Home Automation 20A00-1 System Power UP Procedure, Console Check OUT, Telephone Check OUT

Page 31

SYSTEM POWER UP PROCEDURE

1.Carefully review hookups to the zones, grounds, sounders, and consoles.

2.Disconnect 1 lead of both the interior and exterior sounders.

NOTE: Follow this power up procedure to verify proper operation of the power supply, battery charger, and low voltage cut out relay.

3.The positive lead to the battery should be disconnected at this time. Make sure that the red battery wire is not touching anything.

4.Plug in the power transformer.

-The AC ON LED should illuminate.

-Within one minute, the STATUS LED should begin blinking at a rate of 1 blink per second. This indicates that the Omni II processor and software are working.

-The PHONE LED should be OFF (if all telephones are on-hook and the RJ31X jack is properly connected.

5.Unplug the power transformer to kill the system. Connect the red battery wire to the + (positive) battery terminal. The system should not start.

6.Plug in the power transformer. The system should start.

7.Unplug the power transformer. The system should continue to run on the battery (the STATUS LED will continue to flash).

8.Plug the transformer back in and secure it to the outlet.

CONSOLE CHECK OUT

1.The console(s) should be operating. Press ' * ' to silence the trouble beeper if it is beeping. Press OFF, 1, 1, 1, 1 (or the current User code) if the alarm is tripped. If the consoles are not operating properly, make sure that no two consoles have the same address, and check the wiring.

2.With all doors and windows closed and all motion detectors secure, the bottom line of the display should read SYSTEM OK. If there are any trouble indications that occurred during installation, press ' * ' to acknowledge them and silence the beeper.

3.Set the time and date by pressing the 9 key. Enter the Master Code, then press the 2 key. Enter the time on the keypad, then the DATE (enter date as 6 characters: January 1, 00 as 010100).

4.The console should now show the time and date on the top line and "SYSTEM OK" on the bottom line.

TELEPHONE CHECK OUT

1.Verify that the Telephone Company surge arrestor is properly grounded.

2.Verify that the incoming telephone lines are run to the surge arrestor first, then from the surge arrestor to the RJ31X jack, then from the RJ31X jack to the house phones.

3.The PHONE LED, on the controller, should be off when the phones are hung up.

4.Pick up an in-house phone, wait about 1 second, then press the ' # ' key. You should hear the Voice menu on the phone. If not, check to see that the RJ31X jack is properly wired and connected to the controller. There should be no interference from the Telephone Company while the menu is being read over the phone.

Page 25

Image 31
Contents Installation Manual Page Home Automation, Inc Installation Manual Contents Installer Setup Figures Planning IntroductionController Hookup InstallationController Hookup About Security Zones Overall Connections Diagram About Fire Zones TWO-WIRE Fire Zone Connections FOUR-WIRE Fire Zone Connections Telephone Connections Refer to RJ31X Jack Connections for this configurationRJ31X Jack Connections LCD Console Hookup Console SetupConsole Self Test Console Connections Sounder Outputs Sounder Connections Controller Outputs Reset OutputsOutput Applications Home Control Modules Remote ARM/DISARM SwitchRemote Keyswitch Connections HAI Thermostats HAI Thermostat ConnectionsConnections Programmable Energy Saver ModulesTEMPERATURE, Outdoor TEMPERATURE, and Humidity Temperature / Humidity Sensor ConnectionsPesm Connections BUILT-IN Serial Port RS-232 Connections Console Check OUT System Power UP ProcedureTelephone Check OUT Fire Zone Check OUT Burglar Zone Check OUTHome Control Checkout Case of Trouble Customer CheckoutFollow this procedure for removing the controller board Description of Contact ID Digital CommunicatorDescription of 4/2 Format Opening and Closing Reports FormatSetup Control Installer SetupHouse Code Output Type Number Description Output TypesWireless Receiver Setup ZonesZone Resistors Zone Type Number Description Zone TypesType Through Z 48 Type Zone Response TimeDescription of Zone Types Latching Zone TypesENTRY/EXIT Fire Emergency Police EmergencyDuress Emergency Silent Dial OUT Supervised FireTemperature Alarm Keyswitch InputOutdoor Temperature TemperatureCommunicator Type Setup Digital CommunicatorFirst Phone NUMBER, First Account Number Second Phone NUMBER, Second Account NumberAutomatic Test Time Report OPEN/CLOSESetup Areas Control Setup AreasSetup Areas Buttons Setup Areas ZonesSetup Areas Messages Setup Areas ConsolesSET-UP Areas Thermostats Temperature Display Setup TemperaturesThermostat Type PC Access Code Setup MiscellaneousInstaller Code Enable PC AccessFire Alarm Verification Outside Siren DelayDial OUT Delay Alarm Reset TimeTime Display Enable Emergency KeysSupervise INT Sndr Supervise EXT SndrDead Line Detect AC Power FrequencyClock Adjustment Date DisplayReset System RAM Reset System EepromModel and Software Version Setup Expansion Function Types Number Description Serial 1 FunctionSerial 2 Rate VDC Omni II SpecificationsUnderwriters Laboratories UL Installation Requirements Maximum current ratings for 24-hours Hour Standby Battery CapacitySmoke Detector Installation Guidelines Zone Type Trip Trouble Description Appendix a Contact ID Reporting FormatInformation for Central Station Appendix B Digital Communicator Code SheetCode Zone Description Action to Take Code Zone Description Action to Take Code Zone Description Action to Take Code Zone Description Action to Take Page HAI New Orleans, LA U S a