Rinnai Venting Instructions and Manual for Tankless Water Heaters RL94I and RL75I

Page 26

Venting Instructions

Intake / Exhaust Guidelines

Refer to the specific instructions on your vent product for additional

 

installation requirements.

This water heater is a direct vent water heater and therefore is certified and listed with the vent system. You must use vent components that are certified and listed with the water heater model.

Do not combine vent components from different manufacturers.

The vent system must vent directly to the outside of the building and use outside air for combustion.

Venting should be as direct as possible with a minimum number of pipe fittings.

Avoid dips or sags in horizontal vent runs by installing supports per the vent manufacturer’s instructions.

Support horizontal vent runs every four feet and all vertical vent runs every six feet or in accordance with local codes.

Vent diameter must not be reduced.

Do not connect the venting system with an existing vent or chimney.

Do not common vent with the vent pipe of any other water heater or appliance.

Vent connections must be firmly pressed together so that the gaskets form an air tight seal.

RL75i, RL94i: The vent piece connected to the water heater must be secured with one self-tapping screw.

Refer to the instructions of the vent system manufacturer for component assembly instructions.

If the vent system is to be enclosed, it is suggested that the design of the enclosure shall permit inspection of the vent system. The design of such enclosure shall be deemed acceptable by the installer or the local inspector.

Condensate

Condensate formation can occur in high efficiency direct vent appliances. To prevent condensate damage follow these instructions.

Vertical terminations must incorporate a condensate drain and trap as close as possible to the appliance.

RL75i, and RL94i water heaters have an integrated condensate collector.

Rinnai offers a condensate trap.

Regions of cold climate will create more condensate in the vent system. The condensate collector should be used in cold climates.

Use only vent that is approved and identified as acceptable for your particular model.

Do not use PVC, CPVC, ABS or galvanized material to vent this appliance.

Slope the venting toward the appliance according to the vent manufacturers installation instructions.

All condensate must drain and be disposed of per local codes.

Use only PVC or CPVC pipe for the condensate drain line.

The condensate drain pipe should be as short as possible and have a downward pitch.

Do not connect the condensate drain pipe directly to the rain sewer.

The condensate drain pipe (along its entire length) must be at least the same diameter as the drain line, (3/8 inch NPT).

The end of the condensate drain pipe should be open to the atmosphere. The end should not be under water or other substances.

Do not connect the condensate drain line with an air conditioning evaporator coil drain.

To minimize freezing of the condensate, run the condensate drain line through an interior wall or between insulation and an interior wall.

The condensate collector should be used for all hydronic heating applications.

26

VB Series Indoor LS Manual

Image 26
Contents REU-VB2528FFUD-US Table of Contents Specifications RL75i RL94i R98LSiSafety Behaviors and Practices Safety Features Consumer Safety InformationSafety Definitions Description of OperationTemperature Controller MC-91-1US & MCC-91-1USOperating Instructions Features Available on Temperature ControllersFeatures MC-91 MCC-91 MC-100 BC-100 MC-502 DescriptionModel Temperature Settings Available ºF How to Set the TemperatureTemperature Controller Settings Re-setting the Maximum Temperature RL75 and RL94 only Temperature Options Without a Temperature ControllerSetting the Sound Volume Voice Prompt MCC-91 Temperature ControllerOverview Using the Water Smart / Bath Fill FunctionSetting the Water Volume Filling the Tub Setting Controller to MuteSetting the Clock Models MC-91 and MCC-91Maintenance Error Codes Code Fault RemedyCode Water Quality Trouble Shooting for Common IssuesAccessing Operating Information Flushing the Heat Exchanger Error Code LC or Circulating PumpInstallation Instructions General InstructionsClearances from Appliance Attachment of the Water HeaterGeneral Instructions Electrical ConnectionGas Piping Pipe Sizing Procedure Example Pressure Relief Valve Maintenance Isolation Valves Installation InstructionsPressure Relief Valve Installation Instructions Water PipingFreeze Protection Piping RequirementsPressure Relief Valve Requirements Manual draining of the water heater When the water heater or external piping has frozenFreeze Protection Freeze Protection Piping KEYRecommended Piping for Basic Installation Rinnai Water HeaterRecommended Piping for Circulation Systems For this applicationCondensate Venting InstructionsIntake / Exhaust Guidelines Maximum Vent Length Vent Products Manufacturer Product PartsDescription Canadian Installations US Installations Flue Terminal Clearances ANS Z21.10.3, CSAAdditional Clearances Vent Terminal Inside CornerFlue Installation Concentric Venting RL75i, RL94i Exhaust Pipe Assembly Flue Installation R98LSi, R98LSi-ASMEAir Intake Assembly Venting Clearances to CombustiblesHorizontal with Concentric Termination Vertical TerminationsNumber Connected Accessories Necessary Water Heaters Connecting Multiple Water HeatersHigh Altitude Installations GuidelinesCanada only Location Temperature Controller InstallationConfigurations Cable Lengths and SizeMounting the Controller Outline of RemoteFor Your Safety Read Before Operating Operating InstructionsOutlet Flow Data Technical DataPressure Drop Curve Space Heating Temperature SettingReplacement PumpsDimensions RL75i, RL94i R98LSi, R98LSi-ASMELadder Diagram for RL75i and RL94i Ladder Diagram for R98LSi and R98LSi-ASME HOTConsumer Support Warranty InformationLimited Warranty What will Rinnai do? State Regulations Important In the State of Massachusetts 248 CMR 4.00Instructions d’installation Instructions dutilisationInstructions dutilisation Temp. d’eauModel Plages de température disponible ºF Plages de température avec un contrôleur de températureOptions de température sans contrôleur à distance Entretien NettoyageInstructions générales Écartements par rapport à lappareil Fixation du chauffe-eauInstructions générales Installation à altitude élevéeTuyauterie de gaz Tuyauterie deau Valve à Bille / Valve de dégagement de pression RL75i, RL94iQualité de leau Soupape de sûretéTuyauterie recommandée pour installation de base LégendeCondensat Instructions de ventilationConsignes pour aspiration/évacuation Longueur maximum de ventilation 12.5 m 10.7 mHorizontale Produits de ventilationConstructeur Produit Pièces Espacements pour terminaison de cheminée ANS Z21.10.3, CSA Nest PAS PermiseInstallation de conduit de cheminée RL75i, RL94i Montage du tuyau dévacuation Installation de conduit de cheminée R98LSi, R98LSi-ASMEEnsemble de prise dair Terminaisons horizontalesTerminaison horizontale concentrique Terminaisons verticalesInstructions dutilisation VanneMa ualmanuelleValveDiagramme en escalier RL75i, RL94i PhaseDiagramme en escalier R98LSi, R98LSiASME Phase TRE NEU RALQuest-ce qui est couvert ? Support à la clientèleInformations sur la garantie Combien de temps dure la couverture ?Que fait Rinnai pour exercer la garantie ? VB Series Indoor LS Manual VB Series Indoor LS Manual VB Series Indoor LS Manual VB2528FFU VB2735FFU VA3237FFU