Liebert DS user manual DPN000933, 16-1/16, 408mm

Models: DS

1 136
Download 136 pages 14.39 Kb
Page 106
Image 106
16-1/16"

Piping Schematics

Figure 71 Primary connection locations—downflow, water/glycol/GLYCOO,L 53-77kW (15-22 ton), all compressor models

Note: Drawing not to scale

 

 

 

All dimensions

 

 

 

from rear corner

 

 

A

 

A

Tolerance on all

 

of unit including

Front View

 

piping dimensions

 

panels

is ± 1/2" (13mm)

 

Section A-A

 

X

 

 

 

 

O

 

 

 

 

 

 

3-1/2"

Blower

16-1/16"

Blower

 

 

W (89mm)

Y

 

Outlet

(408mm)

Outlet

8" (203mm)

WS

 

 

 

 

 

WR

 

B2

B1

35"

 

 

 

 

 

ECS

 

 

(889mm)

 

 

 

 

LV1

 

 

HUM ECR

 

 

 

 

CD

 

 

LV2

 

 

 

 

 

LV3

E1 E2

Front of Unit

 

 

 

 

 

 

 

 

 

 

 

109"

 

 

 

 

 

 

 

 

 

 

 

 

 

(2769mm)

DPN000933

 

 

 

 

 

 

 

 

Rev. 2

 

 

X

 

Y

Connection Size / Opening

Point)

Description)

inches (mm)

inches (mm)

inches (mm)

 

 

 

 

 

W

Water/Glycol/GLYCOOL Access

103 (2616)

9 (229)

3-1/2 x 8 (89 x 203)

 

 

 

 

 

WS

Water/Glycol/GLYCOOL Supply

104-3/4 (2661)

11 (279)

2-1/8 Cu Sweat

 

 

 

 

 

 

WR

Water/Glycol/GLYCOOL Return

104-3/4

(2661)

15 (381)

2-1/8 Cu Sweat

 

 

 

 

 

CD

Condensate Drain *

69-1/4 (1759)

30 (762)

3/4 FPT

 

 

 

 

 

W/ Optional Pump

69-1/4 (1759)

30 (762)

1/2 Cu Sweat

 

 

 

 

 

 

HUM

Humidifier Supply Line

76-1/2 (1943)

29 (736)

1/4 Cu Sweat

 

 

 

 

 

ECS**

Econ-O-Coil Supply

78-5/8 (1997)

22-1/4 (565)

2-1/8 Cu Sweat

 

 

 

 

 

ECR**

Econ-O-Coil Return

72 (1829)

29 (737)

2-1/8 Cu Sweat

 

 

 

 

 

 

HS

Hot Water Reheat Supply

 

 

Consult Factory

 

 

 

 

 

HR

Hot Water Reheat Return

 

 

Consult Factory

 

 

 

 

 

E1

Electrical Connection (High Volt)

78-1/2 (1994)

31-1/8 (790)

2-1/2

 

 

 

 

 

E2

Electrical Connection (High Volt)

75-3/8 (1915)

31-1/8 (790)

2-1/2

 

 

 

 

 

 

LV1

Electrical Connection (Low Volt)

1-7/8

(48)

28-1/2 (724)

7/8

 

 

 

 

 

 

LV2

Electrical Connection (Low Volt)

1-7/8

(48)

30-1/4 (768)

7/8

 

 

 

 

 

 

LV3

Electrical Connection (Low Volt)

1-7/8

(48)

32 (813)

7/8

 

 

 

 

 

B1

Blower Outlet (15 x 15)

23-1/8 (587)

18-1/16 (459)

18-3/4 x 16-1/16 (476 x 408)

 

 

 

 

 

Blower Outlet (15 x 11)

27-3/4

(705)

18-1/16 (459)

14-3/4 x16-1/16 (375 x 408)

 

 

 

 

 

 

B2

Blower Outlet (15 x 15)

50-3/8 (1280)

18-1/16 (459)

18-3/4 x 16-1/16 (476 x 408)

 

 

 

 

 

Blower Outlet (15 x 11)

54-3/8 (1381)

18-1/16 (459)

14-3/4 x16-1/16 (375 x 408)

 

 

 

 

 

 

 

*Field-pitch condensate drain line a minimum of 1/8" (3.2mm) per foot (305mm). All units contain a factory-installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes.

**Supplied on Dual-Cool systems only (4-pipe system)

96

Page 106
Image 106
Liebert DS user manual DPN000933, 16-1/16, 408mm