Figure 18 Cabinet and floor planning dimensions—upflow, air-cooled, 53-77kW (15-22 ton), scroll or digital scroll compressor models

Liebert DS Dimensions and Weights

Figure 18 Cabinet and floor planning dimensions—upflow, air-cooled, 53-77kW (15-22 ton), scroll or digital scroll compressor models

Alternate Refrigerant

Piping Entrance

33"

(838mm)

35"

 

3/4"

Minimum required

(889mm)

 

(19mm)

for blower replacement

 

 

 

 

Bezels

 

 

Top View

Low Volt

 

 

High Volt

Connection(s)

 

 

Connection(s)

 

 

 

 

1-1/2"

98"

 

24"

(2489mm)

 

(38mm)

 

(610mm)

 

 

 

76"

(1930mm)

2"

97"

(51mm)

(2464mm)

Front View

34"

(864mm)

Shaded area indicates a recommended minimum clearance for component access.

Note: Front air return unit shown. For rear return unit, in addition to front service area shown, also include 25" (635mm) on one side of unit for access to rear return filter box. See DPN001196, Figure 28.

DPN001166

Rev. 1

Table 15 Weight for upflow, air-cooled, 53-77kW (15-22 ton), scroll or digital scroll compressor models

 

Dry Weight, lb (kg) approximate

Model No.

 

053, 070, 077

 

 

Air-Cooled

2070 (939)

 

 

Dual-Cool

2250 (1021)

 

 

23