GE 5500 manual Wall Case Installation Data, Window, Curtain and Panel Wall Construction, General

Page 24

Sub-Base (Cont.)

There are separate internal compartments to permit separation of low voltage (Class 2) connections from line voltage connections as required by NEC. Conduit containing building wiring enters the sub-base through knockouts located in the rear or bottom of the sub-base and is not accessible when the wall case is installed.

The sub-base attaches to the RAB71 wall case with two clips (field assembled) that are screwed into pre-drilled holes in the bottom front flange of the wall case. It attaches to the RAB77 wall case with clips that fit over molded ribs without requiring the use of screws into the wall case. See page 33 for illustration. Since the sub-base extends under the wall case, clearance from the inner edge of the wall case to the finished wall must be 2-3/8" or greater. The sub-base has 4 leveling legs and adjustable side channels to enable the area under the wall case to be enclosed. Clearance from the bottom edge of the wall case to the finished floor must be between 3" and 5".

The sub-base may be used as support for the chassis and wall case in installations where the wall is of insufficient thickness to provide secure mounting of the wall case.

Wall Case Installation Data

General

Generally, Zoneline units are installed 3" to 5" above the floor (flush to finished floor installation is possible) as near to the center of the room as possible; underneath a window or a glass panel is typical. Normal installation of the wall case allows installation flexibility; from flush with the finished interior wall to a minimum of 1/4" of the wall case extending beyond the finished exterior of the building. Special consideration must be given to installations where the wall case does not extend a minimum of 1/4" beyond the finished exterior wall. See pages 30 and 31 for information on this type of installation. The unit may be installed high in the wall and these installations usually require a remote thermostat and are discussed on

pages 17 and 18.

Regardless of the installation, there are several things to consider when selecting a location for installing the unit. For instance, drapery location could interfere with air discharge, and placement of furniture may have an impact on the performance of the unit. The following information is intended to minimize installation problems and assure you of trouble-free installation.

Refer to page 22 for required wall opening dimensions. Minimum recommended interior and exterior case projection for standard wall thicknesses are shown in the drawings in this manual. The case may be installed flush with the finished indoor wall. Special attention must be paid to room-side case projection when the unit is installed in a ducted application as shown on page 39.

In walls thicker than 13 1/2" for line cord connected units and 11 1/8" for sub-base installations, it may be necessary to install a field fabricated case extension or use one of the special order RAB71 deep wall cases. If you are unable to locate a local source for case extensions please contact your salesperson for a possible supplier. Such extension must be carefully flashed and sealed both to the wall case and to the wall to insure water integrity. This is necessary to insure that

any water entering the wall case, either from operation of the unit or from other sources, such as rain storms or from washing the exterior of the building, will drain from the case without the possibility of capillary action drawing the water into either the room or the wall cavity. In an installation where the case is recessed less than 3" from the outside surface, flashing and sealing may be all the modificaton necessary. In such an installation, the sides and top of the wall opening must be waterproof to prevent moisture from seeping into and damaging the walls. See Pages 30 and 31 for suggested detail. Since the installation of a case extension requires a considerable amount of attention, we recommend using one of the deep wall cases if the standard case is not of sufficient depth.

Mounting an outdoor grille or louver section to the building face may cause a space between the outdoor coil and the louver section. Air splitters, aligned with the ends of the outdoor coil, must be installed between the outdoor coil inlet and outlet air streams. Gaps between the outdoor coil and the louver section may allow condenser air recirculation and affect the operation of the unit. See page 40 for requirements for custom louver sections.

The wall case should be level from side to side and from level to 1/4 bubble tilt to the outdoors. The condensate disposal system in the unit is designed to dissipate the condensate water generated during cooling operation in accordance with ARI standards and actually uses this water for maximum unit efficiency. A level unit will also insure proper performance of the Internal Condensate Removal (ICR) system optional on heat pump units.

For new construction, early planning with the architect is necessary. Unit location, electrical connection locations, and wall openings of the proper dimensions are essential to avoid the necessity of rework, fillers, framing, moving electrical outlets, and other expensive modifications.

For existing construction it is important that carpentry, masonry and electrical work be performed by competent, qualified personnel. Since installations in existing construction may involve removal of building material from the structure, locating the wall case must be done correctly.

Window, Curtain and Panel Wall Construction

With this type of construction, provision for support of the unit, other than by the wall itself, is often required. Such support may be in the form of wood or metallic material of the proper thickness to maintain a level case. This additional support should be located both near the wall and at the front of the wall case. Sub-base (RAK204 Series) with four leveling legs provides an excellent support for the unit in this type of installation. See page 28 for details of this type of installation.

In existing construction, common practice is to remove a pane of glass, metal, wood, or other construction material and build a frame around the wall case. Similar filler panel material may be installed around the case for appearance and weather seal.

24

Image 24
Contents Architects and Engineers Design Data Manual Series Heat Pump with Backup Resistance Heat Quick Reference3500 Series Control Panel Series Cooling with Electric HeatSeries Control Panel EER COPCooling With Resistance Heat Newest Innovation from GETable of Contents Important NoticeIntroduction Optional Accessories of the Zoneline System Components of the Zoneline SystemDeluxe Series shown Zoneline Features Model Series UPCFeatures and Benefits Fan Only Setting HIGH/LOW Fan Cycle Switch SmartFanCompressor Restart Delay Electronic Temperature LimitingEasy Clean Air Discharge Area Up-Front Air FiltersConcealed Manual Vent Control Corrosion Protection OptionalAuxiliary Control Switches Cooling Temperature LimitsHeating Temperature Limits 3500 SeriesSeries DiagnosCentral Desk Control Remote Thermostat Control Resistance Heat ModelsRAK806 Universal Control Cover Label Heat Pump ModelsFeature Series See RAK806 Universal Control cover Label onFor Use With Mechanical 4-Wire Systems Only Remote Control Low Voltage WiringR1, R2, and R3 Special order, 100 piece minimum orderHeat Pumps and Energy Savings Balance PointHeat pump condensate Heat pump defrost Zoneline 5500 Series Heat Pump Operation Zoneline 5500 SeriesZoneline 5500 Series Heat Source Logic Application Comments Air DistributionRecommendation High Wall Mount For unitsDimensions Wall Case Sub-BaseRAK204 Wall Case Installation Data Window, Curtain and Panel Wall ConstructionGeneral Installation of Wall Case in Wall Opening Masonry Wall ConstructionBrick, Frame, Stucco and Shingle Construction Preparation of the Wall Case for All Types of ConstructionFraming for Wall Case Fastening Wall CaseWall Section Detailed Side View Room CabinetWall Case Room Wall Case CabinetRoom Cabinet Wall CaseWall Case Receptacle By OthersWall Case Installation Cord SET Connected CaulkCorner and lap joints be additionally sealed Page Recommend 2 to Adjustable Caulk Holes by InstallerShown with Access Covers Removed Alternates Small TOP ViewRAK204 Series SUB-BASE Installation and Electrical Data Chaseway OptionType B Screw Green Ground Metal Case Screw Clip Type D Type a To Secure Side ChannelsCondensate Disposal Systems Cooling CondensateTypical Installation Wall Case with RAD10 Drain KITRear Grille Wall Case Room CabinetNUT Molded Case RAB77 only Detail Gasket Cabinet Bottom Tube Cover PlateUSE Type a Screws for Both RAB71 and RAB77 Ducted Installations New Ducted InstallationsReplacements of Existing Ducted Units Ducted Application ConsiderationsDucted Application AZ2500/3500 Series Duct Adapter Extension has 1/2 InsulationSub-Base Installation Ducted Detailed Side Views AZ2500/3500 SeriesExterior Grilles Sample CalculationsPower Connection For Deluxe Series 2500 230/208 Volt Unit Installation Line Cord Connected Units230/208 Volt Unit Installation Permanent Connected Units 265 or 277 Volt Unit Installation Permanent Connected UnitsPower Connection Kits For Premium Series 230/208 Volt InstallationsReplacement of Existing Chassis Maximum Connected Load For Deluxe Series 2500 Cooling Performance Data Heat Pump Performance DataLatent System Capacity Formula for Calculating Operating Costs Using Above Data Normal Yearly Operating DataTypical 2500 Series Wiring Diagram Typical 2500 Series Schematic DiagramDrive Board Unit Typical 3500 Series Wiring Diagram Typical 3500 Series Schematic DiagramBoard Unit Typical 5500 Series Wiring Diagram Typical 5500 Series Schematic DiagramSuggested Bid Form Specifications Page Alternate specification for molded wall case Deluxe Line Dry Air 25 & 3500 Series Receptacles/Sub-Bases Complete Accessory List Kit Number Description For Additional Information Refer toGeneral Installation Suggestions Electrical Wiring InstallationNew Installations Replacement InstallationsAlphabetical Index CategoryZoneline

5500 specifications

The GE 5500 is a sophisticated gas turbine that represents a benchmark in the realm of power generation technology. Known for its impressive performance and efficiency, the GE 5500 has garnered attention in various industries, particularly in energy production. Designed for combined-cycle applications, this turbine effectively leverages both gas and steam cycles to optimize electricity generation.

One of the standout features of the GE 5500 is its advanced aerodynamics, which enhance the efficiency of the combustion process. The turbine employs state-of-the-art combustion technology that allows for high operational flexibility and minimizes emissions, meeting stringent environmental standards. This is particularly important in today’s energy landscape, where sustainability is a crucial focus.

The GE 5500 is equipped with a robust control system that utilizes digital twin technology. This innovative approach allows operators to simulate and analyze the performance of the turbine virtually, leading to improved operational efficiency and reduced downtime. Additionally, this turbine features an integrated health monitoring system that provides real-time data on performance metrics, allowing for predictive maintenance and enhancing overall reliability.

The materials used in the construction of the GE 5500 are engineered to withstand high temperatures and stress levels, ensuring longevity and durability. This includes high-performance alloys that maintain structural integrity even under extreme operating conditions.

Installation and maintenance of the GE 5500 are streamlined through its modular design, which simplifies access to components and reduces service time. This efficiency translates into lower operational costs, making the GE 5500 an economically favorable choice for utilities and independent power producers.

Furthermore, the GE 5500 can be integrated into a variety of power plant configurations, whether for peaking power or baseload operations, which adds to its versatility. Its ability to quickly ramp up production makes it particularly valuable in an energy market characterized by fluctuating demand.

Overall, the GE 5500 gas turbine is a remarkable engineering feat that combines cutting-edge technology with practical design. Its efficiency, reliability, and adaptability position it as a leading choice for power generation needs, meeting the requirements of modern energy systems while contributing to a more sustainable future.