GE 5500 manual Auxiliary Control Switches, Series, Cooling Temperature Limits, Description

Page 12

Auxiliary Control Switches

These switches are located behind the room cabinet under the control panel.

2500 and 3500 Series

Switches

Description

 

 

(1)

ALL I2R

Heat pump override - Down - heat pump operation

 

 

Up - resistance heat only

(not used on 2500 series)

(2)

C:FAN

Fan control for cooling operation - Down - Fan Continuous

 

 

Up - Fan Cycle

 

(3)

H:FAN

Fan control for heating operation - Down - Fan Cycle

 

 

Up - Fan Continuous

 

(4)

CLASS 2

Remote Thermostat Mode

Down - Unit Control

 

 

Up - Remote Thermostat

 

(5)

LOAD SHED

Load Shedding when connected to Central Desk Control System

 

 

Down - Fan shuts off with unit Up - Fan under “Smart Fan” settings

(6)FREEZ S Freeze Sentinel Override - Down - Freeze Sentinel ON Up - Freeze Sentinel OFF

(7)

CONST FAN

Constant Fan - Fan runs when unit is in STOP mode

(8)

OCCUPIED

Occupancy Sensor Mode - Down - Unit Control

 

 

Up - Occupancy Sensor Connected

Temp L1 - Temp L3

Cooling temperature limiting

(See table at bottom of page)

Temp L4 - Temp L6

Heating temperature limiting

(See table at bottom of page)

Cooling and Heating temperature limits are set independently.

Temperature limiting switches in factory set down position except as noted.

Cooling Temperature Limits

Switches Up

LC Minimum Temperature

Switches Up

LC Minimum Temperature

NONE

1

1,2

2

2,3

1,2,3

1,3

3

60

64

66

68

70

72

74

76

 

 

Heating Temperature Limits

 

 

6

4,6

4,5,6

5,6

5

4,5

4

NONE

65

70

72

74

76

78

80

85

 

 

 

 

 

 

 

 

12

Image 12
Contents Architects and Engineers Design Data Manual Series Heat Pump with Backup Resistance Heat Quick Reference3500 Series Control Panel Series Cooling with Electric HeatSeries Control Panel EER COPCooling With Resistance Heat Newest Innovation from GETable of Contents Important NoticeIntroduction Optional Accessories of the Zoneline System Components of the Zoneline SystemDeluxe Series shown Zoneline Features Model Series UPCFeatures and Benefits Fan Only Setting HIGH/LOW Fan Cycle Switch SmartFanCompressor Restart Delay Electronic Temperature LimitingEasy Clean Air Discharge Area Up-Front Air FiltersConcealed Manual Vent Control Corrosion Protection OptionalAuxiliary Control Switches Cooling Temperature LimitsHeating Temperature Limits 3500 SeriesSeries DiagnosCentral Desk Control Remote Thermostat Control Resistance Heat ModelsRAK806 Universal Control Cover Label Heat Pump ModelsFeature Series See RAK806 Universal Control cover Label onFor Use With Mechanical 4-Wire Systems Only Remote Control Low Voltage WiringR1, R2, and R3 Special order, 100 piece minimum orderHeat Pumps and Energy Savings Balance PointHeat pump condensate Heat pump defrost Zoneline 5500 Series Heat Pump Operation Zoneline 5500 SeriesZoneline 5500 Series Heat Source Logic Application Comments Air DistributionRecommendation High Wall Mount For unitsDimensions Wall Case Sub-BaseRAK204 Wall Case Installation Data Window, Curtain and Panel Wall ConstructionGeneral Installation of Wall Case in Wall Opening Masonry Wall ConstructionBrick, Frame, Stucco and Shingle Construction Preparation of the Wall Case for All Types of ConstructionFraming for Wall Case Fastening Wall CaseWall Section Detailed Side View Room CabinetWall Case Room Wall Case CabinetRoom Cabinet Wall CaseWall Case Receptacle By OthersWall Case Installation Cord SET Connected CaulkCorner and lap joints be additionally sealed Page Recommend 2 to Adjustable Caulk Holes by InstallerShown with Access Covers Removed Alternates Small TOP ViewRAK204 Series SUB-BASE Installation and Electrical Data Chaseway OptionType B Screw Green Ground Metal Case Screw Clip Type D Type a To Secure Side ChannelsCondensate Disposal Systems Cooling CondensateTypical Installation Wall Case with RAD10 Drain KITRear Grille Wall Case Room CabinetNUT Molded Case RAB77 only Detail Gasket Cabinet Bottom Tube Cover PlateUSE Type a Screws for Both RAB71 and RAB77 Ducted Installations New Ducted InstallationsReplacements of Existing Ducted Units Ducted Application ConsiderationsDucted Application AZ2500/3500 Series Duct Adapter Extension has 1/2 InsulationSub-Base Installation Ducted Detailed Side Views AZ2500/3500 SeriesExterior Grilles Sample CalculationsPower Connection For Deluxe Series 2500 230/208 Volt Unit Installation Line Cord Connected Units230/208 Volt Unit Installation Permanent Connected Units 265 or 277 Volt Unit Installation Permanent Connected UnitsPower Connection Kits For Premium Series 230/208 Volt InstallationsReplacement of Existing Chassis Maximum Connected Load For Deluxe Series 2500 Cooling Performance Data Heat Pump Performance DataLatent System Capacity Formula for Calculating Operating Costs Using Above Data Normal Yearly Operating DataTypical 2500 Series Wiring Diagram Typical 2500 Series Schematic DiagramDrive Board Unit Typical 3500 Series Wiring Diagram Typical 3500 Series Schematic DiagramBoard Unit Typical 5500 Series Wiring Diagram Typical 5500 Series Schematic DiagramSuggested Bid Form Specifications Page Alternate specification for molded wall case Deluxe Line Dry Air 25 & 3500 Series Receptacles/Sub-Bases Complete Accessory List Kit Number Description For Additional Information Refer toGeneral Installation Suggestions Electrical Wiring InstallationNew Installations Replacement InstallationsAlphabetical Index CategoryZoneline

5500 specifications

The GE 5500 is a sophisticated gas turbine that represents a benchmark in the realm of power generation technology. Known for its impressive performance and efficiency, the GE 5500 has garnered attention in various industries, particularly in energy production. Designed for combined-cycle applications, this turbine effectively leverages both gas and steam cycles to optimize electricity generation.

One of the standout features of the GE 5500 is its advanced aerodynamics, which enhance the efficiency of the combustion process. The turbine employs state-of-the-art combustion technology that allows for high operational flexibility and minimizes emissions, meeting stringent environmental standards. This is particularly important in today’s energy landscape, where sustainability is a crucial focus.

The GE 5500 is equipped with a robust control system that utilizes digital twin technology. This innovative approach allows operators to simulate and analyze the performance of the turbine virtually, leading to improved operational efficiency and reduced downtime. Additionally, this turbine features an integrated health monitoring system that provides real-time data on performance metrics, allowing for predictive maintenance and enhancing overall reliability.

The materials used in the construction of the GE 5500 are engineered to withstand high temperatures and stress levels, ensuring longevity and durability. This includes high-performance alloys that maintain structural integrity even under extreme operating conditions.

Installation and maintenance of the GE 5500 are streamlined through its modular design, which simplifies access to components and reduces service time. This efficiency translates into lower operational costs, making the GE 5500 an economically favorable choice for utilities and independent power producers.

Furthermore, the GE 5500 can be integrated into a variety of power plant configurations, whether for peaking power or baseload operations, which adds to its versatility. Its ability to quickly ramp up production makes it particularly valuable in an energy market characterized by fluctuating demand.

Overall, the GE 5500 gas turbine is a remarkable engineering feat that combines cutting-edge technology with practical design. Its efficiency, reliability, and adaptability position it as a leading choice for power generation needs, meeting the requirements of modern energy systems while contributing to a more sustainable future.