Liebert DS Dimensions and Weights

Figure 10 Cabinet and floor planning dimensions—downflow, air-cooled, 53-77kW (15-22 ton), scroll compressor models

Secondary Refrigerant Piping Entrance

33"

(838mm)

80" Opening (2032mm)

Notes: Filters are accessible only through top of unit. Downflow electrical connections can be made

from top or bottom of unit. 24-5/8"

35"

Air Inlet Opening

(625mm Opening

(889mm)

Secondary EntranceTop View High Volt Connection(s)

98"

(2489mm)

76"

(1930mm)

2"

97"

(51mm)

(2464mm)

Front View

3/4"

(19mm) Bezels

Minimum required

Secondary Entrance for filter replacement Low Volt Connections

15"

(381mm)

34"

(864mm)

Shaded area indicates a recommended minimum

clearance for component

access.DPN000925 Rev. 1

Table 7

Weights for downflow, air-cooled, 53-77kW (15-22 ton), scroll compressor models

 

 

 

 

 

 

 

 

Dry Weight, lb (kg) Approximate

 

Model No.

 

 

 

 

 

 

053

070

077

 

 

 

 

 

 

 

Air-Cooled

 

1920 (873)

1970 (896)

2020 (919)

 

 

 

 

 

 

 

Dual-Cool

 

2100 (955)

2150 (978)

2200 (1000)

 

 

 

 

 

 

 

15