Page 47

D7212G

Off-board Relays

9.0Off-board Relays

9.1D8129 OctoRelay

The D8129 OctoRelay allows the addition of relay outputs to the system in groups of eight. The D7212G allows up to 24 OctoRelay outputs to be added to the system. Review Section 5.0 Power Outputs on page 29 to be sure to provide enough power for the OctoRelays and other powered devices that will be connected to the system.

OctoRelays for relay numbers 1 to 24 connect to ZONEX 1, Terminal 28. See Figure 16 on page 48.

Alarm output, auxiliary relay, sensor reset, arming status, point status, alarm memory, or remote functions can be assigned to the OctoRelay outputs individually. See Relay Parameters in the D7212G Program Entry Guide (P/N: 4998138538) for programming details.

D8129 restricted for fire systems: The D8129 relay outputs are not supervised and can not be used in fire or combined fire/ burglary installations for primary indicating devices.

9.1.1Configuring the D8129 OctoRelay

Five switches on the OctoRelay determine the relay numbers for the eight relay outputs. Refer to Table 11.

Panel Relay

D8129 OctoRelay

D8129 OctoRelay Switch

Number

Switch Setting

Setting

1 to 8

Off-On-On-On-On

ZONEX 1 Terminal 28

9 to 16

On-Off-On-On-On

ZONEX 1 Terminal 28

17 to 24

Off-Off-On-On-On

ZONEX 1 Terminal 28

Table 11: D8129 OctoRelay Switch Settings

Relay outputs may activate while you are setting the OctoRelay switches or programming the panel. You may wish to disconnect equipment connected to relay outputs before performing these functions.

CAUTION

9.1.2Relay Outputs

Each OctoRelay output provides a Form C dry contact rated for 1.0 A at 12 VDC. Normally-open, common, and normally- closed terminals are available for each relay output. When an individual output is activated, there is continuity between the normally-open and common terminals. When the output is not activated, there is continuity between the normally-closed and common terminals.

9.1.3Installation

Set the switches on the OctoRelay before installing it in the enclosure. See Section 9.1.1 Configuring the D8129 OctoRelay. Install the OctoRelay in the enclosure with the panel (see Figure 2 on page 21) or in an adjacent enclosure not more than 5 ft. (1.5 m) from the panel. Use 16 to 22 AWG wire.

Follow the procedure below to install OctoRelays in the enclosure with the panel.

1.Align the module with one of the mounting locations in the enclosure. See Figure 2 on page 21.

2.Use the screws provided with the module to secure it in the enclosure.

Use the D137 Mounting Bracket or D9002 Mounting Skirt to install OctoRelays in enclosures with no module mounting locations available.

9.1.4Wiring Connections

Power down the panel to connect OctoRelays as shown in Figure 16 on page 48. Note that OctoRelays for relay numbers 1 to 24 connect to ZONEX 1, Terminal 28.

Only one OctoRelay is shown wired to each ZONEX bus in Figure 16. Wire additional OctoRelays in parallel. Review Section

5.0Power Outputs on page 29 to be sure to provide enough power for the relays.

D7212G Operation and Installation Guide

© 2003 Bosch Security Systems

Page 47

4998138544C

Image 47
Contents Control/Communicator D7212G D7212G Operation and Installation GuideContents 11.2 10.111.1 11.0 10.013.0 Figures Tables D7212G Operation and Installation Guide OrganizationAppendix Description IntroductionGuide Organization Section DescriptionType Styles Used in the Text Related DocumentationDocumentation Conventions Part FCC RulesTips, Notes, Cautions and Warnings D7212G 9000G Series Panel Differences New Features D9412G D7412G D7212GOverview Secondary SpecificationsTelephone Connections Telephone Line Introduction Features in D7212GCompatible Accessories Ground Fault DetectStandard Features Model Display Application Components and Literature Available by Separate Order Other FeaturesControl/Communicator Assembly Listings Listings and ApprovalsBurglary Enclosure Options InstallationBeginning the Installation Before BeginningLocking the Reset Pin Installing the AssemblyConnecting Earth Ground Ground Fault Detect EnableInstall Modules and Relays Finishing the InstallationCharge the Battery While Finishing Install and Wire Detection DevicesProgramming the Panel Install the Point Chart LabelTesting the System Secondary Power Terminals Power SupplyPrimary Power Terminals Replacing the Battery Installing the BatteryDischarge Cycle Battery SupervisionBattery Charging Circuit Float Charge Battery Discharge/Recharge ScheduleColor State Charging Status and Low Battery LEDsType ActionProgrammable Power Outputs Terminals Power OutputsTotal Available Power Aux Power Terminals Continuous Current DrawVerification/Reset Relay Relay InstallationAvailable Power Fire System Power FormulaTelephone Connections Called Party Disconnect Operation Monitor LED GreenDialing Format Phone Line MonitorPosition Ground Start Ground StartPhone Monitor Select Jumper Loop StartD7212G Point Parameters On-board PointsDescription Terminals Point Sensor LoopsBell Point Zonex Bus D7212G Terminals Off-board PointsD8125, D8127 and D9127 Popit Modules Installing the D8125 Popex ModulePopit Sensor Loops Wiring Data Expansion Loops to Popex ModulesExpansion Loops Combined Length in ft. mConnecting the D8125 Popex to the D7212G Panel Radxpnts Handler Popit Module Point AssignmentsProgram Record Sheet Description Installing the OctoPOPITD8128D OctoPOPIT Module Popit LabelsLine Termination Wiring OctoPOPITsOctoPOPIT Sensor Loops Testing Off-board PointsAddress Assignment Switches D8128D Address SwitchesConnecting D8128D OctoPOPITs to the D7212G D7212G D8129 OctoRelay Panel Relay D8129 OctoRelay D8129 OctoRelay Switch NumberOff-board Relays D8129 Connections to the D7212G Arming Devices Command Center TerminalsAssigning the command center an address Address SwitchPower at Command Centers D7212G Command Center Terminal FunctionMomentary Contact KeyswitchKeyswitch Operation Maintained Contact 10.3 D279A Independent Zone ControlD7212G 11.3 D9131A Parallel Printer Interface Module InstallationPrinter Switch SDI DevicesSDI Address 11.5.2 D9133TTL-E Network Interface Module Address SettingsD7212G Programmer Access Reports Programmer and Accessory ConnectionsProgrammer Connector Accessory ConnectorProgrammer and Accessory Connections AccessoryProgramming ConnectorConnector13.1 D7212G Faceplate Faceplate 13.0Faceplate D7212G Control/Communicator, 1 Appendix a System Wiring Diagrams, Issue aD7212G Control/Communicator, 2 D7212G System Wiring Diagram, 2D7212G Control/Communicator, 3 D7212G System Wiring Diagram, 3D7212G Zonex 1, Points 9 to Appendix B Point Address ChartD7212G Index SymbolsZonex