D7212G
Arming Devices
10.3D279A Independent Zone Control
Any
•See the Point Assignments in the D7212G Program Entry Guide (P/N: 4998138538) for programming information.
•See the D279A Operation and Installation Guide (P/N: 46456) for wiring and operation instructions.
10.4Keyswitch
10.4.1Description
A maintained or momentary contact arming station (keyswitch) can be connected to master arm/disarm any of the areas in the system. The keyswitch is connected to an
(P/N: 4998138538).
10.4.2Programming
See Point Assignments in the D7212G Program Entry Guide (P/N: 4998138538) for the correct programming for points used for keyswitches.
10.4.3Installation
For maintained switches, connect the
For momentary switches, connect the
10.4.4Keyswitch Operation Maintained Contact
If the point to which the keyswitch is connected is programmed for a maintained contact, an open on the arming circuit arms the area. All faulted points are force armed, regardless of the entry in the FA Bypass Max program item. Returning the circuit to normal disarms the area. See Area Parameters and Point Assignments in the D7212G Program Entry Guide (P/N: 4998138538).
Momentary Contact
If the point to which the keyswitch is connected is programmed for a momentary contact, shorting the arming circuit toggles the area’s arming state between armed and disarmed. All faulted points are force armed, regardless of the entry in the FA Bypass Max program item. See Point Assignments in the D7212G Program Entry Guide (P/N: 4998138538).
Silencing the Bell
To silence the bell (stop Alarm Bell output) if the system is armed, operate the keyswitch to disarm the area. If the area is disarmed, operate the keyswitch once to start the arming process and a second time to stop the arming process and silence the bell.
MAINTAINED KEYSWITCH | MOMENTARY KEYSWITCH |
COMMON
1 kΩ *
or
33 kΩ *
POINT INPUT
| COMMON |
|
|
|
|
OPEN ON |
| 1 kΩ * |
|
|
|
|
|
| |||
|
| ||||
CIRCUIT |
| or | |||
ARMS AREA | POINT INPUT | 33 kΩ * |
|
| |
|
|
| |||
| |||||
|
|
|
|
|
SHORT ON
CIRCUIT
TOGGLES
ARMING
STATE
*Use 1 kΩ
Figure 18: Keyswitch Wiring
D7212G Operation and Installation Guide
© 2003 Bosch Security Systems | Page 51 | 4998138544C |