UNDERWRITER'S LABORATORIES (UL) INSTALLATION REQUIREMENTS
The Omni II control units
1.The line carrier
2.For those zones programmed as PANIC, DURESS or POLICE EMERGENCY, the initiating device shall be a UL Listed Hold Up Device switch.
3.Connections to phone circuit must be made via the supplied cable and RJ31X Jack as shown under RJ31X JACK CONNECTIONS in this manual.
4.For connection of smoke detectors to the controller, refer to requirements under FIRE ZONE HOOKUP and FIRE ZONE CONNECTIONS diagrams in this manual.
5.The controller must be configured for 24 hour Standby Time as shown under 24 HR STANDBY CONNECTIONS diagram in this manual. Maximum current ratings for 24 hours must be observed.
6.Recognized energy limited cable shall be employed, 22 AWG minimum for all connections.
7.The audible signal appliance shall be the Listed Wheelock Model
8.For Residential Applications, the Model
9.For Commercial Applications, the Model
10.For Commercial Applications, Listed Ademco AB12 Bell and housing to be used.
11.If the remote arm/disarm switch is used, it shall be the Listed Ademco Model 9789.
12.Operation of the controls with the Programmable Energy Saver Module was not conducted by UL.
13.Operation of the Model 12A00 Wireless Receiver was not verified by UL.
14.Operation of the
15.
16.Refer to the Omni II Owner's Manual (Document No.
17.For the monitoring of burglar alarm initiating devices, the zone type shall provide an audible output (i.e., not DURESS).
18.The Omni controller must be connected (when employed) to listed carbon monoxide gas detectors (i.e. Sentrol
19.All connections to energy sensors and modules must be done to listed Class 2 circuits only.
20.The Omni II must be used in Residential Applications that are under a single ownership.
When used in UL Listed Installations, the following items apply:
1.The "High Security Mode" must be ON.
2.The "Enable Auto Bypass" feature must be OFF.
3.The "Zone Resistors" must be YES.
4.The "Supervise Int Horn" must be YES.
5.The ENTRY DELAY SHALL NOT EXCEED 45 SECONDS for Residential Applications; 60 seconds for Commercial Applications.
6.The EXIT DELAY shall not exceed 60 seconds.
7.Double Delay and Quad Delay zone types shall not be used.
8.The BEEP ON TROUBLE feature must be ON.
9.For Residential Applications the sounding device may be mounted indoors. If, however, the sounding device is connected to the "EXT HORN" terminals of the Omni II, then the OUTSIDE SIREN DELAY shall be set to 0.
Installer: NAME: __________________________________ | NUMBER: _______________________________ |