GE 5500 manual For Use With Mechanical 4-Wire Systems Only, Remote Control Low Voltage Wiring

Page 18

Remote Thermostat Control

Multiple Units Connected to One Remote Thermostat (2500 Series)

One remote control thermostat may be used to control multiple resistance heat Zoneline units, however the units may not be wired direct. Since each Zoneline unit has an integral transformer, direct wiring can result in a “bucking”

or “boosting” voltage condition, and is in violation of the National Electric Code. The diagram below shows the correct wiring for such an installation through the use of field supplied isolation relays.

For Use With Mechanical 4-Wire Systems Only

Remote Control (Low Voltage) Wiring

One stage Thermostat Controlling Three Zoneline Units

Resistance Heat Zoneline 2500 Series Units

(Not Applicable on Heat Pump Units)

FIELD SUPPLIED RELAY SPECIFICATIONS

NUMBER OF

RELAY DESIGNATION

UNITS CONTROLLED

R1, R2, and R3

2

POTTER and BRUMFIELD TYPE KA11AY-24 OR EQUIVALENT

3

POTTER and BRUMFIELD TYPE KA14AY-24* OR EQUIVALENT

4

POTTER and BRUMFIELD TYPE KU17A11-24* OR EQUIVALENT

MORE THAN 4

USE COMBINATION OF RELAYS SPECIFIED ABOVE

NOTE: Current draw through thermostat contacts should not exceed 1.0 amps.

*Special order, 100 piece minimum order.

18

Image 18
Contents Architects and Engineers Design Data Manual 3500 Series Control Panel Series Heat Pump with Backup Resistance HeatQuick Reference Series Cooling with Electric HeatSeries Control Panel EER COPCooling With Resistance Heat Newest Innovation from GETable of Contents Important NoticeIntroduction Optional Accessories of the Zoneline System Components of the Zoneline SystemDeluxe Series shown Zoneline Features Model Series UPCFeatures and Benefits Compressor Restart Delay Fan Only Setting HIGH/LOWFan Cycle Switch SmartFan Electronic Temperature LimitingConcealed Manual Vent Control Easy Clean Air Discharge AreaUp-Front Air Filters Corrosion Protection OptionalHeating Temperature Limits Auxiliary Control SwitchesCooling Temperature Limits 3500 SeriesSeries DiagnosCentral Desk Control Remote Thermostat Control Resistance Heat ModelsRAK806 Universal Control Cover Label Heat Pump ModelsFeature Series See RAK806 Universal Control cover Label onR1, R2, and R3 For Use With Mechanical 4-Wire Systems OnlyRemote Control Low Voltage Wiring Special order, 100 piece minimum orderHeat Pumps and Energy Savings Balance PointHeat pump condensate Heat pump defrost Zoneline 5500 Series Heat Pump Operation Zoneline 5500 SeriesZoneline 5500 Series Heat Source Logic Recommendation Application CommentsAir Distribution High Wall Mount For unitsDimensions Wall Case Sub-BaseRAK204 Wall Case Installation Data Window, Curtain and Panel Wall ConstructionGeneral Brick, Frame, Stucco and Shingle Construction Installation of Wall Case in Wall OpeningMasonry Wall Construction Preparation of the Wall Case for All Types of ConstructionFraming for Wall Case Fastening Wall CaseWall Case Wall Section Detailed Side ViewRoom Cabinet Room Wall Case CabinetWall Case Receptacle RoomCabinet Wall Case By OthersWall Case Installation Cord SET Connected CaulkCorner and lap joints be additionally sealed Page Shown with Access Covers Removed Alternates Small Recommend 2 to Adjustable CaulkHoles by Installer TOP ViewType B Screw Green Ground RAK204 Series SUB-BASE Installation and Electrical DataChaseway Option Metal Case Screw Clip Type D Type a To Secure Side ChannelsCondensate Disposal Systems Cooling CondensateRear Grille Typical InstallationWall Case with RAD10 Drain KIT Wall Case Room CabinetNUT Molded Case RAB77 only Detail Gasket Cabinet Bottom Tube Cover PlateUSE Type a Screws for Both RAB71 and RAB77 Replacements of Existing Ducted Units Ducted InstallationsNew Ducted Installations Ducted Application ConsiderationsDucted Application AZ2500/3500 Series Duct Adapter Extension has 1/2 InsulationSub-Base Installation Ducted Detailed Side Views AZ2500/3500 SeriesExterior Grilles Sample Calculations230/208 Volt Unit Installation Permanent Connected Units Power Connection For Deluxe Series 2500230/208 Volt Unit Installation Line Cord Connected Units 265 or 277 Volt Unit Installation Permanent Connected UnitsPower Connection Kits For Premium Series 230/208 Volt InstallationsReplacement of Existing Chassis Maximum Connected Load For Deluxe Series 2500 Cooling Performance Data Heat Pump Performance DataLatent System Capacity Formula for Calculating Operating Costs Using Above Data Normal Yearly Operating DataTypical 2500 Series Wiring Diagram Typical 2500 Series Schematic DiagramDrive Board Unit Typical 3500 Series Wiring Diagram Typical 3500 Series Schematic DiagramBoard Unit Typical 5500 Series Wiring Diagram Typical 5500 Series Schematic DiagramSuggested Bid Form Specifications Page Alternate specification for molded wall case Deluxe Line Dry Air 25 & 3500 Series Receptacles/Sub-Bases Complete Accessory List Kit Number Description For Additional Information Refer toGeneral Installation Suggestions Electrical Wiring InstallationNew Installations Replacement InstallationsAlphabetical Index CategoryZoneline