Piping Schematics

Figure 70 Primary connection locations—downflow, air-Cooled, 53-77kW (15-22 ton) with scroll compressor models

Note: Drawing not to scale

Tolerance on all piping dimensions A is ± 1/2" (13mm)

 

 

 

 

 

All dimensions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

from rear corner

 

 

 

 

 

 

of unit including

 

 

 

 

 

 

 

 

 

 

A

panels

 

Front View

 

 

 

 

 

 

 

 

 

X

 

Section A-A

 

 

 

O

 

 

 

 

 

 

 

 

 

 

 

 

4" (102mm)

 

Blower

 

 

Blower

 

R

16-1/16"

Y

Outlet

(408mm)

Outlet

 

 

 

 

L1

L2

G 1

G2

 

 

B1

35"

 

 

 

 

 

B2

 

 

 

 

 

 

 

 

 

 

 

 

(889mm)

 

 

 

 

ECS

 

 

 

 

 

 

 

 

 

12-3/16"

HUM ECR

LV1

(310mm)

CD

LV2

 

 

LV3

 

E1 E2

Front of Unit

98"

(2489mm)

DPN000929

Rev. 2

 

 

X

Y

Connection Size / Opening

Point

Description

inches (mm)

inches (mm)

inches (mm)

 

 

 

 

 

R

Refrigerant Access

81-3/4 (2076)

14-3/4 (374)

12-3/16 x 4 (310 x 102)

 

 

 

 

 

 

 

 

53kW (15ton) / 70 & 77kW (20 & 22ton)

 

 

 

 

 

L1

Liquid Line System 1

94-11/16 (2405)

16-3/4 (425)

1/2 / 5/8 Cu Sweat

 

 

 

 

 

L2

Liquid Line System 2

91-7/8 (2334)

16-3/4 (425)

1/2 / 5/8 Cu Sweat

 

 

 

 

 

G1

Hot Gas Discharge 1

88-3/4 (2254)

16-3/8 (416)

7/8 / 1-1/8 Cu Sweat

G2

Hot Gas Discharge 2

85-9/16 (2173)

16-3/8 (416)

7/8 / 1-1/8 Cu Sweat

 

 

 

 

 

CD

Condensate Drain *

69-1/4 (1759)

30 (762)

3/4 FPT

 

 

 

 

W/ Optional Pump

69-1/4 (1759)

30 (762)

1/2 Cu Sweat

 

HUM

Humidifier Supply Line

76-1/2 (1943)

29 (736)

1/4 Cu Sweat

 

 

 

 

 

ECS**

Econ-O-Coil Supply

78-5/8 (1997)

22-1/4 (565)

2-1/8 Cu Sweat

 

 

 

 

 

ECR**

Econ-O-Coil Return

72 (1829)

29 (737)

2-1/8 Cu Sweat

HS

Hot Water Reheat Supply

 

Consult Factory

 

 

 

 

HR

Hot Water Reheat Return

 

Consult Factory

 

 

 

 

 

E1

Electrical Connection (High Volt)

78-1/2 (1994)

31-1/8 (790)

2-1/2

E2

Electrical Connection (High Volt)

75-3/8 (1915)

31-1/8 (790)

2-1/2

 

 

 

 

 

LV1

Electrical Connection (Low Volt)

1-7/8 (48)

28-1/2 (724)

7/8

 

 

 

 

 

LV2

Electrical Connection (Low Volt)

1-7/8 (48)

30-1/4 (768)

7/8

LV3

Electrical Connection (Low Volt)

1-7/8 (48)

32 (813)

7/8

 

 

 

 

 

B1

Blower Outlet (15 x 15)

23-1/8 (587)

18-1/16 (459)

18-3/4 x 16-1/16 (476 x 408)

 

 

 

 

Blower Outlet (15 x 11)

27-3/4 (705)

18-1/16 (459)

14-3/4 x 16-1/16 (375 x 408)

 

B2

Blower Outlet (15 x 15)

50-3/8 (1280)

18-1/16 (459)

18-3/4 x 16-1/16 (476 x 408)

 

 

 

 

Blower Outlet (15 x 11)

54-3/8 (1381)

18-1/16 (459)

14-3/4 (375) x 16-1/16 (408)

 

 

 

 

 

 

*Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory installed condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes.