Liebert DS user manual Top View, Front View

Models: DS

1 136
Download 136 pages 14.39 Kb
Page 27
Image 27
Top View

Liebert DS Dimensions and Weights

Figure 12 Cabinet and floor planning dimensions—downflow, air-cooled, 105kW (30 ton), all compressor models

 

Second Refrigerant

 

Piping Entrance

 

102-13/16"Opening

 

(2611mm)

33"

 

(838mm)

Air Inlet Opening

35"

(889mm)

Top View

Notes: Filters are accessible only through top of unit. Downflow electrical connections can be made from top or bottom of unit.

24-3/8" Opening (619mm)

3/4" Bezels (19mm)

Secondary Entrance

Secondary Entrance

Minimum required

High Volt Connection(s)

Low Volt Connections

for filter replacement

 

132"

 

 

(3353mm)

 

15"

 

 

(381mm)

76"

(1930mm)

34" (864mm)

 

 

 

 

 

Shaded area indicates a

 

 

 

 

 

recommended minimum

 

 

Front View

clearance for component

 

 

access.

DPN001012

 

 

131"

 

 

 

 

 

 

 

(3327mm)

 

Rev. 2

Table 9

Weights for downflow, air-Cooled, 105kW (30 ton), all compressor models

 

 

 

 

 

 

 

 

 

Dry Weight, lb (kg) approximate

 

 

Compressor Type

 

 

 

 

Model

 

105

 

 

 

 

 

 

 

 

 

Semi-Hermetic Compressor

Air-Cooled

 

3040 (1382)

 

 

 

 

 

 

 

Dual-Cool

 

3400 (1545)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Scroll Compressor

Air-Cooled

 

2920 (1327)

 

 

 

 

 

 

 

Dual-Cool

 

3280 (1491)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

17

Page 27
Image 27
Liebert DS user manual Top View, Front View, Weights for downflow, air-Cooled, 105kW 30 ton, all compressor models