GE 5500 manual Application Comments, Air Distribution, Recommendation, High Wall Mount For units

Page 21

Application Comments

Use and Care Manual and installation instructions are shipped with Zoneline units. It is important that any air conditioning system be properly sized and applied in order to achieve the desired temperature and humidity levels with the space to be conditioned. Air conditioners are designed primarily to provide heating and cooling with the additional benefit that during operation in the cooling mode, the units also remove some moisture from the conditioned space. The following are some brief application comments on undersizing, oversizing, heating, wall coverings, and air infiltration: all are important in the proper matching of the heating/air conditioning system to the building structure.

Undersizing: If an air conditioner is undersized (cooling capacity is less than required for a specific application), the unit will typically not be able to cool the space down to the desired temperature (thermostat set point), nor be able to remove enough moisture from the air. A result could be a warm and humid or warm and dry conditioned space.

Oversizing: If an air conditioner is oversized (cooling capacity is greater than required for the specific application), the unit will typically cool the space down to the desired temperature (thermostat set point) too quickly. The compressor then begins to cycle on and off. Dehumidification only takes place when the compressor is operating. A typical result in a hot/humid climate could be a cool but excessively humid space.

Heating: Undersizing can result in not being able to maintain the desired temperature level within the conditioned space.

Wall Covering: Use of a non-permeable wall covering (some paints, some wallpapers, and other types of coverings) which severely restricts passage of air or water vapor can cause a severe moisture problem. Typical results could be staining of room surfaces, wall damage, as well as mold and mildew growth in hot/humid climates.

Air Infiltration: Excessive air infiltration can magnify problems associated with undersizing or oversizing of an air conditioner unit and can be the root cause of insufficient cooling, dehumidification, or heating. Some sources of air infiltration include vents, gaps around windows and doors, and improperly sealed floor, ceiling and wall joints.

Recommendation

For the above reasons it is strongly recommended that a professional engineer be retained to match the Zoneline unit with the building structure.

Air Distribution

Zoneline packaged terminal air conditioners and heat pumps discharge air from the top of the unit through reversible 2-position discharge louvers. Unit discharge louvers are reversed by removing the room cabinet from the unit, removing seven screws that hold the louver section in place, removing the louver section and rotating it end for

end, reinstalling the louver section in the room cabinet with the seven screws, and reinstalling the room cabinet on the unit. The unit is shipped from the factory with the discharge louvers at an angle of 50° off vertical. In the alternate position, the louvers will be at an angle of 40° off vertical.

All room cabinets return air through the front of the unit.

High Wall Mount - For units

 

mounted high in the wall, the

 

discharge louvers should be at a

 

setting that provides the most

 

horizontal air discharge.

 

Recommended installation is at

50°

least 3" below the ceiling. In

installations where units are

 

close to the ceiling, the most

 

horizontal discharge angle can

 

be obtained by removing the

 

discharge grill from the room

 

cabinet.

 

Supply Air Throw - One

40°

Zoneline unit should not be required to do a job obviously requiring two or more units.

Units should be located around large rooms according to calculated loads or in such

fashion as to achieve balanced air distribution in all parts of the room. The single unit in the “Incorrect” illustration below obviously cannot condition the entire room.

Add a second unit as shown in the “Correct” illustration.

INCORRECT

OVER 40 FT.

CORRECT

OVER 40 FT.

21

Image 21
Contents Architects and Engineers Design Data Manual Quick Reference Series Heat Pump with Backup Resistance Heat3500 Series Control Panel Series Cooling with Electric HeatEER COP Series Control PanelNewest Innovation from GE Cooling With Resistance HeatImportant Notice Table of ContentsIntroduction Optional Accessories of the Zoneline System Components of the Zoneline SystemDeluxe Series shown UPC Zoneline Features Model SeriesFeatures and Benefits Fan Cycle Switch SmartFan Fan Only Setting HIGH/LOWCompressor Restart Delay Electronic Temperature LimitingUp-Front Air Filters Easy Clean Air Discharge AreaConcealed Manual Vent Control Corrosion Protection OptionalCooling Temperature Limits Auxiliary Control SwitchesHeating Temperature Limits 3500 SeriesDiagnos SeriesCentral Desk Control Resistance Heat Models Remote Thermostat ControlHeat Pump Models RAK806 Universal Control Cover LabelSee RAK806 Universal Control cover Label on Feature SeriesRemote Control Low Voltage Wiring For Use With Mechanical 4-Wire Systems OnlyR1, R2, and R3 Special order, 100 piece minimum orderHeat Pumps and Energy Savings Balance PointHeat pump condensate Heat pump defrost Zoneline 5500 Series Heat Pump Operation Zoneline 5500 SeriesZoneline 5500 Series Heat Source Logic Air Distribution Application CommentsRecommendation High Wall Mount For unitsDimensions Wall Case Sub-BaseRAK204 Wall Case Installation Data Window, Curtain and Panel Wall ConstructionGeneral Masonry Wall Construction Installation of Wall Case in Wall OpeningBrick, Frame, Stucco and Shingle Construction Preparation of the Wall Case for All Types of ConstructionFastening Wall Case Framing for Wall CaseRoom Cabinet Wall Section Detailed Side ViewWall Case Room Wall Case CabinetCabinet Wall Case RoomWall Case Receptacle By OthersCaulk Wall Case Installation Cord SET ConnectedCorner and lap joints be additionally sealed Page Holes by Installer Recommend 2 to Adjustable CaulkShown with Access Covers Removed Alternates Small TOP ViewChaseway Option RAK204 Series SUB-BASE Installation and Electrical DataType B Screw Green Ground Metal Case Screw Clip Type D Type a To Secure Side ChannelsCooling Condensate Condensate Disposal SystemsWall Case with RAD10 Drain KIT Typical InstallationRear Grille Wall Case Room CabinetNUT Molded Case RAB77 only Detail Gasket Cabinet Bottom Tube Cover PlateUSE Type a Screws for Both RAB71 and RAB77 New Ducted Installations Ducted InstallationsReplacements of Existing Ducted Units Ducted Application ConsiderationsDuct Adapter Extension has 1/2 Insulation Ducted Application AZ2500/3500 SeriesDucted Detailed Side Views AZ2500/3500 Series Sub-Base InstallationSample Calculations Exterior Grilles230/208 Volt Unit Installation Line Cord Connected Units Power Connection For Deluxe Series 2500230/208 Volt Unit Installation Permanent Connected Units 265 or 277 Volt Unit Installation Permanent Connected Units230/208 Volt Installations Power Connection Kits For Premium SeriesReplacement of Existing Chassis Maximum Connected Load For Deluxe Series 2500 Heat Pump Performance Data Cooling Performance DataLatent System Capacity Normal Yearly Operating Data Formula for Calculating Operating Costs Using Above DataTypical 2500 Series Wiring Diagram Typical 2500 Series Schematic DiagramDrive Board Unit Typical 3500 Series Wiring Diagram Typical 3500 Series Schematic DiagramBoard Unit Typical 5500 Series Schematic Diagram Typical 5500 Series Wiring DiagramSuggested Bid Form Specifications Page Alternate specification for molded wall case Deluxe Line Dry Air 25 & 3500 Series Receptacles/Sub-Bases Kit Number Description For Additional Information Refer to Complete Accessory ListElectrical Wiring Installation General Installation SuggestionsReplacement Installations New InstallationsCategory Alphabetical IndexZoneline

5500 specifications

The GE 5500 is a sophisticated gas turbine that represents a benchmark in the realm of power generation technology. Known for its impressive performance and efficiency, the GE 5500 has garnered attention in various industries, particularly in energy production. Designed for combined-cycle applications, this turbine effectively leverages both gas and steam cycles to optimize electricity generation.

One of the standout features of the GE 5500 is its advanced aerodynamics, which enhance the efficiency of the combustion process. The turbine employs state-of-the-art combustion technology that allows for high operational flexibility and minimizes emissions, meeting stringent environmental standards. This is particularly important in today’s energy landscape, where sustainability is a crucial focus.

The GE 5500 is equipped with a robust control system that utilizes digital twin technology. This innovative approach allows operators to simulate and analyze the performance of the turbine virtually, leading to improved operational efficiency and reduced downtime. Additionally, this turbine features an integrated health monitoring system that provides real-time data on performance metrics, allowing for predictive maintenance and enhancing overall reliability.

The materials used in the construction of the GE 5500 are engineered to withstand high temperatures and stress levels, ensuring longevity and durability. This includes high-performance alloys that maintain structural integrity even under extreme operating conditions.

Installation and maintenance of the GE 5500 are streamlined through its modular design, which simplifies access to components and reduces service time. This efficiency translates into lower operational costs, making the GE 5500 an economically favorable choice for utilities and independent power producers.

Furthermore, the GE 5500 can be integrated into a variety of power plant configurations, whether for peaking power or baseload operations, which adds to its versatility. Its ability to quickly ramp up production makes it particularly valuable in an energy market characterized by fluctuating demand.

Overall, the GE 5500 gas turbine is a remarkable engineering feat that combines cutting-edge technology with practical design. Its efficiency, reliability, and adaptability position it as a leading choice for power generation needs, meeting the requirements of modern energy systems while contributing to a more sustainable future.