11.0SDI Devices
11.1Description
The D7212G Panel can support a number of accessory devices off the SDI bus using Terminals 29 through 32. Some devices include the Command Centers (discussed in the previous section), the D9131A Parallel Printer Interface Module, the D9133 Serial Interface Module, the D9133DC Direct Connect Module, and the
11.2Installation
Consult the Operation and Installation Guide of the specific SDI device for complete installation instructions. SDI devices connect to the panel in parallel as shown in Table 14.
These devices may share power with the panel or be powered by a
D7212G | SDI Devices | ||
Terminal | Function | Wire Color | Function |
32 | POWER + | Red | +12 VDC |
|
|
|
|
31 | DATA BUS A | Yellow | |
|
|
|
|
30 | DATA BUS B | Green | |
|
|
|
|
29 | COMMON | Black | Common |
|
|
|
|
Table 14: SDI Device Connections
A
IMPORTANT
11.3D9131A Parallel Printer Interface Module
The Bosch Security Systems D9131A Parallel Printer Interface Module is a
11.3.1Switch Settings
Switches on the D9131A assign the address to the printer. The address determines if the printer is supervised, the printer's scope, and the area to which the printer is assigned. See Printer Parameters in the D7212G Program Entry Guide (P/N: 4998138538) for a complete description of addresses.
Table 15 shows the correct switch setting for Address 17.
Printer |
|
| Switch |
|
| ||
1 | 2 | 3 | 4 | 5 | 6 | ||
| |||||||
17 | ON | ON | ON | * | ON | ON | |
|
|
|
|
|
|
| |
* ON = Header and Form Feed |
|
|
| ||||
OFF = No Header and No Form Feed |
|
| |||||
|
|
|
|
|
|
|
Table 15: Printer Address Switch Settings
11.3.2Supervision
Supervision includes proper operation of the SDI bus, proper connection of the printer cable between the printer and the D9131A, printer paper supply, printer selected
The panel sends an SDI failure report to the receiver if it fails to communicate with the printer interface, and
SERVC PRINTER displays at the command center. The report to the receiver includes the address of the troubled D9131A to indicate which printer needs service.
If an SDI device is supervised and SDI A becomes disconnected, the device may still operate normally, depending upon environmental conditions.