Honeywell Ademco Vista Series Commercial Burglary Partitioned Security System With Scheduling

Page 13

Zone Programming

If using 5800 Series transmitters, do not the install batteries until you are ready to enroll them. After enrolling the transmitter, the battery need not be removed. This is to prevent enrolling the wrong serial number.

PROMPTEXPLANATION

ZONE PROG?

 

1 = YES 0 = NO

0

Press 1 to enter ZONE PROGRAMMING mode. The following screens appear. Press [] to display the next screen. Press # to display a previous screen.

SET TO CONFIRM?

 

1 = YES 0 = NO

0

This prompt appears once upon entering Zone Programming Mode.

If “Yes,” Confirmation prompts will be displayed after the device’s Serial and Loop numbers have been entered later.

ENTER ZONE NO.

 

00 = QUIT

10￿

Zone 10 entered

10 ZT P RC In L

0 0

1

1 0

0 0 1

10 ZONE TYPE

PERIMETER03

Zone number 10 and Zone Type 03 entry shown

These are special zone types used with 5800 Series Wireless Pushbutton Units that result in arming the system in the STAY or AWAY mode, or disarming the system, depending on the selection made.

Enter the 2-digit zone number to be programmed, as follows: Protection Zones = 01–86

System Supervisory Zones = 88, 89, 90, 91, 92 (duress), 97 and 98 (bell supervision) Keypad Panic Zones = 95, 96, 99

Press [] to continue.

This display appears, showing a summary of the zone's current programming. ZT = Zone Type, P = Partition, RC = Report Code, In = the input type of device, and L = the device's loop number to which the sensor is connected.

Some devices can support more than one zone by means of individual loops (for example, 5801, 5804, 5816, 5817, etc.). If the zone is not programmed, the display appears as shown here. If you are checking a zone's programming, and it is programmed satisfactorily, press [#] to back up one step and enter another zone number, if desired.

Press [] to continue.

Each zone must be assigned a zone type, which defines the way in which the system responds to faults in that zone. Refer to the Zone Type Definitions section in the ADEMCO VISTA-50P/VISTA-50PUL Installation and Setup Guide for detailed definitions of each zone type. Enter the zone type desired (or change it, if necessary). Available zone types are listed below.

00

= Assign for Unused Zones

08

= 24 Hr. Auxiliary

01

= Entry/Exit #1, Burglary

09

= Fire Without Verification

02

= Entry/Exit #2, Burglary

10

= Interior Delay, Burglary

03

= Perimeter, Burglary

20

= Arm–STAY†

04

= Interior Follower, Burglary

21

= Arm AWAY†

05

= Trouble Day/Alarm Night

22

= Disarm†

06

= 24

Hr. Silent Alarm

23

= No Alarm Response

07

= 24

Hr. Audible Alarm

 

(e.g., relay activation)

Press [] to continue.

10 Partition

1

Enter the partition number (1–8)you are assigning this zone to. Press [] to continue.

10 REPORT CODE

 

1st 03 2nd 12

3C

Enter the report code. The report code consists of 2 hexadecimal digits, each in turn consisting of 2 numerical digits. For example, for a report code of "3C," enter 03 for "3" and 12 for "C."

(Refer to the System Communication section in the Installation and Setup Guide for more information about report codes and reporting formats.)

Press [] to continue.

– 13 –

Image 13
Contents VISTA50P-PRV2 5/04 Rev a $0&29,67$65,6 9,67$39,67$38Table of Contents Recommended Programming Procedure Field Group Program Field IndexField Group VISTA-50P/VISTA-50PUL Programming Form OPEN/CLOSE Report for Keyswitch Enable OPEN/CLOSE Report for59 *62 Alarm Report Codes & ID Digits for Zones 64 *67 Alarm Report Codes & ID Digits for Zones2nd Page Programming Fields press *94 Fields 1*28 1*31 are not applicable for UL installations3rd Page Programming Fields press *94 Summary of Programming Commands 1st Page Fields Partition-Specific Fields2nd Page Programming Fields press *94 Enable J7 Triggers by Partition #93 Menu Mode KEY Commands Programming With #93 Menu ModeSET to CONFIRM? Zone ProgrammingEnter Zone no Zone Type PERIMETER03Input S/N AXXX-XXXX Input TypeInput S/N Xmit to Confirm Press to Skip Series Transmitters Loop DesignationsProgram field 200 Number of Partitions Expert Mode Zone ProgrammingOn this screen Input S/N XXX-XXXXFrom Template Entering Wireless KeysPartition Enter Zone no 5804BD Wireless Key Default Templates 5804Template Loop Function Zone Type Template Loop FunctionAlpha Descriptors Programming Zone Descriptors Select Zone Descriptor modeSelect Custom Word Mode Select Default Screen modeAccept the word Select the next wordFollow the same procedure as for custom words Type the word using one of two methods as followsEnter the custom word number 01-20 you want to create Save the word by pressingSee the Relay Voice Descriptors section when Alpha Descriptor VocabularyAlpha or Fixed-Word Keypad Device ProgrammingRF Expander VIP ModuleFault AlarmRelay Programming TroubleChoices for Start/Stop Zone Types and System Operations Relay Devices ProgrammingEnter Relay # Relay Action No Response Start Event Not UsedRelay Type ECP ECP Address Module RELAY# House Code Start Partn ANY PartitionUnit Code Zone List Programming Relay Voice DescriptorsWord Index Custom Word no =QUIT Enter Index # Custom Word Substitutes for VIP Module AnnunciationPartitions System Layout WorksheetsCommunication Options by Partition System Definitions by Partition enter values or yes/noPrinter Options Access Codes & User Definitions for Partitions 1Event LOG Types Devices keypads, 4204, rf receivers, vip moduleAccess Codes & User Definitions for Partitions 5 Access Codes & User Definitions for Partitions 3Access Codes & User Definitions for Partitions 7 Zone Definition for Zones Zone Definition for Zones Zone Definition for Zones Zone Definition for Zones Zone Types Zone Definitions for System Zones 88 89, 90, 91, 97Input Types ZoneApplicable only if relays 4204, or X-10 devices are used Relay Devices WorksheetsDevice Action Event= Partition No -8, 0 = Any ZT = Zone TYPE/SYSTEM OperationScheduling Menu Prompts #80 & #81 Menu Mode KEY CommandsStart Time Scheduling WorksheetsStop Time Time Window NumberMonth/Day Partition HOLSched Num Time Window Days W T F S S HArm/Disarm commands Relay commandsBypass commands Open/Close WindowsHhmm Partition/Windows Disarm WindowArm Window Mon Tue Wed Thu Fri Sat SunPartition/Windows Disarm Window Ademco VISTA-50P/VISTA-50PUL Summary of Connections VISTA50P-PRV2 5/04 Rev. a Eileen Way, Syosset, New York