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rev. 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X

 

 

Y

Connection Size / Opening

Point

 

 

Description

inches (mm)

 

 

inches (mm)

inches (mm)

W

Water/Glycol/GLYCOOL Access

79-15/16 (2030)

 

 

9-1/16 (230)

3-1/2 x 8 (89 x 203)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WS

Water/Glycol/GLYCOOL Supply

82-15/16 (2107)

 

 

10-15/16 (278)

1-5/8 Cu Sweat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WR

Water/Glycol/GLYCOOL Return

82-15/16 (2107)

 

 

14-1/16 (357)

1-5/8 Cu Sweat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CD

Condensate Drain *

46 (1168)

 

 

29-1/2 (749)

3/4 FPT

 

 

 

 

 

 

 

 

 

 

 

 

 

W/ Optional Pump

46 (1168)

 

 

29-1/2 (749)

1/2 Cu Sweat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HUM

Humidifier Supply Line

53-1/2 (1359)

 

 

29 (737)

1/4 Cu Sweat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ECS

Econ-O-Coil Supply **

54-7/8 (1394)

 

 

22-9/16 (573)

1-5/8 Cu Sweat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ECR

Econ-O-Coil Return **

49-13/16 (1265)

 

 

28-1/2 (724)

1-5/8 Cu Sweat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HS

Hot Water Reheat Supply

 

 

 

 

Consult Factory

 

 

 

 

 

 

 

 

 

 

 

 

 

HR

Hot Water Reheat Return

 

 

 

 

Consult Factory

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E1

Electrical Connection (High Volt)

55-1/2 (1410)

 

 

31-1/4 (794)

2-1/2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E2

Electrical Connection (High Volt)

52-7/16 (1332)

 

 

31-1/4 (794)

2-1/2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LV1

Electrical Connection (Low Volt)

2-1/4 (57)

 

 

27 (686)

7/8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LV2

Electrical Connection (Low Volt)

2-1/4 (57)

 

 

29 (737)

7/8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LV3

Electrical Connection (Low Volt)

2-1/4 (57)

 

 

31 (787)

7/8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

Blower Outlet

21-15/16 (557)

 

 

18-1/16 (459)

18-3/4 x 16-1/16 (476 x 408)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Field-pitch condensate drain line a minimum of 1/8" (3.2mm) per foot (305mm). All units contain a factory-installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes.

**Supplied on Dual-Cool systems only (4-pipe system)