Honeywell Vista-50P/Vista-50PUL manual Relay Devices Programming, Enter Relay #

Page 26

Relay Devices Programming

From Data Field Programming Mode, press #93 to display the "ZONE PROG?" prompt. Press [0] (NO) to each menu option until the "RELAY PGM?" prompt appears. Press [1] (YES).

While in this mode, press [] to advance to next screen. Press [#] to back up to the previous screen.

PROMPTEXPLANATION

ENTER RELAY #

(00=QUIT) 01

02A EV ZL ZT P STT 0 0 00 00 0

02A ZL ZT P STOP 0 00 00 0

 

02

RELAY ACTION

 

 

NO RESPONSE

0

 

 

 

 

 

 

 

 

 

 

02

START EVENT

 

 

NOT USED

0

 

Enter the relay (output device) identification number 01-16. This is a reference number only, used for identification purposes. The actual module address and relay number on the module are programmed in the last two prompts.

Press [] to continue.

Press [] to continue.

The keypad displays a summary STOP screen.

Press [] to continue.

The Relay Action is the way in which the relay will respond when activated by the "start" event. Enter the desired action for this relay as follows:

0=not used; 1=close for 2 secs.; 2=stay closed; 3=pulse on/off

An output may be activated by an Event/Zone List combination, and/or by a Zone Type/System Operation. For an Event/Zone List combination, enter the event code as follows:

0=not used; 1=alarm; 2=fault; 3=trouble

If you are not using a Zone List to activate the relay, enter 0. Press [] to continue.

 

02

START: ZN LIST

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

02

START: ZN TYPE

 

 

NO RESPONSE

00

 

A zone list is a set of zones that can be used to initiate the start or stop relay action. If a zone list is being used to start this relay action, enter the zone list number, 1-8. If a zone list is not being used, enter 0.

Press [] to continue.

A Zone Type/System Operation can be used instead of or in addition to an Event/Zone List combination or a specific zone to start the relay action. If a Zone Type/System Operation is being used, enter the 2-digit code as listed in the table that follows.

Press [] to continue.

Choices for Start/Stop Zone Types and System Operations:

00

= No Response (Not Used)

 

23

= No Alarm Response

01

= Entry/Exit #1

31

= End of Exit Time

02

= Entry/exit #2

32

= Start of Entry Time

03

= Perimeter

33

= Any Burglary Alarm

04

= Interior Follower

34

= Code + [#] + 71 Key Entry

05

= Trouble Day/Alarm Night

 

 

= Code + [#] + 72 Key Entry

35

06

= 24-Hr. Silent

36

= At Bell Timeout **

07

= 24-Hr. Audible

37

= 2 Times Bell Timeout **

08

= 24-Hr. Auxiliary

38

= Chime

09

= Fire Alarm or Trouble

39

= Fire Alarm

10

= Interior W/Delay

40

= Bypassing

20

= Arming-STAY***

41

= AC Power Fail

21

= Arming-AWAY****

42

= System Battery Low

22

= Disarming (Code + Off)

 

 

 

*Stop condition only

**Or at disarming, whichever occurs earlier

***The output also activates when the partition is armed in the INSTANT mode

****The output also activates when the partition is armed in the MAXIMUM mode

43 = Communication failure

44 = RF Low Battery

45 = Polling Loop Failure

51 = RF Receiver Failure

52 = Kissoff

54 = Fire Zone Reset

55 = Disarm + 1 Minute

56 = XX Minutes (enter XX in field 1*74) * 57 = YY Seconds (enter YY in field 1*75) * 58 = Duress

60 = Audio Alarm Verification (must be selected for both START and STOP operation)

If you are using options 56 and/or 57 (usually as the STOP Zone Type), you must program data fields 1*74 and 1*75 for the respective relay timeouts for minutes and seconds.

– 26 –

Image 26
Contents $0&29,67$65,6 9,67$39,67$38 VISTA50P-PRV2 5/04 Rev aTable of Contents Recommended Programming Procedure Field Group Program Field IndexField Group VISTA-50P/VISTA-50PUL Programming Form 59 *62 Alarm Report Codes & ID Digits for Zones Enable OPEN/CLOSE Report forOPEN/CLOSE Report for Keyswitch 64 *67 Alarm Report Codes & ID Digits for ZonesFields 1*28 1*31 are not applicable for UL installations 2nd Page Programming Fields press *943rd Page Programming Fields press *94 Summary of Programming Commands 2nd Page Programming Fields press *94 Partition-Specific Fields1st Page Fields Enable J7 Triggers by Partition Programming With #93 Menu Mode #93 Menu Mode KEY CommandsEnter Zone no Zone ProgrammingSET to CONFIRM? Zone Type PERIMETER03Input S/N Input TypeInput S/N AXXX-XXXX Series Transmitters Loop Designations Xmit to Confirm Press to SkipExpert Mode Zone Programming Program field 200 Number of PartitionsInput S/N XXX-XXXX On this screenPartition Enter Zone no Entering Wireless KeysFrom Template Template Loop Function Wireless Key Default Templates 58045804BD Zone Type Template Loop FunctionZone Descriptors Select Zone Descriptor mode Alpha Descriptors ProgrammingAccept the word Select Default Screen modeSelect Custom Word Mode Select the next wordEnter the custom word number 01-20 you want to create Type the word using one of two methods as followsFollow the same procedure as for custom words Save the word by pressingAlpha Descriptor Vocabulary See the Relay Voice Descriptors section whenRF Expander Device ProgrammingAlpha or Fixed-Word Keypad VIP ModuleRelay Programming AlarmFault TroubleEnter Relay # Relay Devices ProgrammingChoices for Start/Stop Zone Types and System Operations Relay Action No Response Start Event Not UsedUnit Code Start Partn ANY PartitionRelay Type ECP ECP Address Module RELAY# House Code Relay Voice Descriptors Zone List ProgrammingWord Index Custom Word Substitutes for VIP Module Annunciation Custom Word no =QUIT Enter Index #Communication Options by Partition System Layout WorksheetsPartitions System Definitions by Partition enter values or yes/noEvent LOG Types Access Codes & User Definitions for Partitions 1Printer Options Devices keypads, 4204, rf receivers, vip moduleAccess Codes & User Definitions for Partitions 7 Access Codes & User Definitions for Partitions 3Access Codes & User Definitions for Partitions 5 Zone Definition for Zones Zone Definition for Zones Zone Definition for Zones Zone Definition for Zones Input Types Zone Definitions for System Zones 88 89, 90, 91, 97Zone Types ZoneDevice Action Relay Devices WorksheetsApplicable only if relays 4204, or X-10 devices are used EventZT = Zone TYPE/SYSTEM Operation = Partition No -8, 0 = Any#80 & #81 Menu Mode KEY Commands Scheduling Menu PromptsStop Time Scheduling WorksheetsStart Time Time Window NumberSched Num Time Window Days HOLMonth/Day Partition W T F S S HBypass commands Relay commandsArm/Disarm commands Open/Close WindowsArm Window Partition/Windows Disarm WindowHhmm Mon Tue Wed Thu Fri Sat SunPartition/Windows Disarm Window Ademco VISTA-50P/VISTA-50PUL Summary of Connections Eileen Way, Syosset, New York VISTA50P-PRV2 5/04 Rev. a