Remote Thermostat Control

When connected to a remote thermostat, the indoor air temperature sensing is shifted from the unit to the remote thermostat. For this reason, the units will operate slightly differently when connected to a remote thermostat. The following chart shows the unit operation when connected to a remote thermostat.

Feature

3500 Series

5500 Series

Indoor Frost Control

Yes

Yes

Freeze Sentinel

Yes

Yes

Auto Fan Speed

No

No

Electronic Temperature Limiting

No

No

Switch to Resistance Heat Based

Determined by

Determined by

On Indoor Temperature

Remote Thermostat

Remote Thermostat

Switch to Resistance Heat Based

 

 

On Outdoor Temperature

Yes

Yes

Reverse Cycle Defrost

Yes

Simultaneous Resistance Heat

 

 

with Heat Pump

No

Resistance Heat Lockout

Yes

“Smart Fan” Fan Cycle

Fan ON/AUTO Set On

Fan ON/AUTO Set On

 

Remote Thermostat

Remote Thermostat

Central Desk Control

Yes

Yes

Temperature Boost option should not be used with remote thermostat operation since this will cause the unit to switch to resistance heat when outdoor temperatures are below 46°F.

See RAK806 Universal Control cover Label on page 15.

R

GL

GH

B

Y

W

C

Common - Ground

White - Heater

Yellow - Compressor

Black - Not Used On 2500

Green - High Speed Fan

Green - Low Speed Fan

Red - 24 VAC

Remote Thermostat Control Selection Chart For Zoneline Packaged Terminal Units

 

 

 

 

LOW

ZONELINE

THERMOSTAT

 

 

VOLTAGE

SERIES

MODEL

TYPE

FUNCTION

CONDUCTORS

 

RAK163A1

Mechanical

 

4

 

 

 

Cooling and Heating

5

2500

RAK163D1

Digital

 

RAK163P1

Digital Programmable

 

5

 

 

 

 

 

 

RAK147

Mechanical

Single Stage

6

 

 

 

Cooling

6

3500 and

RAK147D1

Digital

5500

RAK147P1

Digital Programmable

2 - Stage Heating

6

Thermostat wire size - up to 60 feet AWG20 - up to 66 feet AWG18

17

Image 17
Contents Architects and Engineers Design Data Manual Quick Reference Series Heat Pump with Backup Resistance Heat3500 Series Control Panel Series Cooling with Electric HeatEER COP Series Control PanelNewest Innovation from GE Cooling With Resistance HeatImportant Notice Table of ContentsIntroduction Deluxe Series shown Optional Accessories of the Zoneline SystemComponents of the Zoneline System UPC Zoneline Features Model SeriesFeatures and Benefits Fan Cycle Switch SmartFan Fan Only Setting HIGH/LOWCompressor Restart Delay Electronic Temperature LimitingUp-Front Air Filters Easy Clean Air Discharge AreaConcealed Manual Vent Control Corrosion Protection OptionalCooling Temperature Limits Auxiliary Control SwitchesHeating Temperature Limits 3500 SeriesDiagnos Series Central Desk Control Resistance Heat Models Remote Thermostat ControlHeat Pump Models RAK806 Universal Control Cover LabelSee RAK806 Universal Control cover Label on Feature SeriesRemote Control Low Voltage Wiring For Use With Mechanical 4-Wire Systems OnlyR1, R2, and R3 Special order, 100 piece minimum orderHeat pump condensate Heat Pumps and Energy SavingsBalance Point Zoneline 5500 Series Heat Source Logic Heat pump defrost Zoneline 5500 SeriesHeat Pump Operation Zoneline 5500 Series Air Distribution Application CommentsRecommendation High Wall Mount For unitsDimensions RAK204 Wall CaseSub-Base General Wall Case Installation DataWindow, Curtain and Panel Wall Construction Masonry Wall Construction Installation of Wall Case in Wall OpeningBrick, Frame, Stucco and Shingle Construction Preparation of the Wall Case for All Types of ConstructionFastening Wall Case Framing for Wall CaseRoom Cabinet Wall Section Detailed Side ViewWall Case Room Wall Case CabinetCabinet Wall Case RoomWall Case Receptacle By OthersCaulk Wall Case Installation Cord SET ConnectedCorner and lap joints be additionally sealed Page Holes by Installer Recommend 2 to Adjustable CaulkShown with Access Covers Removed Alternates Small TOP ViewChaseway Option RAK204 Series SUB-BASE Installation and Electrical DataType B Screw Green Ground Metal Case Screw Clip Type D Type a To Secure Side ChannelsCooling Condensate Condensate Disposal SystemsWall Case with RAD10 Drain KIT Typical InstallationRear Grille Wall Case Room CabinetUSE Type a Screws for Both RAB71 and RAB77 NUT Molded Case RAB77 only DetailGasket Cabinet Bottom Tube Cover Plate New Ducted Installations Ducted InstallationsReplacements of Existing Ducted Units Ducted Application ConsiderationsDuct Adapter Extension has 1/2 Insulation Ducted Application AZ2500/3500 SeriesDucted Detailed Side Views AZ2500/3500 Series Sub-Base InstallationSample Calculations Exterior Grilles230/208 Volt Unit Installation Line Cord Connected Units Power Connection For Deluxe Series 2500230/208 Volt Unit Installation Permanent Connected Units 265 or 277 Volt Unit Installation Permanent Connected Units230/208 Volt Installations Power Connection Kits For Premium SeriesReplacement of Existing Chassis Maximum Connected Load For Deluxe Series 2500 Heat Pump Performance Data Cooling Performance DataLatent System Capacity Normal Yearly Operating Data Formula for Calculating Operating Costs Using Above DataDrive Board Unit Typical 2500 Series Wiring DiagramTypical 2500 Series Schematic Diagram Board Unit Typical 3500 Series Wiring DiagramTypical 3500 Series Schematic Diagram Typical 5500 Series Schematic Diagram Typical 5500 Series Wiring DiagramSuggested Bid Form Specifications Page Alternate specification for molded wall case Deluxe Line Dry Air 25 & 3500 Series Receptacles/Sub-Bases Kit Number Description For Additional Information Refer to Complete Accessory ListElectrical Wiring Installation General Installation SuggestionsReplacement Installations New InstallationsCategory Alphabetical IndexZoneline