GE 5500 manual

Page 52

Additional specifications for GE Zoneline 3500 Series Packaged Terminal Heat Pump (for 5500 series units use specifications noted for 5500 series instead of these specifications).

Heat pump units shall automatically change from heat pump operation to electric resistance heat when heat pump operation is unable to produce sufficient heat to maintain room temperature within 2.7°F. of thermostat set point, or when the outdoor coil temperature falls below 9°F. - approximately 25°F. outdoor temperature.

Heat pump unit shall automatically begin a passive defrost cycle when the outdoor coil temperature drops below 9°F. Defrosting shall be accomplished by natural defrost with unit automatically reinitiating heat pump operation when outdoor coil reaches 37°F.

Unit shall be equipped with a temperature activated drain valve to allow water generated in heat pump operation and defrost cycles to drain into wall case rather than being deposited on outdoor coil.

Each time the heat mode is selected, or the unit is powered up in the heat mode selection, the heat pump will use electric resistance heat to bring room temperature to selected thermostat set point. Heat pump operation will be used on subsequent unit heating operation if the room temperature is within 2.7°F of the set point and the unit is not in the defrost cycle.

Unit shall have a switch concealed from room occupant to allow heat pump operation to be overridden and heat provided by electric resistance heat regardless of outdoor temperature.

In the event of compressor failure during heat pump operation, unit shall automatically switch to electric resistance heat to maintain selected room temperature regardless of outdoor temperatures.

Alternate specifications for GE Zoneline 5500 Series Packaged Terminal Heat Pump (for 3500 series units use specifications noted for 3500 series instead of these specifications).

Heat pump units shall provide operation that will either:

A)automatically phase in partial electric resistance heat, if outdoor temperature is below 46°F., simultaneously with heat pump if heat pump alone is unable to maintain room temperature; or B) use partial electric resistance heat simultaneous with heat pump operation any time the outdoor temperature is below 45°F. Selection of A or B operation is made by means of a selector switch concealed from room occupant. In either A or B operation the unit will switch to full resistance heat if room temperature continues to decline or the outdoor temperature falls below 25°F. If the outdoor temperature is above 46°F., unit will lock out electric resistance heat and operate on heat pump only.

Heat pump unit shall include Reverse Cycle Defrost that automatically begins a defrost cycle when microprocessor determines criteria for defrosting has been met. Defrosting shall be accomplished by systematically ceasing heat pump operation, pausing to allow internal refrigerant pressures to equalize, then operating the compressor with the flow of refrigerant reversed, to allow the hot gas to flow through the outdoor coil melting the accumulated frost. Unit shall automatically resume heat pump operation, after pausing to allow refrigerant pressures to equalize, at conclusion of defrost cycle.

Unit shall be equipped with a temperature activated drain valve to allow water generated in heat pump operation and defrost cycles to drain into wall case rather than being deposited on outdoor coil.

Each time the heat mode is selected, or the unit is powered up in the heat mode selection, the heat pump will use electric resistance heat to bring room temperature to selected thermostat set point. Heat pump operation will be used on subsequent unit heating operation if the room temperature is within 2.7°F of the set point and the unit is not in the defrost cycle.

Unit shall have a switch concealed from room occupant to allow heat pump operation to be overridden and heat provided by electric resistance heat regardless of outdoor temperature.

In the event of compressor failure during heat pump operation, unit shall automatically switch to electric resistance heat to maintain selected room temperature regardless of outdoor temperatures.

Specifications for Optional Internal Condensate Removal (ICR) system for Zoneline 3500 or 5500 series heat pump units.

Unit shall have a factory installed Internal Condensate Removal (ICR) system to permit unit to automatically dispose of heat pump generated condensate water with no overflow to outdoors to occur during heating under outdoor ambient of 55°F. Dry Bulb, 90% Relative Humidity; indoor ambient 70°F. Dry Bulb, 52% Relative Humidity, for four hours of continuous run time.

52

Image 52
Contents Architects and Engineers Design Data Manual Series Heat Pump with Backup Resistance Heat Quick Reference3500 Series Control Panel Series Cooling with Electric HeatSeries Control Panel EER COPCooling With Resistance Heat Newest Innovation from GETable of Contents Important NoticeIntroduction Components of the Zoneline System Optional Accessories of the Zoneline SystemDeluxe Series shown Zoneline Features Model Series UPCFeatures and Benefits Fan Only Setting HIGH/LOW Fan Cycle Switch SmartFanCompressor Restart Delay Electronic Temperature LimitingEasy Clean Air Discharge Area Up-Front Air FiltersConcealed Manual Vent Control Corrosion Protection OptionalAuxiliary Control Switches Cooling Temperature LimitsHeating Temperature Limits 3500 SeriesSeries DiagnosCentral Desk Control Remote Thermostat Control Resistance Heat ModelsRAK806 Universal Control Cover Label Heat Pump ModelsFeature Series See RAK806 Universal Control cover Label onFor Use With Mechanical 4-Wire Systems Only Remote Control Low Voltage WiringR1, R2, and R3 Special order, 100 piece minimum orderBalance Point Heat Pumps and Energy SavingsHeat pump condensate Heat Pump Operation Zoneline 5500 Series Heat pump defrost Zoneline 5500 SeriesZoneline 5500 Series Heat Source Logic Application Comments Air DistributionRecommendation High Wall Mount For unitsDimensions Sub-Base Wall CaseRAK204 Window, Curtain and Panel Wall Construction Wall Case Installation DataGeneral Installation of Wall Case in Wall Opening Masonry Wall ConstructionBrick, Frame, Stucco and Shingle Construction Preparation of the Wall Case for All Types of ConstructionFraming for Wall Case Fastening Wall CaseWall Section Detailed Side View Room CabinetWall Case Room Wall Case CabinetRoom Cabinet Wall CaseWall Case Receptacle By OthersWall Case Installation Cord SET Connected CaulkCorner and lap joints be additionally sealed Page Recommend 2 to Adjustable Caulk Holes by InstallerShown with Access Covers Removed Alternates Small TOP ViewRAK204 Series SUB-BASE Installation and Electrical Data Chaseway OptionType B Screw Green Ground Metal Case Screw Clip Type D Type a To Secure Side ChannelsCondensate Disposal Systems Cooling CondensateTypical Installation Wall Case with RAD10 Drain KITRear Grille Wall Case Room CabinetGasket Cabinet Bottom Tube Cover Plate NUT Molded Case RAB77 only DetailUSE Type a Screws for Both RAB71 and RAB77 Ducted Installations New Ducted InstallationsReplacements of Existing Ducted Units Ducted Application ConsiderationsDucted Application AZ2500/3500 Series Duct Adapter Extension has 1/2 InsulationSub-Base Installation Ducted Detailed Side Views AZ2500/3500 SeriesExterior Grilles Sample CalculationsPower Connection For Deluxe Series 2500 230/208 Volt Unit Installation Line Cord Connected Units230/208 Volt Unit Installation Permanent Connected Units 265 or 277 Volt Unit Installation Permanent Connected UnitsPower Connection Kits For Premium Series 230/208 Volt InstallationsReplacement of Existing Chassis Maximum Connected Load For Deluxe Series 2500 Cooling Performance Data Heat Pump Performance DataLatent System Capacity Formula for Calculating Operating Costs Using Above Data Normal Yearly Operating DataTypical 2500 Series Schematic Diagram Typical 2500 Series Wiring DiagramDrive Board Unit Typical 3500 Series Schematic Diagram Typical 3500 Series Wiring Diagram Board Unit Typical 5500 Series Wiring Diagram Typical 5500 Series Schematic DiagramSuggested Bid Form Specifications Page Alternate specification for molded wall case Deluxe Line Dry Air 25 & 3500 Series Receptacles/Sub-Bases Complete Accessory List Kit Number Description For Additional Information Refer toGeneral Installation Suggestions Electrical Wiring InstallationNew Installations Replacement InstallationsAlphabetical Index CategoryZoneline