5100-I ACT WOOD INSERT
E. Metal Heat Circulating Masonry
This insert conforms with the safety standard
•The original
•If the chimney is not listed as meeting HT requirements, or if the factory built fireplace was tested prior to 1998, a full height listed chimney liner must be installed from the appliance flue collar to the chimney top.
F. Prefabricated Metal Chimney
The chimney can be new or existing, masonry or prefabricated and must meet the following minimum requirements:
•Must be minimum 6 inch (152mm) inside diameter of high temperature chimney listed to UL 103 HT (2100oF) or ULC S628.
•Must use components required by the manufacturer for installation.
•Must maintain clearances required by the manufacturer for installation.
•Refer to manufacturers instructions for installation
•This insert is listed to UL 1482 Standard and is approved for installation into listed
•The liner must be securely attached to the insert flue collar and the chimney top.
•The air flow of the
•No dilution air is allowed to enter the chimney.
1.Secure the fireplace damper in the open position. If this cannot be accomplished, it will be necessary to remove the damper
2.Seal damper area of chimney around chimney connector with a high temperature sealant or seal insert against the face of the fireplace.
3.Both methods must be removable and replaceable for cleaning and
Flue Liner with Required Air Space |
| |
Stainless Steel Chimney Connector |
| |
Must Extend to Flue Liner |
| |
Minimum 8” (203mm) Masonry Thickness |
| |
in Front of Smoke Chamber |
| |
| Airtight Insulated | |
Minimum Clearance in Accordance with |
| |
Insert Listing | Damper Plate Removed or | |
| ||
| Fastened in Open Position | |
Floor Protection in |
| |
Accordance with Insert | Seal with Non- | |
Listing | ||
Combustible Material | ||
| ||
Combustible Floor |
|
Figure 16.1
Page 16 | April 21, 2010 |