Home Automation 20A00-1 installation manual Setup Zones, Wireless Receiver, Zone Resistors

Page 39

OUTPUT 7 TYPE:

0

GENERAL PURPOSE #=CHNG

OUTPUT 8 TYPE:

0

GENERAL PURPOSE #=CHNG

INTERIOR HORN:

4

INT SNDR

#=CHNG

EXTERIOR HORN:

7

EXT SNDR

#=CHNG

For output types, the current setting is shown on the bottom line. Press the ' # ' key to select a new type from a list of types. The display shows:

SELECT TYPE:

6

INT SNDR

Use the Up and Down arrow keys to scroll through the list, or select the appropriate output type number. Then press ' # ' to enter the new type.

If the Interior Horn is configured as a "General Purpose" output, Unit Number 73 is used to control the output. If the Exterior Horn is configured as a "General Purpose" output, Unit Number 74 is used to control the output. In this configuration, Unit Numbers 73 and 74 should not be used as "Flags".

SETUP ZONES

To configure the zone type for each security zone, from the Installer Setup menu, select the 2 (ZONE) key.

WIRELESS RECEIVER

A Wireless Receiver can be used to add 16 zones (33-48) to the Omni II. If used, you must enable the following item:

WIRELESS RECEIVER:

0

0=NO 1=YES

NOTES:

1.Up to 2 Model 10A06 Hardwire Expanders can be used with the Omni II. Zones 1-16 on the first Expander are Zones 17-32 on Omni II. Zones 1-16 on the second Expander are Zones 33-48 on Omni II.

2.When used, the Model 10A06 Hardwire Expander Modules must be configured under Setup Installer Expansion.

3.If a Wireless Receiver is used, a second 10A06 Hardwire Expander cannot be used also. Transmitters 1-16 on the Wireless Receiver are Zones 33-48 on Omni II.

ZONE RESISTORS

This item is used to specify if the 1000-ohm end-of-line zone resistors will be used with zone inputs other than Supervised Fire and Gas. If this item is set to "Yes", all zones other than Supervised Fire and Gas will require an end-of-line resistor.

The default setting is "Yes".

 

ZONE RESISTORS:

1

0=NO 1=YES

Page 33

Image 39
Contents Installation Manual Page Home Automation, Inc Installation Manual Contents Installer Setup Figures Planning IntroductionController Hookup InstallationController Hookup About Security Zones Overall Connections Diagram About Fire Zones TWO-WIRE Fire Zone Connections FOUR-WIRE Fire Zone Connections Telephone Connections Refer to RJ31X Jack Connections for this configurationRJ31X Jack Connections LCD Console Hookup Console SetupConsole Self Test Console Connections Sounder Outputs Sounder Connections Reset Outputs Controller OutputsOutput Applications Home Control Modules Remote ARM/DISARM SwitchRemote Keyswitch Connections HAI Thermostats HAI Thermostat ConnectionsConnections Programmable Energy Saver ModulesTEMPERATURE, Outdoor TEMPERATURE, and Humidity Temperature / Humidity Sensor ConnectionsPesm Connections BUILT-IN Serial Port RS-232 Connections System Power UP Procedure Console Check OUTTelephone Check OUT Burglar Zone Check OUT Fire Zone Check OUTHome Control Checkout Case of Trouble Customer CheckoutFollow this procedure for removing the controller board Digital Communicator Description of Contact IDDescription of 4/2 Format Opening and Closing Reports FormatInstaller Setup Setup ControlHouse Code Output Type Number Description Output TypesSetup Zones Wireless ReceiverZone Resistors Zone Type Number Description Zone TypesType Through Z 48 Type Zone Response TimeLatching Zone Types Description of Zone TypesENTRY/EXIT Fire Emergency Police EmergencyDuress Emergency Silent Dial OUT Supervised FireTemperature Alarm Keyswitch InputOutdoor Temperature TemperatureCommunicator Type Setup Digital CommunicatorFirst Phone NUMBER, First Account Number Second Phone NUMBER, Second Account NumberAutomatic Test Time Report OPEN/CLOSESetup Areas Control Setup AreasSetup Areas Buttons Setup Areas ZonesSetup Areas Consoles Setup Areas MessagesSET-UP Areas Thermostats Setup Temperatures Temperature DisplayThermostat Type PC Access Code Setup MiscellaneousInstaller Code Enable PC AccessFire Alarm Verification Outside Siren DelayDial OUT Delay Alarm Reset TimeTime Display Enable Emergency KeysSupervise INT Sndr Supervise EXT SndrDead Line Detect AC Power FrequencyClock Adjustment Date DisplayReset System Eeprom Reset System RAMModel and Software Version Setup Expansion Serial 1 Function Function Types Number DescriptionSerial 2 Rate VDC Omni II SpecificationsUnderwriters Laboratories UL Installation Requirements Maximum current ratings for 24-hours Hour Standby Battery CapacitySmoke Detector Installation Guidelines Zone Type Trip Trouble Description Appendix a Contact ID Reporting FormatInformation for Central Station Appendix B Digital Communicator Code SheetCode Zone Description Action to Take Code Zone Description Action to Take Code Zone Description Action to Take Code Zone Description Action to Take Page HAI New Orleans, LA U S a