GE 5500 manual Replacement of Existing Chassis

Page 43

Power Connection Kits For Premium Series (5500)

265 or 277 Volt Installations

National Electrical Code (Article 440 section G) requires permanent connection for installation on circuit in excess of 250 volts.

Permanent Connection Kits are available for 265 volt installations. The regular kit consists of a self-aligning 9-pin connector that plugs into a mating connector on the chassis, a length of power cord with the plug cap molded to the end. There are four 265 volt cord sets so that the desired heater KW will be achieved when the correct RAK5*** kit is selected. See chart below for guide. These cord sets will match the receptacle in the RAK204E Series sub-base. It is important that care be used in this selection process. This cord set, when used with the appropriate sub-base with provided chase way from the junction box to the sub-base, is considered to be permanently connected.

For those installations that require a method of direct connection using flexible or rigid conduit, the RAK4002B junction box (provided with chassis) can be used and the field supplied conduit attached to it. The universal cord set will be cut off and connections made inside the junction box.

See page 44 for total connected load for 5500 series units.

Electrical Wiring Information - 2500/3500/5500 Series

All Zoneline units are single phase 60 hertz units.

For all installations feeder, sub-feeder, branch circuit and electrical protective devices and selection must conform to the National Electrical Code and to local codes.

Maximum connected load in amperes, including demands for the electric heater and the fan motor, are shown on page 44. Branch circuit ampacity and electrical protective device sizing are shown on page 42 for 230/208 volt units and on this page for 265 volt units. (Although presented with Premium 5500 Series this information also is valid for Deluxe Series 2500 and 3500 Series units.)

More than one unit per branch circuit is not recommended; however, when in doubt, consult the National Electrical Code. All wiring, including installation of receptacle, must conform to local electrical regulations and codes.

Replacement of Existing Chassis

230/208 Volt and 265 Volt Units

There have been changes to NEC and improvements and modifications to the Zoneline chassis and sub-bases since the unit was first introduced. Some of these changes require alterations to be made when replacing an older unit with a new chassis.

Line Cord Connected Units

The plug configuration of new line cord connected units complies with the current NEC standards. Older installations may have wall receptacles that conformed to NEC standards at the time the building was constructed and may not match the configuration of the plug on the new line cord. Recommended solution is to change the wall receptacle to conform to current standard plug configuration. See chart on page 42 for current receptacle configuration.

Permanent Connected Units With Sub-base

If the existing unit is connected to a sub-base the installation of the new unit may involve modifying the existing installation slightly. It is recommended these modifications be made by a qualified electrician.

If the existing sub-base is the full width of the wall case, RAK201 sub-base access plate may be ordered and used to replace the cover on the old sub-base. Field supplied wiring, conduit and conduit connectors should be used to make connection between new chassis and the center knockout of the RAK201. The wiring connections should be made inside the sub-base and the RAK201 attached to the sub-base with the 2 screws provided.

If the existing sub-base is not the full width of the wall case the electrician will have to modify the existing cover plate to allow field supplied wiring, conduit, and conduit connectors to be run from the permanent connection kit to the sub-base.

Permanent

 

Heater

Circuit

Protective Device

Connection Kit

Voltage

KW

Ampacity

(Fuse Included)

 

 

 

 

 

 

 

RAK5152

265

1.7

15 Amp

15 Amp

 

RAK5172

265

3.0

15 Amp

15 Amp

 

 

 

 

 

 

 

 

RAK5202

265

3.7

20 Amp

20 Amp

 

 

 

 

 

 

 

 

RAK5302

265

5.0

30 Amp

30 Amp

 

 

 

 

 

 

 

 

 

NEMA7-15R; receptacle used on 265V sub-base

15 Amp

GE0715

 

 

 

 

 

 

NEMA7-20R; receptacle used on 265V sub-base

20 Amp

GE0720-3

 

 

 

 

 

 

NEMA7-30R; receptacle used on 265V sub-base

30 Amp

GE073

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RAK4002B Installed

RAK4002B

43

Image 43
Contents Architects and Engineers Design Data Manual Series Cooling with Electric Heat Series Heat Pump with Backup Resistance HeatQuick Reference 3500 Series Control PanelEER COP Series Control PanelNewest Innovation from GE Cooling With Resistance HeatImportant Notice Table of ContentsIntroduction Components of the Zoneline System Optional Accessories of the Zoneline SystemDeluxe Series shown UPC Zoneline Features Model SeriesFeatures and Benefits Electronic Temperature Limiting Fan Only Setting HIGH/LOWFan Cycle Switch SmartFan Compressor Restart DelayCorrosion Protection Optional Easy Clean Air Discharge AreaUp-Front Air Filters Concealed Manual Vent Control3500 Series Auxiliary Control SwitchesCooling Temperature Limits Heating Temperature LimitsDiagnos SeriesCentral Desk Control Resistance Heat Models Remote Thermostat ControlHeat Pump Models RAK806 Universal Control Cover LabelSee RAK806 Universal Control cover Label on Feature SeriesSpecial order, 100 piece minimum order For Use With Mechanical 4-Wire Systems OnlyRemote Control Low Voltage Wiring R1, R2, and R3Balance Point Heat Pumps and Energy SavingsHeat pump condensate Heat Pump Operation Zoneline 5500 Series Heat pump defrost Zoneline 5500 SeriesZoneline 5500 Series Heat Source Logic High Wall Mount For units Application CommentsAir Distribution RecommendationDimensions Sub-Base Wall CaseRAK204 Window, Curtain and Panel Wall Construction Wall Case Installation DataGeneral Preparation of the Wall Case for All Types of Construction Installation of Wall Case in Wall OpeningMasonry Wall Construction Brick, Frame, Stucco and Shingle ConstructionFastening Wall Case Framing for Wall CaseRoom Wall Case Cabinet Wall Section Detailed Side ViewRoom Cabinet Wall CaseBy Others RoomCabinet Wall Case Wall Case ReceptacleCaulk Wall Case Installation Cord SET ConnectedCorner and lap joints be additionally sealed Page TOP View Recommend 2 to Adjustable CaulkHoles by Installer Shown with Access Covers Removed Alternates SmallMetal Case Screw Clip Type D Type a To Secure Side Channels RAK204 Series SUB-BASE Installation and Electrical DataChaseway Option Type B Screw Green GroundCooling Condensate Condensate Disposal SystemsWall Case Room Cabinet Typical InstallationWall Case with RAD10 Drain KIT Rear GrilleGasket Cabinet Bottom Tube Cover Plate NUT Molded Case RAB77 only DetailUSE Type a Screws for Both RAB71 and RAB77 Ducted Application Considerations Ducted InstallationsNew Ducted Installations Replacements of Existing Ducted UnitsDuct Adapter Extension has 1/2 Insulation Ducted Application AZ2500/3500 SeriesDucted Detailed Side Views AZ2500/3500 Series Sub-Base InstallationSample Calculations Exterior Grilles265 or 277 Volt Unit Installation Permanent Connected Units Power Connection For Deluxe Series 2500230/208 Volt Unit Installation Line Cord Connected Units 230/208 Volt Unit Installation Permanent Connected Units230/208 Volt Installations Power Connection Kits For Premium SeriesReplacement of Existing Chassis Maximum Connected Load For Deluxe Series 2500 Heat Pump Performance Data Cooling Performance DataLatent System Capacity Normal Yearly Operating Data Formula for Calculating Operating Costs Using Above DataTypical 2500 Series Schematic Diagram Typical 2500 Series Wiring DiagramDrive Board Unit Typical 3500 Series Schematic Diagram Typical 3500 Series Wiring DiagramBoard Unit Typical 5500 Series Schematic Diagram Typical 5500 Series Wiring DiagramSuggested Bid Form Specifications Page Alternate specification for molded wall case Deluxe Line Dry Air 25 & 3500 Series Receptacles/Sub-Bases Kit Number Description For Additional Information Refer to Complete Accessory ListElectrical Wiring Installation General Installation SuggestionsReplacement Installations New InstallationsCategory Alphabetical IndexZoneline

5500 specifications

The GE 5500 is a sophisticated gas turbine that represents a benchmark in the realm of power generation technology. Known for its impressive performance and efficiency, the GE 5500 has garnered attention in various industries, particularly in energy production. Designed for combined-cycle applications, this turbine effectively leverages both gas and steam cycles to optimize electricity generation.

One of the standout features of the GE 5500 is its advanced aerodynamics, which enhance the efficiency of the combustion process. The turbine employs state-of-the-art combustion technology that allows for high operational flexibility and minimizes emissions, meeting stringent environmental standards. This is particularly important in today’s energy landscape, where sustainability is a crucial focus.

The GE 5500 is equipped with a robust control system that utilizes digital twin technology. This innovative approach allows operators to simulate and analyze the performance of the turbine virtually, leading to improved operational efficiency and reduced downtime. Additionally, this turbine features an integrated health monitoring system that provides real-time data on performance metrics, allowing for predictive maintenance and enhancing overall reliability.

The materials used in the construction of the GE 5500 are engineered to withstand high temperatures and stress levels, ensuring longevity and durability. This includes high-performance alloys that maintain structural integrity even under extreme operating conditions.

Installation and maintenance of the GE 5500 are streamlined through its modular design, which simplifies access to components and reduces service time. This efficiency translates into lower operational costs, making the GE 5500 an economically favorable choice for utilities and independent power producers.

Furthermore, the GE 5500 can be integrated into a variety of power plant configurations, whether for peaking power or baseload operations, which adds to its versatility. Its ability to quickly ramp up production makes it particularly valuable in an energy market characterized by fluctuating demand.

Overall, the GE 5500 gas turbine is a remarkable engineering feat that combines cutting-edge technology with practical design. Its efficiency, reliability, and adaptability position it as a leading choice for power generation needs, meeting the requirements of modern energy systems while contributing to a more sustainable future.