GE 5500 manual Receptacles/Sub-Bases

Page 55

Receptacles/Sub-Bases

Tandem

Perpendicular

Large Tandem

230/208V 15 Amp

230/208V 20 Amp

230/208V 30 Amp

NEMA6-20R

NEMA6-20R

NEMA6-30R

Premium Line: 5500 Series - Power Connection Kits are

REQUIRED on Premium Zoneline Chassis. (see chart below) The correct kit for the installation is determined by the voltage and amperage of the electrical circuit and the means of connecting the unit to the building wiring. If the unit is to be plugged into a receptacle, a line cord kit would be used; if the unit is to be permanently connected, a permanent connection kit would be used. 265 volt cord set units must be installed in compliance with National Electrical Code.®

Power Connection Kits - Required on premium models. See specification sheet for heater KW and branch circuit ampacity.

265V 15 Amp

265V 20 Amp

265V 30 Amp

NEMA7-15R;

NEMA7-20R;

NEMA7-30R;

receptacle used on

receptacle used on

receptacle used on

265V sub-base

265V sub-base

265V sub-base

Sub-bases

 

RAK204U

RAK204D20

RAK204D30

RAK204E15

RAK204E20

RAK204E30

 

Voltage

N/A

230/208

230/208

265

265

265

Amps

N/A

15/20

30

15

20

30

Receptacle

N/A

NEMA6-20R

NEMA6-30R

NEMA7-15R

NEMA7-20R

NEMA7-30R

265 Volt units are to be direct connected. Cordset through enclosed chaseway into interior sub-base receptacle meets the NEC requirements.

RAK3152/3202/3302

230/208 volt Line Cord Connection Kit

230/208 Volt

Line Cord Connected Units

 

 

 

 

 

Power Connection

 

RAK3152

RAK3202

RAK3302

Kit

 

 

 

 

Heater KW

 

2.55/2.09

3.45/2.82

5.00/4.09

Watts

 

2,550/2,090

3,450/2,820

5,000/4,090

BTUH

 

8,600/7,100

11,700/9,600

17,000/13,900

Amps

 

11.0/10.0

15.0/13.6

21.7/19.7

Min. Circuit Amps

 

15

20

30

Recommended

 

15 Amp

20 Amp

30 Amp

Protective

 

Time Delay

Time Delay

Time Delay

Device

 

Fuse or Breaker

Fuse or Breaker

Fuse or Breaker

265 Volt

Permanent Connected Units**

(Cord Set)

 

 

 

 

 

RAK5152

RAK5172

RAK5202

 

RAK5302

 

 

 

 

 

1.7

3.0

3.7

 

5.0

1,700

3,000

3,700

 

5,000

5,800

10,200

12,600

 

17,000

6.4

11.3

14.0

 

18.9

15

15

20

 

30

15 Amp

15 Amp

20 Amp

 

30 Amp

Time Delay Fuse

Time Delay Fuse

Time Delay Fuse

 

Time Delay Fuse

 

Deluxe Series - Heat Pump Units

 

Premium Series - Heat Pump Units

 

 

 

 

 

 

 

 

 

 

3500 Series Units

 

 

5500 Series Units

 

230/208V Models

AZ35H07D

AZ35H09D

AZ35H12D

 

AZ35H15D

AZ55H07D

AZ55H09D

AZ55H12D

AZ55H15D

Capacity

 

 

 

 

 

 

 

 

 

Cooling BTUH

7,100/6,900

9,000/8,800

11,700/11,500

 

14,600/14,300

7,100/6,800

9,000/8,800

11,800/11,600

14,700/14,400

EER (BTU/Watt)

11.8/11.8

11.5/11.5

10.9/10.9

 

9.6/9.6

12.0/12.0

11.5/11.5

10.9/10.9

10.0/10.0

Dehumidification Pts/Hr

1.7

2.7

3.6

 

4.5

1.7

2.8

3.6

4.8

Sensible Heat Ratio @ 230 Volts

75%

68%

67%

 

67%

75%

67%

68%

65%

CFM, Indoor Fan High

250

260

280

 

310

240

290

330

350

CFM, Indoor Fan Low

220

230

250

 

280

220

270

310

330

Vent CFM

40/35

65/60

70/65

 

70/65

40/35

65/60

70/65

70/65

Power/Ratings

 

 

 

 

 

 

 

 

 

Power Factor

95

96

97

 

94

95

96

94

95

Watts

600/585

785/765

1075/1055

 

1520/1490

590/565

785/765

1085/1065

1470/1440

Amperes, F.L.

2.8/3.0

3.6/3.9

4.9/5.3

 

7.0/7.5

2.7/2.9

3.6/3.9

5.1/5.5

6.7/7.3

Amperes, L.R.

19.0

21.0

33.0

 

38.0

19.0

21.0

33.0

38.0

Reverse Cycle Heat BTUH

6400/6200

8400/8200

10900/10700

 

13400/13200

6,400/6,200

8,400/8,200

10,900/10,700

13,400/13,200

COP

3.5/3.5

3.5/3.5

3.3/3.3

 

3.1/3.1

3.5/3.5

3.5/3.5

3.3/3.3

3.1/3.1

Watts

535/520

705/685

970/950

 

1265/1250

535/520

705/685

970/950

1,265/1,250

Amps

2.4/2.6

3.1/3.4

4.3/4.7

 

5.8/6.3

2.4/2.6

3.1/3.3

4.3/4.7

5.8/6.3

Weight (Net/Ship)**

96/112

99/115

111/127

 

121/137

101/117

106/122

116/132

123/139

Sound Transmission Class (STC)

28

28

28

 

28

28

28

28

28

 

 

 

 

 

 

 

 

 

 

265V Models

AZ35H07E

AZ35H09E

AZ35H12E

 

AZ35H15E

AZ55H07E

AZ55H09E

AZ55H12E

AZ55H15E

Capacity

 

 

 

 

 

 

 

 

 

Cooling BTUH

7,100

9,000

11,700

 

14,600

7,100

9,000

11,800

14,700

EER (BTU/Watt)

11.8

11.5

10.9

 

9.6

12.0

11.5

10.9

10.0

Dehumidification Pts/Hr

1.7

2.7

3.6

 

4.5

1.7

2.8

3.6

4.8

Sensible Heat Ratio @ 265 Volts

75%

68%

67%

 

67%

75%

67%

68%

65%

CFM, Indoor Fan High

250

260

280

 

310

240

290

330

350

CFM, Indoor Fan Low

220

230

250

 

280

220

270

310

330

Vent CFM

40

65

70

 

70

40

65

70

70

Power/Ratings

 

 

 

 

 

 

 

 

 

Power Factor

96

94

94

 

96

96

94

94

96

Watts

600

785

1075

 

1520

590

785

1085

1470

Amperes, F.L.

2.4

3.2

4.4

 

6.0

2.3

3.2

4.5

5.8

Amperes, L.R.

16.0

18.0

24.0

 

31.0

16.0

18.0

24.0

31.0

Reverse Cycle Heat BTUH

6,400

8,400

10,900

 

13,400

6,400

8,400

10,900

13,400

COP

3.5

3.5

3.3

 

3.1

3.5

3.5

3.3

3.1

Watts

535

700

970

 

1265

535

705

970

1,265

Amps

2.2

2.8

3.9

 

5.0

2.2

2.8

3.9

5.0

Weight (Net/Ship)**

96/112

99/115

111/127

 

121/137

101/117

106/122

116/132

123/139

Sound Transmission Class (STC)

28

28

28

 

28

28

28

28

28

** ICR adds 3 pounds to unit weight

 

 

 

 

 

 

 

 

 

55

Image 55
Contents Architects and Engineers Design Data Manual Series Cooling with Electric Heat Series Heat Pump with Backup Resistance HeatQuick Reference 3500 Series Control PanelEER COP Series Control PanelNewest Innovation from GE Cooling With Resistance HeatImportant Notice Table of ContentsIntroduction Components of the Zoneline System Optional Accessories of the Zoneline SystemDeluxe Series shown UPC Zoneline Features Model SeriesFeatures and Benefits Electronic Temperature Limiting Fan Only Setting HIGH/LOWFan Cycle Switch SmartFan Compressor Restart DelayCorrosion Protection Optional Easy Clean Air Discharge AreaUp-Front Air Filters Concealed Manual Vent Control3500 Series Auxiliary Control SwitchesCooling Temperature Limits Heating Temperature LimitsDiagnos SeriesCentral Desk Control Resistance Heat Models Remote Thermostat ControlHeat Pump Models RAK806 Universal Control Cover LabelSee RAK806 Universal Control cover Label on Feature SeriesSpecial order, 100 piece minimum order For Use With Mechanical 4-Wire Systems OnlyRemote Control Low Voltage Wiring R1, R2, and R3Balance Point Heat Pumps and Energy SavingsHeat pump condensate Heat Pump Operation Zoneline 5500 Series Heat pump defrost Zoneline 5500 SeriesZoneline 5500 Series Heat Source Logic High Wall Mount For units Application CommentsAir Distribution RecommendationDimensions Sub-Base Wall CaseRAK204 Window, Curtain and Panel Wall Construction Wall Case Installation DataGeneral Preparation of the Wall Case for All Types of Construction Installation of Wall Case in Wall OpeningMasonry Wall Construction Brick, Frame, Stucco and Shingle ConstructionFastening Wall Case Framing for Wall CaseRoom Wall Case Cabinet Wall Section Detailed Side ViewRoom Cabinet Wall CaseBy Others RoomCabinet Wall Case Wall Case ReceptacleCaulk Wall Case Installation Cord SET ConnectedCorner and lap joints be additionally sealed Page TOP View Recommend 2 to Adjustable CaulkHoles by Installer Shown with Access Covers Removed Alternates SmallMetal Case Screw Clip Type D Type a To Secure Side Channels RAK204 Series SUB-BASE Installation and Electrical DataChaseway Option Type B Screw Green GroundCooling Condensate Condensate Disposal SystemsWall Case Room Cabinet Typical InstallationWall Case with RAD10 Drain KIT Rear GrilleGasket Cabinet Bottom Tube Cover Plate NUT Molded Case RAB77 only DetailUSE Type a Screws for Both RAB71 and RAB77 Ducted Application Considerations Ducted InstallationsNew Ducted Installations Replacements of Existing Ducted UnitsDuct Adapter Extension has 1/2 Insulation Ducted Application AZ2500/3500 SeriesDucted Detailed Side Views AZ2500/3500 Series Sub-Base InstallationSample Calculations Exterior Grilles265 or 277 Volt Unit Installation Permanent Connected Units Power Connection For Deluxe Series 2500230/208 Volt Unit Installation Line Cord Connected Units 230/208 Volt Unit Installation Permanent Connected Units230/208 Volt Installations Power Connection Kits For Premium SeriesReplacement of Existing Chassis Maximum Connected Load For Deluxe Series 2500 Heat Pump Performance Data Cooling Performance DataLatent System Capacity Normal Yearly Operating Data Formula for Calculating Operating Costs Using Above DataTypical 2500 Series Schematic Diagram Typical 2500 Series Wiring DiagramDrive Board Unit Typical 3500 Series Schematic Diagram Typical 3500 Series Wiring DiagramBoard Unit Typical 5500 Series Schematic Diagram Typical 5500 Series Wiring DiagramSuggested Bid Form Specifications Page Alternate specification for molded wall case Deluxe Line Dry Air 25 & 3500 Series Receptacles/Sub-Bases Kit Number Description For Additional Information Refer to Complete Accessory ListElectrical Wiring Installation General Installation SuggestionsReplacement Installations New InstallationsCategory Alphabetical IndexZoneline

5500 specifications

The GE 5500 is a sophisticated gas turbine that represents a benchmark in the realm of power generation technology. Known for its impressive performance and efficiency, the GE 5500 has garnered attention in various industries, particularly in energy production. Designed for combined-cycle applications, this turbine effectively leverages both gas and steam cycles to optimize electricity generation.

One of the standout features of the GE 5500 is its advanced aerodynamics, which enhance the efficiency of the combustion process. The turbine employs state-of-the-art combustion technology that allows for high operational flexibility and minimizes emissions, meeting stringent environmental standards. This is particularly important in today’s energy landscape, where sustainability is a crucial focus.

The GE 5500 is equipped with a robust control system that utilizes digital twin technology. This innovative approach allows operators to simulate and analyze the performance of the turbine virtually, leading to improved operational efficiency and reduced downtime. Additionally, this turbine features an integrated health monitoring system that provides real-time data on performance metrics, allowing for predictive maintenance and enhancing overall reliability.

The materials used in the construction of the GE 5500 are engineered to withstand high temperatures and stress levels, ensuring longevity and durability. This includes high-performance alloys that maintain structural integrity even under extreme operating conditions.

Installation and maintenance of the GE 5500 are streamlined through its modular design, which simplifies access to components and reduces service time. This efficiency translates into lower operational costs, making the GE 5500 an economically favorable choice for utilities and independent power producers.

Furthermore, the GE 5500 can be integrated into a variety of power plant configurations, whether for peaking power or baseload operations, which adds to its versatility. Its ability to quickly ramp up production makes it particularly valuable in an energy market characterized by fluctuating demand.

Overall, the GE 5500 gas turbine is a remarkable engineering feat that combines cutting-edge technology with practical design. Its efficiency, reliability, and adaptability position it as a leading choice for power generation needs, meeting the requirements of modern energy systems while contributing to a more sustainable future.