GE 5500 manual New Ducted Installations, Ducted Application Considerations

Page 37
Duct Adapter RAK6052
RAK601 Duct Extension,
Mounting Collar and Register

Ducted Installations

2500 and 3500 Series Zoneline units may be used in ducted installations.

With a ducted installation it is possible to condition the air in two areas that have a common wall separating them. A special adapter mounts on the wall case and a transition piece directs the air from the unit into the adapter. Instructions for mounting the adapter to the wall case are included with the duct adapter. The adapter contains a grille that allows air from the unit to be discharged into the primary room and the adapter connects to a duct extension that allows the air to flow to the adjoining room. Ducting a unit may allow a single unit to be used rather than a separate unit in each room, providing a means of reducing initial equipment cost. The duct may extend a total of 15 feet (with a field fabricated insulated duct extension) in one direction, either to the right or to the left of the unit. A baffle in the adapter allows up to 50% of the discharge air to be delivered to the secondary room.

The installation of the wall case and sub-base, if used, is the same for units being ducted as for free-standing units. The duct adapter support bracket overlaps the wall case by 1" and the bracket and mounting screws add approximately 3/8" (3/16" on each side) to the width of the wall case. If less than 1" of the wall case projects into the room it will be necessary to allow for the additional width in the opening for the wall case. The duct adapter mounting brackets should be mounted prior to installing the case in the wall.

Refer to pages 38 and 39 for drawings of ducted installations.

Prior to the installation of the transition from the room cabinet to the adapter, it will be necessary to remove the discharge grille from the room cabinet. Instructions for this modification are included with the duct adapter.

New Ducted Installations

Components

Duct Adapter RAK6052 - The duct adapter is secured to each side of the wall case and requires the drilling of mounting holes

in the wall case during installation.

A template for the hole location is in the installation instructions. By securing the duct adapter to the

wall case, the chassis retains the slide-out feature for servicing after the transition piece is removed.

Duct Extension RAK601 - This kit contains a 44" long insulated duct, a register mounting collar, and an air supply register. It can be secured to the duct adapter at either end of the adapter. This duct may be cut at any dimension and used in two applications providing the sum of the two duct lengths necessary do not exceed the 44" length. Even in single applications the mounting flange must be cut off one end of the duct to accept the collar and supply register.

Mounting Collar and Supply Register RAK602 These components are included in the Duct Extension Kit RAK601. They

may be ordered separately for installations where two duct extensions are made from one RAK601.

Ducted Application

Considerations

When designing a ducted application some application considerations to be made include:

1.Do not exceed the 15 foot length maximum for the duct extension. Field supplied duct extension must be completely insulated with minimum of 1/2" insulation

2.The duct must be a straight run. Turns or bends in the duct extension create air pressure drops that the unit is not designed to overcome.

3.Minimum recommended clearance between the unit and the adjacent wall is 2".

4.Provisions for return air must be made to allow air circulation from secondary room. Doors in both secondary and primary rooms may be undercut or a return grille may be installed through a common wall.

5.When calculating the heat gain / heat loss take both areas into consideration.

Replacements of Existing Ducted Units

Since the design of the Zoneline chassis has changed over the years to provide better performance and appearance, some of the components used in ducted applications have changed. Select the proper components from the information below. The best procedure in determining the correct kit is to measure duct extension cross section.

Flat Top-Discharge Units

(Zoneline Units Built Prior to 1988)

Existing Duct Extension Cross Section Measurements: 8-3/8" height x 6-1/2" width

Duct Adapter RAK7012 - This duct adapter will allow the replacement of a new chassis (2500 or 3500 Series unit) into an existing ducted application. This adapter will align properly with the duct extension and will eliminate the need to modify the wall opening. In order to minimize replacement costs, some of the components of the old duct adapter must be removed and used in the new installation. Consult the Installation Instructions of the RAK7012 before removing and discarding the old duct adapter. See additional notes page 58.

Slope-Front Discharge Units

(Models With AZC, AZR, AZW, or AZ21 or AZ31 Prefix)

Existing Duct Extension Cross Section Measurements: 7-3/32" height x 6-1/2" width

Duct Transition RAK7022 - This duct transition will allow the replacement of a new slope-front discharge Zoneline chassis (2500 or 3500 Series unit) into a previous design slope-front ducted installation. See additional notes page 58.

37

Image 37
Contents Architects and Engineers Design Data Manual Quick Reference Series Heat Pump with Backup Resistance Heat3500 Series Control Panel Series Cooling with Electric HeatEER COP Series Control PanelNewest Innovation from GE Cooling With Resistance HeatImportant Notice Table of ContentsIntroduction Components of the Zoneline System Optional Accessories of the Zoneline SystemDeluxe Series shown UPC Zoneline Features Model SeriesFeatures and Benefits Fan Cycle Switch SmartFan Fan Only Setting HIGH/LOWCompressor Restart Delay Electronic Temperature LimitingUp-Front Air Filters Easy Clean Air Discharge AreaConcealed Manual Vent Control Corrosion Protection OptionalCooling Temperature Limits Auxiliary Control SwitchesHeating Temperature Limits 3500 SeriesDiagnos SeriesCentral Desk Control Resistance Heat Models Remote Thermostat ControlHeat Pump Models RAK806 Universal Control Cover LabelSee RAK806 Universal Control cover Label on Feature SeriesRemote Control Low Voltage Wiring For Use With Mechanical 4-Wire Systems OnlyR1, R2, and R3 Special order, 100 piece minimum orderBalance Point Heat Pumps and Energy SavingsHeat pump condensate Heat Pump Operation Zoneline 5500 Series Heat pump defrost Zoneline 5500 SeriesZoneline 5500 Series Heat Source Logic Air Distribution Application CommentsRecommendation High Wall Mount For unitsDimensions Sub-Base Wall CaseRAK204 Window, Curtain and Panel Wall Construction Wall Case Installation DataGeneral Masonry Wall Construction Installation of Wall Case in Wall OpeningBrick, Frame, Stucco and Shingle Construction Preparation of the Wall Case for All Types of ConstructionFastening Wall Case Framing for Wall CaseRoom Cabinet Wall Section Detailed Side ViewWall Case Room Wall Case CabinetCabinet Wall Case RoomWall Case Receptacle By OthersCaulk Wall Case Installation Cord SET ConnectedCorner and lap joints be additionally sealed Page Holes by Installer Recommend 2 to Adjustable CaulkShown with Access Covers Removed Alternates Small TOP ViewChaseway Option RAK204 Series SUB-BASE Installation and Electrical DataType B Screw Green Ground Metal Case Screw Clip Type D Type a To Secure Side Channels Cooling Condensate Condensate Disposal SystemsWall Case with RAD10 Drain KIT Typical InstallationRear Grille Wall Case Room CabinetGasket Cabinet Bottom Tube Cover Plate NUT Molded Case RAB77 only DetailUSE Type a Screws for Both RAB71 and RAB77 New Ducted Installations Ducted InstallationsReplacements of Existing Ducted Units Ducted Application ConsiderationsDuct Adapter Extension has 1/2 Insulation Ducted Application AZ2500/3500 SeriesDucted Detailed Side Views AZ2500/3500 Series Sub-Base InstallationSample Calculations Exterior Grilles230/208 Volt Unit Installation Line Cord Connected Units Power Connection For Deluxe Series 2500230/208 Volt Unit Installation Permanent Connected Units 265 or 277 Volt Unit Installation Permanent Connected Units230/208 Volt Installations Power Connection Kits For Premium SeriesReplacement of Existing Chassis Maximum Connected Load For Deluxe Series 2500 Heat Pump Performance Data Cooling Performance DataLatent System Capacity Normal Yearly Operating Data Formula for Calculating Operating Costs Using Above DataTypical 2500 Series Schematic Diagram Typical 2500 Series Wiring DiagramDrive Board Unit Typical 3500 Series Schematic Diagram Typical 3500 Series Wiring DiagramBoard Unit Typical 5500 Series Schematic Diagram Typical 5500 Series Wiring DiagramSuggested Bid Form Specifications Page Alternate specification for molded wall case Deluxe Line Dry Air 25 & 3500 Series Receptacles/Sub-Bases Kit Number Description For Additional Information Refer to Complete Accessory ListElectrical Wiring Installation General Installation SuggestionsReplacement Installations New InstallationsCategory Alphabetical IndexZoneline